Plan Review Details - Permit 10020532
Plan Review Stops For Permit 10020532
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2010-03-09 Cont ID  
Sent By lmartine Date 2010-03-09 Time 12:47 Rev Time 0.00
Received By jnguyen Date 2010-03-09 Time 11:20 Sent To  
Notes
2010-03-09 12:00:44THIS PERMIT IS FOR A RESTAURANT TO TAKE PLACE IN THE
 WEST SPACE OF THE PARKING GARAGE ON THE SOUTH SIDE OF
 PCN# 74434321010250010 AT THE SECONDARY ADDRESS OF 509
 CLEMATIS ST (PRIMARY ONE BEING 500 BANYAN BLVD). I
 EXAMINED THE SITE PLANS & TALKED TO LUIS MARTINEZ TO
 CONFIRM THAT THE WORK WAS INDEED OCCURRING
 "EXCLUSIVELY" WITHIN THE PARAMETERS OF THE SPACE
 DESIGNATED AS 509 CLEMATIS ST (AND NOT ALSO WITHIN THE
 EAST SPACE LOCATED AT THE OTHER SECONDARY ADDRESS OF
 505 CLEMATIS ST). I HAVE RETURNED THE DOCUMENTS & SITE
 PLANS BACK TO THE B2 BOX DOWNSTAIRS.
  
 JOHN NGUYEN
 GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE: (561) 822-1239
 FAX: (561) 822-1249
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-04-29 Cont ID  
Sent By lmartine Date 2010-04-29 Time 14:18 Rev Time 0.00
Received By lmartine Date 2010-04-29 Time 14:18 Sent To  
Notes
2010-04-29 14:19:20WAITING FOR IMPACT STAMP AND RECEIPT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-09 Cont ID  
Sent By lmartine Date 2010-03-09 Time 08:29 Rev Time 0.00
Received By lmartine Date 2010-03-09 Time 08:29 Sent To AD
Notes
2010-03-09 09:18:46BUILDING REVIEW COMMENTS
  
  
 1)
 PALM BEACH COUNTY IMPACT FEES WILL BE REQUIRED.
  
 2)
 SHEET TS-1 SHOWS 2 EXISTING FIXED WINDOWS AT THE WEST
 ELEVATION, FLOOR PLAN INDICATES 1. PROVIDE SURVEY TO
 VERIFY WEST ELEVATION IS NOT A '0' LOT LINE.
  
 3)
 ENERGY CALCULATIONS CALL FOR A SOLID CORE ENTRY DOOR,
 THE PLANS INDICATE AN EXISTING GLASS ENTRY DOOR ? THE
 CALCULATIONS ALSO REFERENCE A METAL BUILDING WITH R/19
 ROOF INSULATION ?
  
 4)
 SHEET A-1-0 FINISH NOTE # 10 CALLS FOR 1 3/4" SOLID
 CORE DOORS, IF THAT IS THE CASE THEN YOUR 2'10"
 INTERIOR DOORS WILL NOT MEET THE MINIMUM 32" CLEAR
 WIDTH REQUIREMENT OF 11-4.13.5 FBC 2007.
  
  
  
  
  
 LUIS MARTINEZ
 561-805-6710
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-04-12 Cont ID  
Sent By jleahy Date 2010-04-12 Time 11:06 Rev Time 0.00
Received By jleahy Date 2010-04-12 Time 11:06 Sent To  
Notes
2010-04-12 11:08:33NO OUTLETS SHOWN FOR SHOW WINDOW (2) REQUIRED.
  
 NO MAIN SHOWN ON 208V PANEL "B" REQUIRED.
  
 ALL "B" CKTS ARE SHOWN AS 277 VOLTS
  
 JAKE LEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-03-04 Cont ID  
Sent By btrobaug Date 2010-03-04 Time 16:57 Rev Time 0.00
Received By btrobaug Date 2010-03-04 Time 12:50 Sent To  
Notes
2010-03-04 14:06:24 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 ALL COMMENTS RELATE TO SHEETS E-1.0 & E-2.0, UNLESS
 OTHERWISE NOTED. ALL CODE ARTICLES REFERENCED ARE 2008
 NEC UNLESS OTHERWISE NOTED.
  
 1} THE NOTES ON SHEET E-1.0#1 & 11 INCORRECTLY
 REFERENCE CODES FOR WHICH ARE NOT CURRENT FOR THIS
 PROJECT APPLICATION DATE, SEE REFERENCE STANDARDS
 ABOVE. THE REFERENCES TO CHAPTER 13 INTHE NOTES ARE
 FROM THE 2004 FBC, SEE 2007 FBC.
  
