Plan Review Details - Permit 10020362
Plan Review Stops For Permit 10020362
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-03-17 Cont ID  
Sent By jwitmer Date 2010-03-17 Time 13:04 Rev Time 0.00
Received By jwitmer Date 2010-03-17 Time 13:04 Sent To  
Notes
2010-03-17 13:05:58NOTE: CONTRACTOR OR REPRESENTATIVE NEEDS TO COME IN AND
 PULL OLD SHEETS AND INSERT NEW SHEETS BEFORE TTHE PLANS
 CAN BE STAMPED.
  
 BUILDING PLAN REVIEW
 PERMIT: 10020362
 ADD: 1701 OKEECHOBEE BLVD# 1727
 CONT: DEWHURST
 TEL: (561241-1540
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
 MARCH 17/ 2010
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). ALL MISSING OR
 APPROVALS NOT ACCEPTED WILL BE CONSIDERED A REVISION
 WITH ASSOCIATED FEES AND REVIEWS.
  
 MISSING PRODUCT APPROVALS WILL BE REQUIRED BEFORE
 FRAMING INSPECTION.
  
 1) ROOFTOP UNITS PLANS HAVEN'T PROVIDED ROOF TOP
 PRESSURES FOR ROOF TOP UNITS, MISSING WIND CRITERIA:
  
 1604.4 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY LATERAL FORCES SPECIFIED
 IN THIS CHAPTER. SEE SECTION 1609 FOR WIND .
  
 1604.9 COUNTERACTING STRUCTURAL ACTIONS. STRUCTURAL
 MEMBERS, SYSTEMS, COMPONENTS AND CLADDING SHALL BE
 DESIGNED TO RESIST FORCES DUE TO WIND, WITH
 CONSIDERATION OF OVERTURNING, SLIDING, AND UPLIFT.
 CONTINUOUS LOAD PATHS SHALL BE PROVIDED FOR
 TRANSMITTING THESE FORCES TO THE FOUNDATION.
  
 1603.1.4 WIND DESIGN DATA.THE FOLLOWING INFORMATION
 RELATED TO WIND LOADS SHALL BE SHOWN, REGARDLESS OF
 WHETHER WIND LOADS GOVERN THE DESIGN OF THE
 LATERAL-FORCE-RESISTING SYSTEM OF THE BUILDING:
 1.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 1.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 1.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 1.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 1.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL.
  
 2) ANCHORING CALCULATIONS SUBMITTED FOR THE CARRIER
 MODELS DOES NOT HAVE MIAMI-DADE APPROVAL OR FLORIDA
 APPROVAL, COPIES OF REPORT ARE NOT ACCEPTABLE.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.FL ADMIN
 CODE 61G15-23.002 ENGINEERS
  
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
 3) MIAMI-DADE NOA GREENHECK FAN MODEL FGI, FGR, &
 R-SERIES STEEL/ ALUMINUM ROOF FANS, PLEASE INDICATE IF
 FANS ARE TO BE STEEL OR ALUMINUM, PRESSURES FOR STEEL
 ARE +/- 130 PSF AND FOR ALULINUM FAN =/- 70. DESIGNER
 OF RECORD WILL NEED TO PROVIDE ROOF TOP PRESSURES IF
 PAREPETS WERE CONSIDERED AND ROOF ZONE LOCATIONS, ZONE
 1, 2 OR 3.
  
 4) CENTRIFUGAL ROOF EXHAUST FANS MODEL H-G AND H-GB NOA
 07-0503.07 SPEECS WERE SUBMITTED BUT NOT THE 63 PAGE
 NOA. PLEASE SUBMIT ONLY THE APPLICABLE SECTIONS OF THIS
 REPORT THAT PERTAIN TO THIS PRODUCT AND INSTALATION.
 PLEASE ALSO NOTE PRESSURES FOR THIS ROOF TOP UNIT.
  
 5) COMPLIED. ARCH ALUMINUM NOA06-0818.02 NOTE:
 NON-IMPACT GLAZING WILL REQUIRE SHUTTERS.
  
