Plan Review Details - Permit 10020416
Plan Review Stops For Permit 10020416
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-04-15 Cont ID  
Sent By shill Date 2010-04-14 Time 17:30 Rev Time 0.00
Received By shill Date 2010-04-14 Time 17:30 Sent To  
Notes
2010-04-14 17:31:50PROVISO
  
 1 HR RATING REQUIRED AT CORRIDOR (MARKED PLAN) FBC
 TABLE 1017.1
 SINGLE EXIT DOOR ONLY NOT TO EXCEED 44" FBC1003.6
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-09 Cont ID  
Sent By shill Date 2010-03-09 Time 12:14 Rev Time 0.00
Received By shill Date 2010-03-09 Time 12:14 Sent To  
Notes
2010-03-09 12:16:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE PROVIDE A REASONABLE VALUATION FOR THE SCOPE
 OF WORK INCLUDED IN THIS REVISION.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-04-09 Cont ID  
Sent By btrobaug Date 2010-04-09 Time 12:48 Rev Time 0.00
Received By btrobaug Date 2010-04-09 Time 12:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-25 Cont ID  
Sent By dpalmer Date 2010-02-25 Time 08:45 Rev Time 0.00
Received By dpalmer Date 2010-02-25 Time 08:45 Sent To  
Notes
2010-02-25 08:58:51** DENIED **
  
  
 1) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2.( 2004
 FBC AS PERMITTED).
 THE WATTSTOPPER TS-400 DOES NOT MEET THE MAXIMUM TIME
 ALLOWED FOR OVER RIDE OR TIME ON. IT ALLOWS 12HRS OF
 TIME ON. THE SPECS ALSO STATE A MAXIMUM WATTAGE FOR
 THIS DEVICE WHICH IS MUCH LESS THAN THE LOAD SHOWN ON
 PLANS.
 THIS COULD BE REDLINED HOWEVER REVIEWS FROM OTHER
 TRADES ARE STILL NEEDED FOR SAME SHEET.
  
  
 2) NOTE: THE VALUE AS STATED FOR INCREASED SCOPE OF
 WORK IS LOW. PLEASE PROVIDE CONTRACT FOR NEW SCOPE.
 PLEASE SEE FBC 108.3 AS THE APPLIED VALUE IS TO INCLUDE
 DESIGN FEES, ALL LABOR, EQUIPMENT AND MATERIALS EVEN IF
 ANY OF THESE THINGS ARE OWNER SUPPLIED.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-04-15 Cont ID  
Sent By mawillia Date 2010-04-15 Time 14:46 Rev Time 0.00
Received By mawillia Date 2010-04-15 Time 14:34 Sent To  
Notes
2010-04-15 14:45:55*****REVISION #7, DATED 03/23/2010, APPROVED*****
  
  
 REVISED PLAN SHEETS 010 (OF 23 - A), 110 (OF 2 LS), AND
 E-7/M6 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-02-22 Cont ID  
Sent By mawillia Date 2010-02-22 Time 15:18 Rev Time 0.00
Received By mawillia Date 2010-02-22 Time 14:26 Sent To  
Notes
2010-02-22 15:18:14*****REVISION #6, DATED 2/05/2010, APPROVED*****
  
  
 REVISED PLAN SHEETS 010 (OF 23 - A) AND 110 (OF 2 LS)
 WERE STAMPED, INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-04-09 Cont ID  
Sent By lmartine Date 2010-04-09 Time 11:43 Rev Time 0.00
Received By lmartine Date 2010-04-09 Time 11:43 Sent To  
Notes
2010-04-09 11:50:37B--12
2010-04-09 11:46:46**************EXPEDITED***************
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-12 Cont ID  
Sent By shill Date 2010-03-09 Time 12:43 Rev Time  
Received By lmartine Date 2010-02-18 Time 08:32 Sent To  
Notes
2010-03-12 12:45:123/12/10 PLAN FOUND IN HOLE C--11, ZONING REVIEW NOT
 REQUIRED, LM
2010-03-09 12:26:49ROUTED TO ZONING BOX (JR); ALL OTHER TRADES COMPLETE
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2010-03-09 Cont ID  
Sent By shill Date 2010-03-09 Time 12:16 Rev Time 0.00
Received By shill Date 2010-03-09 Time 12:16 Sent To  
Notes
2010-03-09 12:25:13PR09002167 (MASTER 08090611); PER GWEN, IMPACT FEES
 WERE PAID FOR 46,527 SF. NEW REVISED PLAN SHOWS 36,225
 FOR PHASE I & PHASE II (RINK AREA AND MEZZANINES), 8110
 SF FOR PHASE III (PRACTICE RINK).
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-04-09 Cont ID  
Sent By hmoser Date 2010-04-09 Time 12:17 Rev Time 0.00
Received By hmoser Date 2010-04-09 Time 11:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-03-04 Cont ID  
Sent By rregueir Date 2010-03-04 Time 20:03 Rev Time 0.00
Received By rregueir Date 2010-03-04 Time 19:58 Sent To  
Notes
2010-03-04 20:02:59REVIEW #: 1ST (REVISION)
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. VENTILATION RATE APPEARS LOW BASED ON USE AND
 OCCUPANT LOAD. PROVDE DETAILED VENTILATION CALCULATIONS
 SHOWING OCCUPANCY CLASSIFICATION, OCCUPANT LOAD,
 APPLIED VENTILATION RATE AND JUSTIFCATION FOR THE
 DETERMINATION OF "OCCUPANCY LESS THAN 3 HOURS."
  
 2. IS THIS TO BE AN UNCONDITIONED SPACE?
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***