 2} PER CHAPTER 13 FBC SEE THE FOLLOWING: 13-415.AB.5
 INTERIOR LIGHTING POWER, SCOPE. THE INTERIOR LIGHTING
 POWER ALLOWANCE FOR A BUILDING OR A SEPARATELY METERED
 OR PERMITTED PORTION OF A BUILDING SHALL BE DETERMINED
 BY THE SPACE-BY-SPACE METHOD DESCRIBED IN SECTION
 13-415.B.1. TRADE-OFFS OF INTERIOR LIGHTING POWER
 ALLOWANCE AMONG PORTIONS OF THE BUILDING FOR WHICH A
 DIFFERENT METHOD OF CALCULATION HAS BEEN USED ARE NOT
 PERMITTED. THE INSTALLED INTERIOR LIGHTING POWER
 IDENTIFIED IN ACCORDANCE WITH SECTION 13-415.AB.5.1
 SHALL NOT EXCEED THE INTERIOR LIGHTING POWER ALLOWANCE
 DEVELOPED IN ACCORDANCE WITH SECTION13-415.B.1*** SHOW
 COMPLIANCE ON THE PLAN. THIS CAN BE DEMONSTRATED ON THE
 PLANS INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN
 FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS.
 INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE
 WITH THE ONES IN THE CALCULATIONS.
  
 3} 13-415.1.AB.1.2 SPACE CONTROL. EACH SPACE ENCLOSED
 BY CEILING-HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE
 CONTROL DEVICE TO INDEPENDENTLY CONTROL THE GENERAL
 LIGHTING WITHIN THE SPACE. SEE BATHROOMS.NOTE \: THE
 SINGLE POLE SWITCHES SHOWN ON THE PLAN WILL NOT
 CORRECTLY OVERIDE THE TIME CLOCK FOR NO MORE THAN FOUR
 HOURS. 13-415.AB.1.2 B
  
 4} CIRCUIT A5 IN THE WINE BAR IS LISTED AS A "SPACE" ON
 THE PANEL SCHEDULE.
  
 5} CIRCUIT A7 IN THE KITCHEN IS LISTED AS A "SPACE" ON
 THE PANEL SCHEDULE.
  
 6} CIRCUIT B18,20 FOR THE DISHWASHER IS ON A 20 AMP
 BREAKER FED WITH # 12 CU WIRE. THE EQUIPMENT SCHEDULE
 LISTS THE DISHWASHER @32 AMPS.SEE 310.16 FOR WIRE SIZE,
 CORRELATE WITH EQUIPMENT SCHEDULE.
  
 7} THE AIR HANDLER ON SHEET M-1.0 IS LISTED AS 460
 VOLTS/3PHASE. THE IS LISTED @ 120/208 VOLTS 3
 PHASE.BOTH THE A/C AND CONDENSOR ARE SINGLE PHASE 208
 ON THE PANEL SCHEDULE. CORRELATE AND INDICATE WHAT THE
 EXISTING UNIT IS.
  
 8} CIRCUIT B32 IS SHOWN AS SERVING THE FLOOR MIXER IN
 THE KITCHEN AND ALSO THE WATER HEATER.408.4 NEC
  
 9} 220.14 (F) SIGN AND OUTLINE LIGHTING SIGN AND
 OUTLINE LIGHTING OUTLETS SHALL BE CALCULATED AT A
 MINIMUM OF 1200 VOLT-AMPERES FOR EACH REQUIRED BRANCH
 CIRCUIT SPECIFIED IN 600.5(A).NONE SHOWN ON THE PANEL
 SCHEDULE OR IN THE CALCULATIONS
  
 10} 220.14(G) SHOW WINDOWS SHOW WINDOWS SHALL BE
 CALCULATED IN ACCORDANCE WITH EITHER OF THE FOLLOWING:
 (1) THE UNIT LOAD PER OUTLET AS REQUIRED IN OTHER
 PROVISIONS OF THIS SECTION
 (2) AT 200 VOLT-AMPERES PER 300 MM (1 FT) OF SHOW
 WINDOW
 THERE APPEARS TO BE 16' OF SHOW WINDOW ON THE SOUTH
 SIDE OF THE BUILDING. THE RECEPTACLES INSTALLED TO
 COMPLY WITH THIS ARTICLE MUST ALSO COMPLY WITH 408.4 ,
 IDENTIFICATION.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-04-20 Cont ID  
Sent By mawillia Date 2010-04-20 Time 13:48 Rev Time 0.00
Received By mawillia Date 2010-04-20 Time 13:29 Sent To  
Notes
2010-04-20 13:48:33*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS L-S.1, A-2.2, A-2.3, A-4.0, AND
 E-2.0 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-03-12 Cont ID  
Sent By mawillia Date 2010-03-12 Time 15:13 Rev Time 0.00
Received By mawillia Date 2010-03-12 Time 14:39 Sent To  
Notes
2010-03-12 15:11:04*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS TO COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. THE 2006 EDITION OF NFPA 101 - LIFE SAFETY CODE -
 SHALL BE REFERENCED.
  