 6) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-02-23 Cont ID  
Sent By jwitmer Date 2010-02-23 Time 16:17 Rev Time 2.22
Received By jwitmer Date 2010-02-23 Time 16:17 Sent To  
Notes
2010-02-23 16:39:53BUILDING PLAN REVIEW
 PERMIT: 10020362
 ADD: 1701 OKEECHOBEE BLVD# 1727
 CONT: DEWHURST
 TEL: (561241-1540
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 FEB.23/ 2010
  
 1) SHEET A100 TTHE IT ROOM DOES NOT INDICATE ANY RATED
 WALLS, PLEASE REVIEW SECTION 645.4(5) 2008 NEC 1 HOUR
 RATED WALLS.
  
 2) SHEET A101 WAREHOUSE OFFICE 110, PLEASE REVIEW FL
 BLDG CODE 1014.3 EXCEPTION# 1 ALLOWS 100 FT.COMMON PATH
 OF TRAVEL, PLANS INDICATE APPROXIMATELY 132 FEET.
  
 3) SHEET A101 ROOM 110 & 111 THE PLANS INDICATE FIRE
 RATED WIRRE GLASS WINDOWS (NOTE# C9), PLANS DO NOT
 INDICATE THE FIRE RATING OF OPENING PROTECTIVES PER
 TABLE 715.4 AND SECTION 715.4.6.1 SIZE LIMITATIONS.
  
 4) SHEET A100, A130, & A131 ALL SHOW A WALLBLOCKING THE
 CORRIDOR 129 AND AT THE LEFT SIDE OF THE CORRIDOR A
 SECOND PAIR OF DOORS ARE MISSING IF YOU COMPARE E2.1
 WITH THE EXITING SIGNAGE REQUIREMENTS. PLEASE REVIEW
 DEAD END CORRIDORS 1017.3 EXCEPTION 2 ALLOWS FOR 50 FT
 WHEN SPRINKLERED. IT APPEARS TO BE APPROXIMATELY 80
 FEET TO AN EXIT.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-03-17 Cont ID  
Sent By btrobaug Date 2010-03-17 Time 13:57 Rev Time 0.00
Received By btrobaug Date 2010-03-17 Time 11:44 Sent To  
Notes
2010-03-17 13:59:07ORIGINAL PLANS AND APPLICATION IN C28 WAITING FOR
 CONTRACTOR TO PUT THE RESUB SET TOGETHER.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-19 Cont ID  
Sent By dpalmer Date 2010-02-19 Time 12:12 Rev Time 0.00
Received By dpalmer Date 2010-02-19 Time 12:12 Sent To  
Notes
2010-02-19 12:13:13** DENIED **
  
 1) NOTE: SEE CVR SHEET. NOTES UNDER LIFE SAFETY/FIRE
 SPRINKLER SECTIONS INDICATES 2004 FLORIDA BUILDING
 CODE.
 THE FOLLOWING CODES ARE RELEVANT TO THIS PROJECT AS
 APPLIED AFTER OCTOBER 1ST, 2009.
 SHEET M-1 INDICATES 2005 NEC. HOWEVER IF THIS IS THE
 ONLY COMMENT ON THIS SHEET THIS MAY BE REDLINED.
  
 2007 FBC W/2009 SUPPLEMENTS.
 2006 NFPA-101
 2008 NFPA-70
  
 2) NOTE: PERMIT APPLICATIONS AND PLANS ALL INDICATE
 *OLD* OKEECHOBEE RD. THIS OFFICE IS WELL AWARE THE
 STREET SIGNAGE INDICATING *OLD OKEECHOBEE RD*. THE
 ACTUAL LEGAL ADDRESS IS *OKEECHOBEE RD*. THIS HAS BEEN
 ADJUSTED ON APPLICATIONS. PLANS DO NOT NEED TO
 RE-PRINTED, THIS MAY BE ADJUSTED BY HAND.
  
