| 2010-02-19 12:13:13 | ** DENIED ** |
| | |
| | 1) NOTE: SEE CVR SHEET. NOTES UNDER LIFE SAFETY/FIRE |
| | SPRINKLER SECTIONS INDICATES 2004 FLORIDA BUILDING |
| | CODE. |
| | THE FOLLOWING CODES ARE RELEVANT TO THIS PROJECT AS |
| | APPLIED AFTER OCTOBER 1ST, 2009. |
| | SHEET M-1 INDICATES 2005 NEC. HOWEVER IF THIS IS THE |
| | ONLY COMMENT ON THIS SHEET THIS MAY BE REDLINED. |
| | |
| | 2007 FBC W/2009 SUPPLEMENTS. |
| | 2006 NFPA-101 |
| | 2008 NFPA-70 |
| | |
| | 2) NOTE: PERMIT APPLICATIONS AND PLANS ALL INDICATE |
| | *OLD* OKEECHOBEE RD. THIS OFFICE IS WELL AWARE THE |
| | STREET SIGNAGE INDICATING *OLD OKEECHOBEE RD*. THE |
| | ACTUAL LEGAL ADDRESS IS *OKEECHOBEE RD*. THIS HAS BEEN |
| | ADJUSTED ON APPLICATIONS. PLANS DO NOT NEED TO |
| | RE-PRINTED, THIS MAY BE ADJUSTED BY HAND. |
| | |
| | |
| | 3) NOTE: THE SUBMITTED FLA COM CALCULATIONS ARE |
| | INDICATING THE ENTIRE SPACE UNDER TYPE OF BUILDING AS |
| | OFFICE. THIS IS NOT CORRECT. ONCE *OFFICE* IS ENTERED |
| | UNDER TYPE OF BUILDING THE ALLOWANCES ARE GIVEN TO |
| | ENTIRE SQ FT UNDER OFFICE. THIS WOULD EXPLAIN THE |
| | ALLOWANCE OF NEARLY 45K WATTS OF LIGHTING ALLOWED. |
| | THE SQ FT OF OFFICE IS LISTED AS LOW AS 11,970 AND |
| | ,12312 ON PLANS. |
| | ANOTHER COORDINATION ISSUE IS SHEETS A010, A011 |
| | INDICATE ALL LIGHTING IN WAREHOUSE AS EXISTING TO |
| | REMAIN. WHY IS PRESCRIPTIVE CALCULATIONS FOR WAREHOUSE |
| | BEING ENTERED INTO THE INPUT DATA REPORT OF THE |
| | SUBMITTED CALCULATIONS? |
| | *PLEASE CONFIRM SPACE #155 IN THE IDR SHOWING MANUAL |
| | ON/OFF WHEN PLANS INDICATE AUTOMATED CONTROLS. |
| | * TRACK LIGHTING SHOWN IN AREAS 100 AND 123 ARE NOT |
| | LISTED ON FIXTURE LEGEND. IT IS NOT POSSIBLE TO |
| | COORDINATE THE IDR IF THE FIXTURES ARE NOT KNOWN. |
| | PLEASE BE SURE TO SEE THE APPENDIX SECTION B4.1.1 FOR |
| | TRACK LIGHTING REQUIREMENTS. |
| | |
| | 4) NOTE: LIGHTING IN CLOSETS SUCH AS 137 AND 137 IS TOO |
| | CLOSE TO ASSUMED DIMENSIONS REQUIRED BY NEC. SEE |
| | 410.6,410.8. THE MINIMUM CLEARANCES ARE REQUIRED |
| | WHETHER OR NOT CLOTHING IS GOING TO BE HUNG IN CLOSETS. |
| | MINIMUM CLEARANCES ARE REQUIRED FOR STORAGE OF ANY |
| | POSSIBLE COMBUSTIBLES. |
| | |
| | 5) NOTE: ROOM #112 MAY NOT BE JANITOR STORAGE. THIS |