 3. NO POINT OF COMPASS INDICATED ON THE FLOOR PLAN
 SHEET(S).
  
 4. NO EXIT LIGHTS AND/OR EMERGENCY LIGHTS SHOWN ON THE
 LIGHTING PLAN (SHEET E-2.0).
  
 5. HOW WILL THE SCOPE OF WORK CAUSE MODIFICATION TO THE
 FIRE SPRINKLER AND/OR FIRE ALARM SYSTEM?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-06-02 Cont ID  
Sent By vmolina Date 2010-06-02 Time 13:03 Rev Time 0.00
Received By vmolina Date 2010-06-02 Time 13:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2010-04-08 Time   Rev Time 0.00
Received By jwitmer Date 2010-04-08 Time 10:40 Sent To  
Notes
2010-04-08 10:51:05INCOMING SENT TO C-17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-22 Cont ID  
Sent By rbrown Date 2010-03-22 Time 15:08 Rev Time 0.00
Received By rbrown Date 2010-02-25 Time 08:58 Sent To  
Notes
2010-03-02 16:57:45NEW TRACKING # B-2
2010-02-25 09:10:06SENT TO C-20.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2010-05-05 Cont ID  
Sent By lmartine Date 2010-04-30 Time 08:09 Rev Time 0.00
Received By lmartine Date 2010-04-30 Time 08:09 Sent To  
Notes
2010-05-05 08:10:16SEE COUNTY STAMP ON SHEET A-1.0

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2010-05-04 Cont ID  
Sent By rregueir Date 2010-05-04 Time 13:56 Rev Time 0.00
Received By rregueir Date 2010-05-04 Time 13:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2010-04-28 Time   Rev Time 0.00
Received By hmoser Date 2010-04-28 Time 07:09 Sent To  
Notes
2010-05-04 13:56:13REVIEW COMPLETED BY RON REGUEIRO ON 5/4/10

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-03-22 Cont ID  
Sent By dwise Date 2010-03-22 Time 14:34 Rev Time 0.00
Received By dwise Date 2010-03-22 Time 12:58 Sent To  
Notes
2010-03-22 14:34:02MECHANICAL PLAN REVIEW COMMENTS:
  
 1. ASHRAE -62-04 FRESH AIR CALCULATION - THE SPACE HAS
 BEEN IMPROPERLY CLASSIFIED PURSUANT TO EITHER ASHRAE
 62-04 OR FBCM AS A "MERCANTILE" SPACE. THIS IS THE
 BUILDING CODE CLASSIFICATION OF THE PROPOSED OCCUPANCY
 AND IS NOT APPLICABLE TO THE REQUIRED VENTILATION RATES
 FOR THE INTENDED USE. PLEASE REVISE THE FRESH AIR
 CALCULATIONS TO ACCURATELY REFLECT THE USAGE OF THE
 SPACE PURSUANT TO EITHER THE CODE ITSELF OF ASHRAE
 62-04. PLEASE SHOW THE BASIS/METHODOLOGY UTILIZED FOR
 YOUR CALCUATION.
 2. THE PROJECT MANUAL N REFLECTS SOLAR AND TRANSMISSION
 HEAT GAINS IN NORTH AND EAST DIRECTIONS, BUT THE
 PROJECT APPEARS TO BE CONFIGURED WITH GLAZING
 PREDOMINATELY LOCATED IN THE SOUTH AND WEST
 ORIENTATIONS, BOTH OF WHICH APPEAR TO REFLECT THE
 "WORST CASE" SCENARIO. PLEASE CHECK ALL TRANSMISSION
 GAIN COMPONENTS LISTED IN THE MANUAL N FOR VALIDITY
 WITHIN THE PROPOSED STRUCTURE AND COORDINATE.
 3. THE PROJECT MANUAL N REFLECTS 23 PERSONS FOR HEAT
 GAIN WHILE THE ACTUAL FLOOR PLAN REFLECTS 35 SEATS.
 PLEASE COORDINATE WITH THE DESIGN COMPONENTS.
 4. THE PROJECT MANUAL N REFLECTS 1200 WATTS FLOURESCENT
 LIGHTING WHILE THE ELECTRICAL PLAN INDICATES 1910 WATTS
 TOTAL WITH 710 WATTS BEING FLOURESCENT AND 1200 WATTS
 BEING IN INCANDESCENT, LED, OR POSSIBLY HALOGEN. PLEASE
 REVIEW AND COORDINATE MANUAL N CALCULATIONS WITH THE
 PROJECT PLANS AND PROVIDE SPECIFICATIONS ON THE
 PROPOSED "HIGH HAT" LIGHTING FIXTURES TO BE INSTALLED.
 5. A JUMPER DUCT TO FACILITATE AIR SUPPLY TO THE MEN'S
 RESTROOM IS INDICTED ON SHEET M-1 BUT NO INFORMATION IS
 PROVIDED FOR A JUMPER DUCT SERVING THE WOMEN'S
 RESTROOM. IS THIS JUMPER ALREADY EXISTING? THIS SEEMS
 IMPROBABLE AS THE GRID CEILING APPEARS TO BE NEW IN THE
 CORRIDOR AS WELL AS THE WOMEN'S RESTROOM GIVEN THAT AT
 LEAST ONE WALL IN THE WOMENS RESTROOM IS BEING
 RELOCATED AS PART OF THIS PROJECT. PLEASE CLARIFY.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6650 DURING
 NORMAL BUSINESS HOURS WITH QUESTIONS OR CONCERNS ABOUT
 ANY OF THESE ISSUES. I MAY ALSO BE REACHED BY EMAIL AT
 [email protected].
  