  
 3) NOTE: THE SUBMITTED FLA COM CALCULATIONS ARE
 INDICATING THE ENTIRE SPACE UNDER TYPE OF BUILDING AS
 OFFICE. THIS IS NOT CORRECT. ONCE *OFFICE* IS ENTERED
 UNDER TYPE OF BUILDING THE ALLOWANCES ARE GIVEN TO
 ENTIRE SQ FT UNDER OFFICE. THIS WOULD EXPLAIN THE
 ALLOWANCE OF NEARLY 45K WATTS OF LIGHTING ALLOWED.
 THE SQ FT OF OFFICE IS LISTED AS LOW AS 11,970 AND
 ,12312 ON PLANS.
 ANOTHER COORDINATION ISSUE IS SHEETS A010, A011
 INDICATE ALL LIGHTING IN WAREHOUSE AS EXISTING TO
 REMAIN. WHY IS PRESCRIPTIVE CALCULATIONS FOR WAREHOUSE
 BEING ENTERED INTO THE INPUT DATA REPORT OF THE
 SUBMITTED CALCULATIONS?
 *PLEASE CONFIRM SPACE #155 IN THE IDR SHOWING MANUAL
 ON/OFF WHEN PLANS INDICATE AUTOMATED CONTROLS.
 * TRACK LIGHTING SHOWN IN AREAS 100 AND 123 ARE NOT
 LISTED ON FIXTURE LEGEND. IT IS NOT POSSIBLE TO
 COORDINATE THE IDR IF THE FIXTURES ARE NOT KNOWN.
 PLEASE BE SURE TO SEE THE APPENDIX SECTION B4.1.1 FOR
 TRACK LIGHTING REQUIREMENTS.
  
 4) NOTE: LIGHTING IN CLOSETS SUCH AS 137 AND 137 IS TOO
 CLOSE TO ASSUMED DIMENSIONS REQUIRED BY NEC. SEE
 410.6,410.8. THE MINIMUM CLEARANCES ARE REQUIRED
 WHETHER OR NOT CLOTHING IS GOING TO BE HUNG IN CLOSETS.
 MINIMUM CLEARANCES ARE REQUIRED FOR STORAGE OF ANY
 POSSIBLE COMBUSTIBLES.
  
 5) NOTE: ROOM #112 MAY NOT BE JANITOR STORAGE. THIS
 ROOM IS TO BE FOR ELECTRICAL ONLY UNLESS SEPARATION IS
 MADE BETWEEN THE TWO LOCATIONS.
 PLEASE SEE 110.26 AND 240.24D.
  
 6) NOTE: ALL NEW LIGHTING SHALL COMPLY WITH FBC
 13-415.AB.1.1,.1.2 AND .1.3 FOR INTERIOR LIGHTING.
 ROOM #147 ON PLANS INDICATES STANDARD 3-WAY SWITCHES
 WITH A NOTE #2. NOTE #2 MENTIONS TO SEE LIGHTING DETAIL
 ON SHEET 6.1 HOWEVER PER THE LIGHTING CONTROL/CONTACTOR
 LEGEND AND DETAIL THIS ROOM AND CIRCUIT IS NOT LISTED.
 PLEASE PROVIDE REQUIRED CONTROLS FOR LOCATION AS THIS
 IS A SEPARATE SPACE WITHIN THE TENANT SPACE.
 PLEASE SEE LIGHTING SUCH AS TRACK LIGHTING, P2 FIXTURES
 ETC WHICH REQUIRE SEPARATE CONTROLS. PLANS INDICATE
 CIRCUITING TO TIME CLOCK LIGHTING CONTROLS HOWEVER NO
 LOCATIONS ON PLANS FOR SEPARATE CONTROLS PER
 13-415.AB.1.3 COULD BE LOCATED.
 AREAS 158, 101 ARE THE SAME. THE SINGLE POLE LIGHT
 SWITCH AS AN OVER RIDE IS NOT PERMITTED.
 ROOM 150 IS NOT LISTED ON DETAIL CONTACTOR LEGEND.
 PLEASE ALSO ADJUST OVER RIDE CONTROL AS NOTED ABOVE.
 SINGLE POLE DIMMER DOES NOT MEET OVER RIDE SEPARATE
 CONTROLS.
  
