| Plan Review Stops For Permit 10020387 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2010-03-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-03-23 |
Time |
12:16 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2010-03-23 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2010-03-23 12:17:30 | REQUIRES CITY PLACE STAMP BEFORE ISSUANCE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2010-03-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-03-08 |
Time |
10:52 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2010-03-08 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2010-03-08 11:14:11 | BUILDING PLAN REVIEW | | | PERMIT: 10020387 | | | ADD: 370 S ROSEMARY / PARKING LOT | | | CONT: SKYLINE BUILDERS | | | TEL: (561)856-6655 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) THE SUBMITTED PLANS MAY BE FLORIDA STATE APPROVED | | | THROUGH THEDEPARTMENT OF CPMMUNITY AFFAIRS BUT THE | | | SUBMITTED PLANS ARE ONLY A PARTIAL SET OF PLANS. THE | | | COMPLETE APPROVED PLANS PLAN TRACKING # 25183 HAS 21 | | | PAGES. PLEASE SUBMIT 2 COMPLETE SEETS OF PLANS WITH THE | | | FLORIDA COVER SHEET PROVIDING THE TRACKING NUMBER,CODE | | | VERSION, BUILDING TYPE MANUFACTURER, AGENCY. THE SECOND | | | ISSUE IS THE PLANS NEED TO BE CLEAR TO BE ABLE TO READ | | | AND TO ALSO SCAN FOR RECORD DETENSION. 106.1.3 QUALITY | | | OF BUILDING PLANS. | | | | | | JIM WITMER C. B. O. | | | COMMERCIAL COMBINATION PLAN REVIEW | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE | | | CUSTOMER SERVICE SURVEY AT: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2010-03-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-03-23 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2010-03-23 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2010-03-23 14:12:06 | ELECTRIC NOT REQUIRED, STATE APPROVED PLANS, SEPERATE | | | PERMIT REQUIRED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2010-02-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2010-02-24 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2010-02-24 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2010-02-24 16:22:04 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008 | | | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING | | | | | | 1} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE | | | PLANS PER 106.1.1 FBC AS AMENDED. | | | | | | 2} INDICATE THE CODE CYCLES THIS PROJECT WAS DESIGNED | | | UNDER. 2007 FBC, 2008 NEC ETC. ADD TO NOTES FOR CLARITY | | | IN THE FIELD AND COMPLIANCE WITH 106.1.3 FBC AS | | | AMENDED. | | | | | | 3} AN ELECTRICAL PERMIT IS REQUIRED FOR THE SCOPE OF | | | WORK PURPOSED. 105.1 | | | | | | 4} A SEPARATE PERMIT IS REQUIRED FOR LOW VOLTAGE AND | | | THE CARD READER.106.3.5.1.2 FBC AS AMENDED. PROVIDE | | | MANUFACTURERS SPECS FOR THE CARD READING EQUIPMENT. | | | | | | 5} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 | | | FS, RESPECTIVELY. | | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, | | | IF EXEMPTIONS APPLY. | | | | | | 6} PLEASE LOCATE ALL SERVICE EQUIPMENT ON A SITE PLAN, | | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | ALSO THE BOOTH LOCATION. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2010-03-23 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2010-03-23 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2010-03-23 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2010-03-23 12:56:38 | *****APPROVED***** | | | | | | PLAN SHEET SP-1.0 STAMPED, INITIALED, AND DATED. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2010-03-05 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2010-03-05 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2010-03-05 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2010-03-05 14:39:43 | *****UNSAT***** | | | | | | | | | 1. THE ACTUAL PROJECT SITE ADDRESS SHALL BE IN THE | | | TITLE BLOCK OF THE EACH SUBMITTED PLAN SHEET. | | | | | | 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE | | | REFERENCED. | | | | | | 3. SPECIFY THE INTERIOR FINISH MATERIAL OF THE TICKET | | | BOOTH IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-03-22 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-03-22 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-03-22 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2010-03-22 13:46:26 | *****************EXPEDITED***************** | | | B--5 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-03-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-03-08 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2010-02-16 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2010-03-04 17:30:55 | MOVED TO B--9 | | 2010-02-18 11:34:49 | C--10 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2010-03-24 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2010-03-24 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2010-03-24 |
Time |
13:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2010-03-03 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2010-03-03 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2010-03-03 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2010-03-03 10:33:07 | PLEASE SUBMIT INFORMATION REGARDING THE TICKET BOOTH | | | LOCATION WITHIN THE PARKING LOT. ATTACHED APPROVED | | | LANDSCAPE DRAWINGS TO CONFIRM COMPLIANCE WITH | | | REGULATIONS. | | | ANA MARIA APONTE 561- 822-1439 |
|
|