| | ROOM IS TO BE FOR ELECTRICAL ONLY UNLESS SEPARATION IS |
| | MADE BETWEEN THE TWO LOCATIONS. |
| | PLEASE SEE 110.26 AND 240.24D. |
| | |
| | 6) NOTE: ALL NEW LIGHTING SHALL COMPLY WITH FBC |
| | 13-415.AB.1.1,.1.2 AND .1.3 FOR INTERIOR LIGHTING. |
| | ROOM #147 ON PLANS INDICATES STANDARD 3-WAY SWITCHES |
| | WITH A NOTE #2. NOTE #2 MENTIONS TO SEE LIGHTING DETAIL |
| | ON SHEET 6.1 HOWEVER PER THE LIGHTING CONTROL/CONTACTOR |
| | LEGEND AND DETAIL THIS ROOM AND CIRCUIT IS NOT LISTED. |
| | PLEASE PROVIDE REQUIRED CONTROLS FOR LOCATION AS THIS |
| | IS A SEPARATE SPACE WITHIN THE TENANT SPACE. |
| | PLEASE SEE LIGHTING SUCH AS TRACK LIGHTING, P2 FIXTURES |
| | ETC WHICH REQUIRE SEPARATE CONTROLS. PLANS INDICATE |
| | CIRCUITING TO TIME CLOCK LIGHTING CONTROLS HOWEVER NO |
| | LOCATIONS ON PLANS FOR SEPARATE CONTROLS PER |
| | 13-415.AB.1.3 COULD BE LOCATED. |
| | AREAS 158, 101 ARE THE SAME. THE SINGLE POLE LIGHT |
| | SWITCH AS AN OVER RIDE IS NOT PERMITTED. |
| | ROOM 150 IS NOT LISTED ON DETAIL CONTACTOR LEGEND. |
| | PLEASE ALSO ADJUST OVER RIDE CONTROL AS NOTED ABOVE. |
| | SINGLE POLE DIMMER DOES NOT MEET OVER RIDE SEPARATE |
| | CONTROLS. |
| | |
| | 7) NOTE: ROOM #125 IS LISTED AS ANY IT ON ARCHITECTURAL |
| | PLANS AS WELL AS ELECTRICAL PLANS AND OTHER TRADE |
| | PLANS. |
| | BASED ON THE PLANS THIS ROOM DOES *NOT* MEET ALL OF THE |
| | REQUIREMENTS PER NEC 645.4 (1-5) OR NFPA-75 2003. THE |
| | WIRING METHODS PERMITTED IN 645 ARE LESS STRINGENT FROM |
| | CHAPTERS 1-4 OF THE NEC. |
| | VERIFICATION WITH OWNER/OWNER*S IT PERSONNEL MAY BE |
| | NEEDED IF WIRING PER 645 IS DESIRED. |
| | THIS ROOM DOES NOT MEET ALL ITEMS 1-5 AS NOTED. PLEASE |
| | ADJUST PLANS FOR AN IT ROOM BY DEFINITION OR REVISE |
| | PLANS AND LIST NOTE TO STATE * NO WIRING METHODS PER |
| | NEC 645 PERMITTED* OR WORDS TO THAT AFFECT. |
| | |
| | 8) NOTE: FYI. KEEP IN MIND ALL CONDENSATE PUMPS ABOVE |
| | CEILING AREAS SHALL NOT BE CORD TYPE. SHALL BE WIRED |
| | WITH ACCEPTABLE WIRING METHODS PERMITTED IN THE NEC. |
| | CORDS ABOVE THE CEILING ARE NOT PERMITTED. 400.8 (1-5) |
| | THIS IS FOR ALL LOCATIONS. |
| | |
| | 9) NOTE: EMERGENCY AND NORMAL EGRESS LIGHTING REQUIRED |
| | FOR EXTERIOR AREAS WHERE THERE ARE SIDEWALKS AND STAIRS |
| | FOR OCCUPANCY LEADING AWAY FROM BUILDING. THERE ARE |