 7) NOTE: ROOM #125 IS LISTED AS ANY IT ON ARCHITECTURAL
 PLANS AS WELL AS ELECTRICAL PLANS AND OTHER TRADE
 PLANS.
 BASED ON THE PLANS THIS ROOM DOES *NOT* MEET ALL OF THE
 REQUIREMENTS PER NEC 645.4 (1-5) OR NFPA-75 2003. THE
 WIRING METHODS PERMITTED IN 645 ARE LESS STRINGENT FROM
 CHAPTERS 1-4 OF THE NEC.
 VERIFICATION WITH OWNER/OWNER*S IT PERSONNEL MAY BE
 NEEDED IF WIRING PER 645 IS DESIRED.
 THIS ROOM DOES NOT MEET ALL ITEMS 1-5 AS NOTED. PLEASE
 ADJUST PLANS FOR AN IT ROOM BY DEFINITION OR REVISE
 PLANS AND LIST NOTE TO STATE * NO WIRING METHODS PER
 NEC 645 PERMITTED* OR WORDS TO THAT AFFECT.
  
 8) NOTE: FYI. KEEP IN MIND ALL CONDENSATE PUMPS ABOVE
 CEILING AREAS SHALL NOT BE CORD TYPE. SHALL BE WIRED
 WITH ACCEPTABLE WIRING METHODS PERMITTED IN THE NEC.
 CORDS ABOVE THE CEILING ARE NOT PERMITTED. 400.8 (1-5)
 THIS IS FOR ALL LOCATIONS.
  
 9) NOTE: EMERGENCY AND NORMAL EGRESS LIGHTING REQUIRED
 FOR EXTERIOR AREAS WHERE THERE ARE SIDEWALKS AND STAIRS
 FOR OCCUPANCY LEADING AWAY FROM BUILDING. THERE ARE
 SEVERAL LOCATIONS IN WHICH THE OCCUPANT WILL EXIT THE
 BUILDING DOORWAY AND STILL BE REQUIRED TO TRAVERSE
 WALKWAY AS WELL AS STAIR AREAS.
 PLEASE SEE FBC 1006, NFPA101 7.8.1.3, 7.9.1.1, 7.9.2.2.
 ** THIS WAS BROUGHT UP IN MEETING PREVIOUSLY HELD
 HOWEVER MEP DESIGN TEAM WAS NOT PRESENT. IF THIS WERE
 THE ONLY COMMENT A PROVISO CONDITION COULD HAVE BEEN
 GRANTED.
 ** WHAT ABOUT LIGHTING IN SINK/AREA #133?
  
  
 10) NOTE: ALL CIRCUITING SHALL BE SPECIFICALLY
 IDENTIFIED. PANEL *H* FOR EXAMPLE IS EXISTING AND IT IS
 UNDERSTOOD SOME OF THESE CIRCUITS MAY NOT BE KNOWN AT
 THIS TIME. THESE WOULD BE REQUIRED TO BE REVISED BEFORE
 FINAL, SUBMITTED, REVIEWED, STAMPED AND ON-SITE BEFORE
 FINAL INSPECTION. 408.4
 LOADS AND CIRCUITING FOR OTHER NEW LOADS NEED TO
 COORDINATE. LOADS, ETC AS LISTED CAN NOT BE VERIFIED AS
 SOME ITEMS ARE LISTED BELOW.
 * WHAT IS CIRCUIT L-19? STATES ONLY RECEPTACLE ON PANEL
 SCHEDULE HOWEVER PLANS APPEAR TO SHOW SOME SORT OF
 APPLIANCE.
 * WHAT ABOUT CIRCUIT #LB-12 LISTED ON PANEL SCHEDULE
 FOR ROOM #130, YET PLANS ALSO INDICATES THIS FOR A
 DEDICATED COPIER IN ROOM #136. PLEASE ADJUST CIRCUITS,
 LOAD, AND PANEL.
 *PLEASE EXPLAIN LOADS ON RECEPTACLE CIRCUITS, HOW IS
 LOAD FOR ONE GENERAL RECEPTACLE THE SAME AS THE LOAD
 FOR SEVERAL ON ONE CIRCUIT? HOW IS THE LOAD FOR THE
 MICROWAVE ( LB 24) THE SAME AS THE LOAD FOR THE
 DEDICATED COPIER WHICH IS ALSO ON GENERAL RECEPTACLES?
 HOW ARE THE APPLIANCES THE SAME?
 PLEASE SEE 220.44, 220.12,220.14, 220.18 ETC.
 ** PLEASE SEE CIRCUITS LB27,29 ON PANEL SCHEDULE AND ON
 SHEET E3.1 AS THESE ARE BOTH LISTED FOR LIGHTING IN
 ROOMS 101,123 AND 130, YET POWER PLANS INDICATE
 DEDICATED CIRCUITS FOR FUTURE EQUIPMENT IN ROOM 147.
  
 ** PLEASE GO THROUGH ALL NEW CIRCUITING FOR LOAD, OVER
 CURRENT PROTECTION ETC.
  
 11) NOTE: PLEASE PLACE NOTE ON PLANS FOR MULTI-WIRE
 BRANCH CIRCUITS. 210.4B OF THE NEC HAS SUBSTANTIALLY
 CHANGED FROM THE 2005 CODE. THIS IS NOT ONLY FOR DEVICE
 WITH THE SAME YOKE AS PREVIOUSLY REQUIRED IN THE CODE.
 THIS OFFICE IS FINDING MANY PROJECTS WHERE THIS CHANGE
 IN THE CODE IS NOT KNOWN.
  
 12) NOTE: AS REQUESTED IN MEETING HELD PRIOR TO
 SUBMITTAL OF PERMIT APPLICATION, PLEASE SUBMIT THE
 MANUFACTURES SPECS/CUT SHEETS FOR THE NEW PROPOSED ATS.
 110.3,90.7
 ** PLEASE BE AWARE OF POSSIBLE COMMENTS FROM OTHER
 TRADES FOR THE POSSIBLE LOCATION OF FUTURE GENERATOR.
 A MEANS OF DISCONNECT FOR FEEDERS FROM GENERATOR WILL
 BE REQUIRED PER 225.31-225.39 UNLESS MEETING THE
 702.11. K3EEP IN MIND BOTH REQUIREMENTS OF 702.11 ARE
 REQUIRED. *WITHIN SIGHT OF THE BUILDING AND READILY
 ACCESSIBLE*. IF THE UNIT IS LOCATED IN AN ENCLOSURE
 WHICH MAY BE REQUIRED BY OTHER TRADE REVIEWS THEN THIS
 MEANS OF DISCONNECT AT THE GENERATOR MAY NO LONGER BE
 READILY ACCESSIBLE.
 DISCONNECT WILL NOT BE PERMITTED INSIDE THE BUILDING
 WHERE IN THE EVENT OF EMERGENCY FIRE DEPARTMENT OR
 OTHER PERSONNEL CAN NOT GAIN IMMEDIATE AND PROTECTED
 ACCESS TO TURN OFF POWER.
  
 13) NOTE: PLEASE SHOW LOCATION OF ALL ELECTRICAL PANELS
 AND PROPOSED LOCATIONS OF PANELS AND EQUIPMENT ON
 PLANS. ( DEPENDING ON NOTE12.
  
 14) NOTE: THE MECHANICAL POWER PLANS DO INDICATE SOME
 GFI RECEPTACLES AS REQUIRED PER 210.63 AND 210.8B3
 HOWEVER NOT ALL MEET DISTANCE REQUIRED PER 210.63
  
 15) NOTE: SPLICE BOXES SHALL INDICATE MINIMUM SIZING
 PER 314.28
  
 16) NOTE: PLEASE SEE FBC CHAPTER 13, SECTION 13-412 AND
 13-411. THE PLANS INDICATE NEW WATER HEATING YET THE
 IDR DOES NOT CONTAIN ANY INFORMATION FOR WATER HEATING,
 OR PIPING INSULATION MINIMUMS. SEE 13-400.0.B.4 AS THIS
 IS REQUIRED EVEN IF NOT MEETING THE DEFINITION OF A
 RENOVATED BUILDING. SEE COMMENTS FROM OTHER POSSIBLE
 TRADES SUCH AS THE PLUMBING REVIEW.
  
 17) NOTE: ALL TENANT MAINS/MEANS OF DISCONNECT SHALL BE
 LABELED IN MAIN ELECTRICAL ROOM. AS NOTED ABOVE THE
 DISCONNECTING MEANS FOR GENERATOR IS NOT KNOWN AT THIS
 TIME.
 PLEASE LABEL RISER. PLEASE ALSO VERIFY WITH FIRE
 MARSHAL THAT MORE THAN ONE DISCONNECT/METER WILL BE
 PERMITTED FOR SINGLE TENANT.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2010-02-24 Cont ID  
Sent By shill Date 2010-02-24 Time 11:50 Rev Time 0.00
Received By shill Date 2010-02-24 Time 11:50 Sent To  
Notes
2010-02-24 11:50:18NOT REQUIRED PER DW
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2010-05-06 Cont ID  
Sent By mawillia Date 2010-05-06 Time 15:18 Rev Time 0.00
Received By mawillia Date 2010-05-06 Time 14:13 Sent To  
Notes
2010-05-06 14:19:00*****REVISION 2, DATED 4/23/10, APPROVED*****
  
 REVISED PLAN SHEETS E2.1, E2.2, AND FA2.2 WERE STAMPED,
 INITIALED, AND DATED.
  
 PLEASE BE ADVISED THAT: THE ABOVE FIRE-STAMPED SHEETS
 STILL CONTAIN THE INCORRECT ADDRESS.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2010-03-18 Cont ID  
Sent By mawillia Date 2010-03-18 Time 14:34 Rev Time 0.00
Received By mawillia Date 2010-03-18 Time 13:42 Sent To  
Notes
2010-03-18 14:30:07*****APPROVED*****
  
 PLAN SHEETS A130, A131, A132, A201, A300, A301, E2.1
 E2.2, FA0.1, FA2.1, FA2.2, FS0.1, FS2.1, AND FS2.2 WERE
 STAMPED, INITIALED, AND DATED.
  
 PLEASE BE ADVISED THAT: OF THE ABOVE FIRE-STAMPED
 SHEETS, E2.1, E2.2, FA0.1, FA2.2, AND FS2.2 STILL
 CONTAIN THE INCORRECT ADDRESS.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-03-11 Cont ID  
Sent By mawillia Date 2010-03-11 Time 16:07 Rev Time 0.00
Received By mawillia Date 2010-03-11 Time 12:26 Sent To  
Notes
2010-03-11 13:10:20*****TEMP. FAILED*****
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED WHEN ALL
 SHEETS HAVE BEEN INCLUDED IN THE SUBMITTED PLAN SETS.
 ALL SHEETS SHALL CONTAIN THE CORRECT ADDRESS AND SHALL
 BE SHOWN IN THE DRAWING LIST ON SHEET CVR.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-02-22 Cont ID  
Sent By mawillia Date 2010-02-22 Time 14:15 Rev Time 0.00
Received By mawillia Date 2010-02-22 Time 10:36 Sent To  
Notes
2010-02-22 10:44:19*****DENIED*****
  
  
 1. WHAT IS ADDRESS FOR THIS PROJECT SITE LOCATION? BE
 ADVISED OF THE FOLLOWING ADDRESS DICREPANCIES:
 SUBMITTED APPLICATION (1701 OLD OKEECHOBEE ROAD), PLAN
 SHEETS CVR THRU A602 (1701 OLD OKEECHOBEE ROAD, SUITE
 1727, PLAN SHEETS M0.1 THRU FS2.2 (1727 OLD OKEECHOBEE
 ROAD)
  
 2. PLEASE EXPLAINE THE DIFFERENCES IN THE SQARE FOOTAGE
 IN THE SCOPE OF WORK SECTION COMPARED TO THE CODE
 RESEARCH SECTION AS LISTED ON THE CVR SHEET.
  
 3. STRUCTURES UNDERGOING CONSTRUCTION, ALATERATION, OR
 DEMOLITIONS OPERATIONS SHALL COMPLY WITH NFPA 241 -
 2004 EDITION.
  
 4. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 5. NO DOOR OPENING SHOWN FOR DOOR #24 ON A101 SHEET.
  
 6. ON SHEET A131 IN THE LOWERE LEFT CORNER OF THE
 DIAGRAM, IT APPEARS THAT THE PATH OF TRAVEL FOR THE
 TRAVEL DISTANCE PASSES THROUGH A WALL. PLEASE EXPLAIN.
  
 7. PROPERLY LIST THE PORTABLE FIRE EXTINGUISHERS AS
 2A10BC INSTEAD OF 2A100BC AS LISTED ON A131 & A132
 SHEETS.
  
 8. ON SHEET FA0.1, AMEND FIRE ALARM NOTE #17 TO REFLECT
 THAT DUCT SMOKE DETECTORS IATE A GENERAL FIRE ALARM (AS
 PER LOCAL CODES) .
  
 9. IT IS LISTED ON SHEET FA2.2 THAT ROOM 112 IS A
 COMBINATION JANITOR/ELECTRICAL ROOM. STORAGE AND/OR
 COMBUSTIBLES SHALL NOT BE ALLOWED IN ELECTRICAL ROOMS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date 2010-05-24 Cont ID  
Sent By rmcdouga Date 2010-05-20 Time 11:16 Rev Time 0.00
Received By rmcdouga Date 2010-05-20 Time 11:11 Sent To  
Notes
2010-05-24 11:17:09REVISION # 10050593 SENT TO MECHANICAL BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-03-10 Cont ID  
Sent By lmartine Date 2010-03-09 Time 15:20 Rev Time 0.00
Received By lmartine Date 2010-03-09 Time 15:20 Sent To  
Notes
2010-03-10 16:44:51*********************EXPEDITED******************
 C--28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-02-24 Cont ID  
Sent By kstevens Date 2010-02-24 Time 16:18 Rev Time 0.00
Received By kstevens Date 2010-02-23 Time 15:33 Sent To  
Notes
2010-02-23 15:33:59*****EXPEDITED****
 C 25
  
  
2010-02-18 08:33:53INCOMING SENT TO C-26

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-03-18 Cont ID  
Sent By rregueir Date 2010-03-18 Time 15:46 Rev Time 0.00
Received By rregueir Date 2010-03-18 Time 15:45 Sent To  
Notes
2010-03-18 15:46:37**PROVISO**
  
 WATER LEVEL MONITORING DEVICE SHALL BE INSTALLED INSIDE
 THE UNIT ON THE PRIMARY DRAIN PAN, NOT OUTSIDE THE UNIT
 IN THE PRIMARY DRAIN LINE, PER FBC_M 307.2.3.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-02-23 Cont ID  
Sent By rregueir Date 2010-02-23 Time 17:33 Rev Time 0.00
Received By rregueir Date 2010-02-23 Time 15:25 Sent To  
Notes
2010-02-23 17:33:35REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THERE ARE MULTIPLE FLEX RETURN AIR DUCTS WHICH ARE
 MISSING SIZES ON PAGES M2.1 AND M2.2. SHOW MISSING DUCT
 SIZES IN ACCORDANCE WITH FBC-M 603.1 AND FBC-M 601.4.
  
 2. FLOOR PLAN ON M2.1 SHOWS FIRE DAMPER INSTALLED IN A
 WALL WHICH IS NOT SHOWN AS FIRE RATED ON ARCHITECTURAL
 OR LIFE SAFETY PLANS. FIRE DAMPERS SHALL BE INSTALLED
 IN RATED ASSEMBLIES PER FBC-M 607.2.
  
 3. PAGE M2.2 KEY NOTE #7 REFERENCES PLUMBING DRAWINGS
 FOR CONDENSATE DISPOSAL AT AHU-1. PLUMBING PLANS SHOW
 NO CONDENSATE DISPOSAL SYSTEM FOR THIS AHU. SHOW MEANS
 AND LOCATION OF CONDENSATE DISPOSAL IN ACCORDANCE WITH
 FBC-M 307.2.1.
  