 THANK YOU,
  
 DOUG WISE
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-04-20 Cont ID  
Sent By lwagner Date 2010-04-20 Time 12:48 Rev Time 0.00
Received By lwagner Date 2010-04-20 Time 09:31 Sent To  
Notes
2010-04-20 12:49:13GREASE TRAP REQUIRES FLOW CONTROL FOR 20 GPM

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-03-22 Cont ID  
Sent By dwise Date 2010-03-22 Time 14:34 Rev Time 0.00
Received By dwise Date 2010-03-22 Time 12:58 Sent To  
Notes
2010-03-22 14:50:45PLUMBING PLAN REVIEW COMMENTS:
  
 1. A GREASE TRAP (NOTE: TRAP NOT INTERCEPTOR) IS
 REQUIRED FOR THIS PROJECT PURSUANT TO FBCP 1003.3.1
 WHICH STATES:
  
 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES REQUIRED. A GREASE INTERCEPTOR OR
 AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO
 RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH
 GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS,
 SUCH AS IN RESTAURANTS, HOTEL KITCHENS, HOSPITALS,
 SCHOOL KITCHENS, BARS, FACTORY CAFETERIAS AND CLUBS.
 FIXTURES AND EQUIPMENT SHALL INCLUDE POT SINKS,
 PRERINSE SINKS; SOUP KETTLES OR SIMILAR DEVICES; WOK
 STATIONS; FLOOR DRAINS OR SINKS INTO WHICH KETTLES ARE
 DRAINED; AUTOMATIC HOOD WASH UNITS AND DISHWASHERS
 WITHOUT PRERINSE SINKS. GREASE INTERCEPTORS AND
 AUTOMATIC GREASE REMOVAL DEVICES SHALL RECEIVE WASTE
 ONLY FROM FIXTURES AND EQUIPMENT THAT ALLOW FATS, OILS
 OR GREASE TO BE DISCHARGED.
  
 YOU SHOULD NOTE THAT THE CODE REQUIRES GREASE REMOVAL
 DEVICES IN ALL "FOOD PREPARATION AREAS" REGARDLESS OF
 WHETHER OR NOT COOKING IS PROPOSED. THIS REQUIREMENT
 ALSO INCLUDES "BARS" AND "CLUBS".
  
 2. THE SANITARY PLUMBING ISOMETRIC AND FLOOR PLAN
 SHOULD BE REVISED TO REFLECT THE PROPOSED LOCATION OF
 THE GREASE TRAP AND THE FIXTURES WHICH MUST BE
 CONNECTED TO IT.
  
 3. PLEASE PROVIDE THE MODEL, TYPE AND SPECIFICATIONS OF
 THE PROPOSED GREASE REMOVAL DEVICE (TRAP) TO ENSURE IT
 COMPLIES WITH APPLICABLE PROVISIONS OF THE FBC PLUMBING
 VOLUME.
  
 PLEASE FEEL FREE TO CONTACT ME DIRECTLY AT 561-805-6650
 IF YOU HAVE SPECIFIC QUESTIONS OR CONCERNS REGARDING
 THE ABOVE LISTED CODE REQUIREMENTS. I MAY ALSO BE
 REACHED BY EMAIL AT [email protected].
  
 THANK YOU,
  
 DOUG WISE
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2010-03-10 Cont ID  
Sent By aaponte Date 2010-03-10 Time 13:29 Rev Time 0.00
Received By aaponte Date 2010-03-10 Time 13:29 Sent To  
Notes
***NONE***