| | SEVERAL LOCATIONS IN WHICH THE OCCUPANT WILL EXIT THE |
| | BUILDING DOORWAY AND STILL BE REQUIRED TO TRAVERSE |
| | WALKWAY AS WELL AS STAIR AREAS. |
| | PLEASE SEE FBC 1006, NFPA101 7.8.1.3, 7.9.1.1, 7.9.2.2. |
| | ** THIS WAS BROUGHT UP IN MEETING PREVIOUSLY HELD |
| | HOWEVER MEP DESIGN TEAM WAS NOT PRESENT. IF THIS WERE |
| | THE ONLY COMMENT A PROVISO CONDITION COULD HAVE BEEN |
| | GRANTED. |
| | ** WHAT ABOUT LIGHTING IN SINK/AREA #133? |
| | |
| | |
| | 10) NOTE: ALL CIRCUITING SHALL BE SPECIFICALLY |
| | IDENTIFIED. PANEL *H* FOR EXAMPLE IS EXISTING AND IT IS |
| | UNDERSTOOD SOME OF THESE CIRCUITS MAY NOT BE KNOWN AT |
| | THIS TIME. THESE WOULD BE REQUIRED TO BE REVISED BEFORE |
| | FINAL, SUBMITTED, REVIEWED, STAMPED AND ON-SITE BEFORE |
| | FINAL INSPECTION. 408.4 |
| | LOADS AND CIRCUITING FOR OTHER NEW LOADS NEED TO |
| | COORDINATE. LOADS, ETC AS LISTED CAN NOT BE VERIFIED AS |
| | SOME ITEMS ARE LISTED BELOW. |
| | * WHAT IS CIRCUIT L-19? STATES ONLY RECEPTACLE ON PANEL |
| | SCHEDULE HOWEVER PLANS APPEAR TO SHOW SOME SORT OF |
| | APPLIANCE. |
| | * WHAT ABOUT CIRCUIT #LB-12 LISTED ON PANEL SCHEDULE |
| | FOR ROOM #130, YET PLANS ALSO INDICATES THIS FOR A |
| | DEDICATED COPIER IN ROOM #136. PLEASE ADJUST CIRCUITS, |
| | LOAD, AND PANEL. |
| | *PLEASE EXPLAIN LOADS ON RECEPTACLE CIRCUITS, HOW IS |
| | LOAD FOR ONE GENERAL RECEPTACLE THE SAME AS THE LOAD |
| | FOR SEVERAL ON ONE CIRCUIT? HOW IS THE LOAD FOR THE |
| | MICROWAVE ( LB 24) THE SAME AS THE LOAD FOR THE |
| | DEDICATED COPIER WHICH IS ALSO ON GENERAL RECEPTACLES? |
| | HOW ARE THE APPLIANCES THE SAME? |
| | PLEASE SEE 220.44, 220.12,220.14, 220.18 ETC. |
| | ** PLEASE SEE CIRCUITS LB27,29 ON PANEL SCHEDULE AND ON |
| | SHEET E3.1 AS THESE ARE BOTH LISTED FOR LIGHTING IN |
| | ROOMS 101,123 AND 130, YET POWER PLANS INDICATE |
| | DEDICATED CIRCUITS FOR FUTURE EQUIPMENT IN ROOM 147. |
| | |
| | ** PLEASE GO THROUGH ALL NEW CIRCUITING FOR LOAD, OVER |
| | CURRENT PROTECTION ETC. |
| | |
| | 11) NOTE: PLEASE PLACE NOTE ON PLANS FOR MULTI-WIRE |
| | BRANCH CIRCUITS. 210.4B OF THE NEC HAS SUBSTANTIALLY |
| | CHANGED FROM THE 2005 CODE. THIS IS NOT ONLY FOR DEVICE |
| | WITH THE SAME YOKE AS PREVIOUSLY REQUIRED IN THE CODE. |