 4. PAGE M6.1 RTU SCHEDULE NOTE #13 CALLS FOR AUX
 CONDENSATE CONTROL SYSTEM ON SECONDARY DRAIN. DOWNDRAFT
 UNITS SHALL HAVE AUXILIARY DRAIN PROTECTION INSTALLED
 IN THE PRIMARY DRAIN PAN IN ACCORDANCE WITH FBC-M
 307.2.3.1.
  
 5. SUPPLY FLEX SCHEDULE ON PAGE M6.1 PROVIDES FLEX
 SIZES FOR DUCTS STARTING AT 50-125 CFM. THERE ARE
 SUPPLY DUCTS PROVIDING FEWER THAN 50 CFM. PROVIDE THE
 INTENDED SIZE OF THESE SUPPLY FLEX DUCTS IN ACCORDANCE
 WITH FBC_M 603.1.
  
 6. PAGE M7.1: MANUFACTURER AND INSTALLATION DETAIL FOR
 A/C STAND DOES NOT CORRESPOND WITH THE SUBMITTED
 PRODUCT APPROVAL. STAND INSTALLATION SHALL BE IN
 ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA PRODUCT
 APPROVAL.
  
 7. PAGE M2.2: MEN'S RESTROOM 120 SHOWS 50 TOTAL CFM OF
 EXHAUST. FLOOR PLAN SHOWS A WATER CLOSET AND A URINAL
 IN THIS RESTROOM. MINIMUM 100 CFM OF EXHAUST IS
 REQUIRED IN THIS ROOM PER FBC-M TABLE 403.3 AND ASHRAE
 62.1-2004 TABLE 6-4.
  
 8. PROVIDE MANUFACTURER'S DATA SHOWING ALL OUTDOOR
 APPLIANCES AND EQUIPMENT, SUCH AS CONDENSERS, RTUS,
 FANS AND ROOF CAPS ARE DESIGNED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-03-18 Cont ID  
Sent By lwagner Date 2010-03-18 Time 14:21 Rev Time 0.00
Received By lwagner Date 2010-03-18 Time 13:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-02-24 Cont ID  
Sent By kstevens Date 2010-02-24 Time 16:04 Rev Time 0.00
Received By kstevens Date 2010-02-24 Time 16:04 Sent To  
Notes
2010-02-24 16:18:30DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 BUILDING
 FBC-2007 CHAPTER 11
  
 1. PER TABLE 104.3 THREE DRINKING FOUNTAINS ARE
 REQUIRED. THE FLOOR PLAN SHOWS 1 DRINKING FOUNTAIN.
 PLEASE SHOW THE LOCATION OF THE OTHER 2 REQUIRED
 DRINKING FOUNTAINS. ALSO SEE SECTION 410.1.
  
 2. SHT A101 ROOM 117 SUBMIT A DETAIL FOR THE SHOWER
 SHOWING COMPLIANCE WITH SECTION 11-4.21 WITH ALL
 SUBSECTIONS.
  
 3. SHT A200 DETAILS 1, 3, 4, 7 & 9. THE CABINET DOORS
 ARE NOT ALLOWED IN THE "CLEAR FLOOR SPACE" REQUIRED FOR
 THE BREAKROOM/LOUNGE SINKS. SECTION 11-4.24.5. PLEASE
 DELETE FROM DETAILS.
  
 4. SHT P5.1 THE SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. THE HDCP LAV IN ROOM 116 AND THE BREAK
 ROOM SINK IN ROOM 115 ARE NOT SHOWN ON THE RISER
 DIAGRAM ONLY ONE URINAL IN ROOM 115 IS SHOWN ON THE
 RISER DIAGRAM. THE MOP SINK AND SINK IN SINK AREA 133
 SHALL NOT DISCHARGE THROUGH THE HORIZONTAL WET VENT FOR
 THE BATHROOM FIXTURES. SECTION 909.1. THE SINKS SHALL
 DISCHARGE DOWNSTREAM OF THE BATHROOM FIXTURES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2010-02-22 Cont ID  
Sent By kdfreema Date 2010-02-22 Time 08:34 Rev Time 0.00
Received By kdfreema Date 2010-02-22 Time 08:34 Sent To  
Notes
***NONE***