| Plan Review Stops For Permit 10020416 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2010-04-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-04-14 |
Time |
17:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-04-14 |
Time |
17:30 |
Sent To |
|
|
| Notes |
| 2010-04-14 17:31:50 | PROVISO | | | | | | 1 HR RATING REQUIRED AT CORRIDOR (MARKED PLAN) FBC | | | TABLE 1017.1 | | | SINGLE EXIT DOOR ONLY NOT TO EXCEED 44" FBC1003.6 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-03-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-03-09 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-03-09 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2010-03-09 12:16:11 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS | | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. PLEASE PROVIDE A REASONABLE VALUATION FOR THE SCOPE | | | OF WORK INCLUDED IN THIS REVISION. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2010-04-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2010-04-09 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2010-04-09 |
Time |
12:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2010-02-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2010-02-25 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2010-02-25 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2010-02-25 08:58:51 | ** DENIED ** | | | | | | | | | 1) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2.( 2004 | | | FBC AS PERMITTED). | | | THE WATTSTOPPER TS-400 DOES NOT MEET THE MAXIMUM TIME | | | ALLOWED FOR OVER RIDE OR TIME ON. IT ALLOWS 12HRS OF | | | TIME ON. THE SPECS ALSO STATE A MAXIMUM WATTAGE FOR | | | THIS DEVICE WHICH IS MUCH LESS THAN THE LOAD SHOWN ON | | | PLANS. | | | THIS COULD BE REDLINED HOWEVER REVIEWS FROM OTHER | | | TRADES ARE STILL NEEDED FOR SAME SHEET. | | | | | | | | | 2) NOTE: THE VALUE AS STATED FOR INCREASED SCOPE OF | | | WORK IS LOW. PLEASE PROVIDE CONTRACT FOR NEW SCOPE. | | | PLEASE SEE FBC 108.3 AS THE APPLIED VALUE IS TO INCLUDE | | | DESIGN FEES, ALL LABOR, EQUIPMENT AND MATERIALS EVEN IF | | | ANY OF THESE THINGS ARE OWNER SUPPLIED. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2010-04-15 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2010-04-15 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2010-04-15 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2010-04-15 14:45:55 | *****REVISION #7, DATED 03/23/2010, APPROVED***** | | | | | | | | | REVISED PLAN SHEETS 010 (OF 23 - A), 110 (OF 2 LS), AND | | | E-7/M6 WERE STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2010-02-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2010-02-22 |
Time |
15:18 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2010-02-22 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2010-02-22 15:18:14 | *****REVISION #6, DATED 2/05/2010, APPROVED***** | | | | | | | | | REVISED PLAN SHEETS 010 (OF 23 - A) AND 110 (OF 2 LS) | | | WERE STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-04-09 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-04-09 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-04-09 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2010-04-09 11:50:37 | B--12 | | 2010-04-09 11:46:46 | **************EXPEDITED*************** | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-03-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-03-09 |
Time |
12:43 |
Rev Time |
|
| Received By |
lmartine |
Date |
2010-02-18 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2010-03-12 12:45:12 | 3/12/10 PLAN FOUND IN HOLE C--11, ZONING REVIEW NOT | | | REQUIRED, LM | | 2010-03-09 12:26:49 | ROUTED TO ZONING BOX (JR); ALL OTHER TRADES COMPLETE | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
P |
Date |
2010-03-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2010-03-09 |
Time |
12:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2010-03-09 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2010-03-09 12:25:13 | PR09002167 (MASTER 08090611); PER GWEN, IMPACT FEES | | | WERE PAID FOR 46,527 SF. NEW REVISED PLAN SHOWS 36,225 | | | FOR PHASE I & PHASE II (RINK AREA AND MEZZANINES), 8110 | | | SF FOR PHASE III (PRACTICE RINK). | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2010-04-09 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2010-04-09 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2010-04-09 |
Time |
11:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2010-03-04 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2010-03-04 |
Time |
20:03 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2010-03-04 |
Time |
19:58 |
Sent To |
|
|
| Notes |
| 2010-03-04 20:02:59 | REVIEW #: 1ST (REVISION) | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. VENTILATION RATE APPEARS LOW BASED ON USE AND | | | OCCUPANT LOAD. PROVDE DETAILED VENTILATION CALCULATIONS | | | SHOWING OCCUPANCY CLASSIFICATION, OCCUPANT LOAD, | | | APPLIED VENTILATION RATE AND JUSTIFCATION FOR THE | | | DETERMINATION OF "OCCUPANCY LESS THAN 3 HOURS." | | | | | | 2. IS THIS TO BE AN UNCONDITIONED SPACE? | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|