| | THIS OFFICE IS FINDING MANY PROJECTS WHERE THIS CHANGE |
| | IN THE CODE IS NOT KNOWN. |
| | |
| | 12) NOTE: AS REQUESTED IN MEETING HELD PRIOR TO |
| | SUBMITTAL OF PERMIT APPLICATION, PLEASE SUBMIT THE |
| | MANUFACTURES SPECS/CUT SHEETS FOR THE NEW PROPOSED ATS. |
| | 110.3,90.7 |
| | ** PLEASE BE AWARE OF POSSIBLE COMMENTS FROM OTHER |
| | TRADES FOR THE POSSIBLE LOCATION OF FUTURE GENERATOR. |
| | A MEANS OF DISCONNECT FOR FEEDERS FROM GENERATOR WILL |
| | BE REQUIRED PER 225.31-225.39 UNLESS MEETING THE |
| | 702.11. K3EEP IN MIND BOTH REQUIREMENTS OF 702.11 ARE |
| | REQUIRED. *WITHIN SIGHT OF THE BUILDING AND READILY |
| | ACCESSIBLE*. IF THE UNIT IS LOCATED IN AN ENCLOSURE |
| | WHICH MAY BE REQUIRED BY OTHER TRADE REVIEWS THEN THIS |
| | MEANS OF DISCONNECT AT THE GENERATOR MAY NO LONGER BE |
| | READILY ACCESSIBLE. |
| | DISCONNECT WILL NOT BE PERMITTED INSIDE THE BUILDING |
| | WHERE IN THE EVENT OF EMERGENCY FIRE DEPARTMENT OR |
| | OTHER PERSONNEL CAN NOT GAIN IMMEDIATE AND PROTECTED |
| | ACCESS TO TURN OFF POWER. |
| | |
| | 13) NOTE: PLEASE SHOW LOCATION OF ALL ELECTRICAL PANELS |
| | AND PROPOSED LOCATIONS OF PANELS AND EQUIPMENT ON |
| | PLANS. ( DEPENDING ON NOTE12. |
| | |
| | 14) NOTE: THE MECHANICAL POWER PLANS DO INDICATE SOME |
| | GFI RECEPTACLES AS REQUIRED PER 210.63 AND 210.8B3 |
| | HOWEVER NOT ALL MEET DISTANCE REQUIRED PER 210.63 |
| | |
| | 15) NOTE: SPLICE BOXES SHALL INDICATE MINIMUM SIZING |
| | PER 314.28 |
| | |
| | 16) NOTE: PLEASE SEE FBC CHAPTER 13, SECTION 13-412 AND |
| | 13-411. THE PLANS INDICATE NEW WATER HEATING YET THE |
| | IDR DOES NOT CONTAIN ANY INFORMATION FOR WATER HEATING, |
| | OR PIPING INSULATION MINIMUMS. SEE 13-400.0.B.4 AS THIS |
| | IS REQUIRED EVEN IF NOT MEETING THE DEFINITION OF A |
| | RENOVATED BUILDING. SEE COMMENTS FROM OTHER POSSIBLE |
| | TRADES SUCH AS THE PLUMBING REVIEW. |
| | |
| | 17) NOTE: ALL TENANT MAINS/MEANS OF DISCONNECT SHALL BE |
| | LABELED IN MAIN ELECTRICAL ROOM. AS NOTED ABOVE THE |
| | DISCONNECTING MEANS FOR GENERATOR IS NOT KNOWN AT THIS |
| | TIME. |
| | PLEASE LABEL RISER. PLEASE ALSO VERIFY WITH FIRE |
| | MARSHAL THAT MORE THAN ONE DISCONNECT/METER WILL BE |
| | PERMITTED FOR SINGLE TENANT. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |