Plan Review Details - Permit 10020370
Plan Review Stops For Permit 10020370
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-04-19 Cont ID  
Sent By jwitmer Date 2010-04-19 Time 09:22 Rev Time 0.55
Received By jwitmer Date 2010-04-19 Time 09:22 Sent To  
Notes
2010-04-19 09:23:07WOOD FLOORING INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-03-18 Cont ID  
Sent By jwitmer Date 2010-03-18 Time 12:36 Rev Time 0.50
Received By jwitmer Date 2010-03-18 Time 12:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-02-25 Cont ID  
Sent By jwitmer Date 2010-02-25 Time 10:33 Rev Time 0.55
Received By jwitmer Date 2010-02-25 Time 10:33 Sent To  
Notes
2010-02-25 10:57:31BUILDING PLAN REVIEW
 PERMIT: 10020370
 ADD: 500 AUSTRALIAN AVE# 800
 CONT: KARL CONSTRUCTION
 TEL: (561)718-5569
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 ACTION: DENIED
  
 1) FBC* 106.1 THE NEW TYPE OF ENGINEER'S SEAL IS
 REQUIRED FOR ALL PLANS SEALED AFTER 12/31/05.
 ENGINEER'S SEALS INCLUDING THE WORD "CERTIFICATE" ARE
 NO LONGER VALID. ON 2/5/04 THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS AMENDED THE 'SEALS' RULE AND
 REQUIRED THAT ALL MEMBERS OBTAIN SEALS WITH THE WORD
 "LICENSE" INSTEAD OF "CERTIFICATE". THE EXTENDED GRACE
 PERIOD FOR COMPLIANCE ENDED ON 12/31/05. (REF: 471.025
 F.S. AND RULE 61G15-23.001 F.A.C.)
  
 RULE 61G15-23.001(1) F.A.C. THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS HAS CLEANED UP THE APPEARANCE
 OF THE SEAL BY ELIMINATING OBSOLETE CONTENT AND
 CHANGING THE WORD "CERTIFICATE" TO "LICENSE". A GRACE
 PERIOD RAN THROUGH DEC. 31,2005.
  
 PURSUANT TO SECTION 471.025 F. S. , THE BOARD HEREBY
 ESTABLISHES AS INDICATED BELOW THE FORMS OF EMBOSSING
 IMPRESSION SEALS WHICH ARE ACCEPTABLE TO THE BOARD.
 SAID SEAL SHALL BE A MINIMUM OF 1 7/8" IN DIAMETER.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 FINISH SCHEDULE OFFICE# 1, WOOD FLOORING TO BE SELECTED
 BY TENANT AND OWNER. PLEASE SUBMIT PRODUCT FLAME SPREAD
 , FIRE DEVELOPMENT AND INSTALATION LITERATURE TO DESIGN
 PROFESSIONAL ( FL 61G-15-30.006 (3) THE DELEGATED
 ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING
 DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW) BEFORE
 SUBMITAL TO THE BUILDING DEPARTMENT.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-03-16 Cont ID  
Sent By btrobaug Date 2010-03-16 Time 14:04 Rev Time 0.00
Received By btrobaug Date 2010-03-16 Time 13:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-25 Cont ID  
Sent By btrobaug Date 2010-02-25 Time 13:03 Rev Time 0.00
Received By btrobaug Date 2010-02-25 Time 12:53 Sent To  
Notes
2010-02-25 13:02:53 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 1} THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH
 A SEAL ACCEPTABLE TO THE BOARD PER 61G15-23.001, AND
 ILLUSTRATED IN SAME.
  
 2} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1*** SHOW COMPLIANCE ON THE PLAN. THIS
 CAN BE DEMONSTRATED ON THE PLANS INDICATING THE
 WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT
 CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES
 ON THE FIXTURE SCHEDULE TO CORRELATE WITH THE ONES IN
 THE CALCULATIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-03-18 Cont ID  
Sent By mawillia Date 2010-03-18 Time 13:38 Rev Time 0.00
Received By mawillia Date 2010-03-18 Time 13:31 Sent To  
Notes
2010-03-18 13:38:19*****APPROVED*****
  
 PLAN SHEET 1 OF 1 STAMPED, INITIALED, AND DATED.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-03-01 Cont ID  
Sent By mawillia Date 2010-03-01 Time 10:44 Rev Time 0.00
Received By mawillia Date 2010-03-01 Time 10:26 Sent To  
Notes
2010-03-01 10:42:54*****PARTIAL APPROVAL*****
  
 THE PLAN SHEET TO BE FIRE-STAMPED WHEN THE THE OTHER
 PLAN EXAMINERS' COMMENTS HAVE BEEN ADDRESSED. BE
 ADVISED AND/OR NOTE ON THE PLAN SHEET THE FOLLOWING
 FIRE COMMENTS:
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS TO COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-03-09 Cont ID  
Sent By btrobaug Date 2010-03-09 Time 10:26 Rev Time 0.00
Received By btrobaug Date 2010-03-09 Time 10:26 Sent To  
Notes
2010-03-09 10:40:13B-6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-03-03 Time   Rev Time 0.00
Received By lmartine Date 2010-02-16 Time 11:43 Sent To  
Notes
2010-02-18 11:47:32B--17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-03-03 Cont ID  
Sent By rregueir Date 2010-03-03 Time 16:40 Rev Time 0.00
Received By rregueir Date 2010-03-03 Time 16:40 Sent To  
Notes
2010-03-03 16:41:15PLANS TO BE STAMPED FOR MECHANICAL UPON RESUBMISSION
 AND ALL OTHER REVIEW COMMENTS FROM OTHER TRADES ARE
 ADDRESSED.

Review Stop Z ZONING
Rev No 1 Status N Date 2010-03-03 Cont ID  
Sent By aaponte Date 2010-03-03 Time 10:43 Rev Time 0.00
Received By aaponte Date 2010-03-03 Time 10:43 Sent To  
Notes
***NONE***