Plan Review Details - Permit 10020355
Plan Review Stops For Permit 10020355
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-04-06 Cont ID  
Sent By jwitmer Date 2010-04-06 Time 14:22 Rev Time 2.22
Received By jwitmer Date 2010-04-06 Time 14:22 Sent To  
Notes
2010-04-06 15:41:09BUILDING PLAN REVIEW
 PERMIT: 10020355
 ADD: 1387 10TH STREET
 CONT: O/B EVADNEY YORK
 TEL: (561)876-5472
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 2007 EXISTING BUILDING CODE
 901.3 CHANGE OF OCCUPANCY CLASSIFICATION. WHERE THE
 OCCUPANCY CLASSIFICATION OF A BUILDING CHANGES, THE
 PROVISIONS OF SECTIONS 902 THROUGH 912 SHALL APPLY.
 THIS INCLUDES A CHANGE OF OCCUPANCY CLASSIFICATION
 WITHIN A GROUP AS WELL AS A CHANGE OF OCCUPANCY
 CLASSIFICATION FROM ONE GROUP TO A DIFFERENT GROUP.
  
 901.4 CERTIFICATE OF OCCUPANCY REQUIRED. A CERTIFICATE
 OF OCCUPANCY SHALL BE ISSUED WHERE A CHANGE OF
 OCCUPANCY OCCURS THAT RESULTS IN BEING CLASSIFIED AS A
 DIFFERENT OCCUPANCY CLASSIFICATION AS DETERMINED BY THE
 FLORIDA BUILDING CODE, BUILDING
  
 1) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
  
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED. 2007 EXISTING BUILDING CODE- CHAPTER 9 CHANGE
 IN OCCUPANCY
  
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
  
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 5,
 TABLE 503 FBC-BUILDING
  
 D) THE OCCUPANT LOAD, SEE TABLE1004.1.1.
  
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED?
  
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED
  
 2) EXT BLD CODE 903.1 GENERAL. BUILDING ELEMENTS AND
 MATERIALS IN PORTIONS OF BUILDINGS UNDERGOING A CHANGE
 OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION
 912.
  
 EXT BLD CODE 904.1 GENERAL. FIRE PROTECTION
 REQUIREMENTS OF SECTION 912 SHALL APPLY WHERE A
 BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE OF
 OCCUPANCY CLASSIFICATION.
 912.2 FIRE PROTECTION SYSTEMS. FIRE PROTECTION SYSTEMS
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS 912.2.1
 AND 912.2.2.
  
 EXT BLD CODE 912.2.1 FIRE SPRINKLER SYSTEM. WHERE A
 CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT REQUIRES
 AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE PROVIDED BASED
 ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF
 THE FLORIDA BUILDING CODE, BUILDING , SUCH SYSTEM SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS.
  
 FBC-BUILDING 903.3.1.4 IN GROUP R4 SMALL FACILITIES, AN
 AUTOMATED SPRINKLER SYSTEMS INSTALLED IN ACCORDANCE
 WITH NFPA 13D OR 13R WITH THEIR SCOPES SHALL BE
 PERMITTED, PROVIDED THE AUTOMATIC SPRINKLER SYSTEM IS
 NOT BE CONSIDERED AN ALTERNATIVE TO OTHER REQUIREMENTS
 OF THE CODE.
  
 3) EXT BLD CODE 912.2.2 FIRE ALARM AND DETECTION
 SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION
 OCCURS THAT REQUIRES A FIRE ALARM AND DETECTION SYSTEM
 TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE
 WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING ,
 SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE
 THE CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM
 NOTIFICATION APPLIANCES SHALL BE AUTOMATICALLY
 ACTIVATED THROUGHOUT THE BUILDING. WHERE THE BUILDING
 IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM, ALARM
 NOTIFICATION APPLIANCES SHALL BE PROVIDED THROUGHOUT
 THE AREA WHERE THE CHANGE OF OCCUPANCY OCCURS AND SHALL
 BE AUTOMATICALLY ACTIVATED.
  
 FBC-BUILDING 907.2.10.1.2 GROUPS R-2, R-3, R-4 AND I-1.
 SINGLE- OR MULTIPLE-STATION SMOKE ALARMS SHALL BE
 INSTALLED AND MAINTAINED IN GROUPS R-2, R-3, R-4 AND
 I-1, REGARDLESS OF OCCUPANT LOAD AT ALL OF THE
 FOLLOWING LOCATIONS:
 3.1. ON THE CEILING OR WALL OUTSIDE OF EACH SEPARATE
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF BEDROOMS.
  
 3.2. IN EACH ROOM USED FOR SLEEPING PURPOSES.
  
 3.3. IN EACH STORY WITHIN A DWELLING UNIT, INCLUDING
 BASEMENTS BUT NOT INCLUDING CRAWL SPACES AND
 UNINHABITABLE ATTICS. IN DWELLINGS OR DWELLING UNITS
 WITH SPLIT LEVELS AND WITHOUT AN INTERVENING DOOR
 BETWEEN THE ADJACENT LEVELS, A SMOKE ALARM INSTALLED ON
 THE UPPER LEVEL SHALL SUFFICE FOR THE ADJACENT LOWER
 LEVEL PROVIDED THAT THE LOWER LEVEL IS LESS THAN ONE
 FULL STORY BELOW THE UPPER LEVEL.
  
 4)EXT BLD CODE 912.3 INTERIOR FINISH. IN AREAS OF THE
 BUILDING UNDERGOING THE CHANGE OF OCCUPANCY
 CLASSIFICATION, THE INTERIOR FINISH OF WALLS AND
 CEILINGS SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING , FOR THE NEW OCCUPANCY
 CLASSIFICATION.
  
 FBC-BUILDING 803.5 INTERIOR FINISH REQUIREMENTS BASED
 ON GROUP. INTERIOR WALL AND CEILING FINISH SHALL HAVE A
 FLAME SPREAD INDEX NOT GREATER THAN THAT SPECIFIED IN
 TABLE 803.5 FOR THE GROUP AND LOCATION DESIGNATED.
 INTERIOR WALL AND CEILING FINISH MATERIALS, OTHER THAN
 TEXTILES, TESTED IN ACCORDANCE WITH NFPA 286 AND
 MEETING THE ACCEPTANCE CRITERIA OF SECTION 803.2.1,
 SHALL BE PERMITTED TO BE USED WHERE A CLASS A
 CLASSIFICATION IN ACCORDANCE WITH ASTM E 84 IS
 REQUIRED.
  
 FBC-BUILDING 803.1 GENERAL. INTERIOR WALL AND CEILING
 FINISHES SHALL BE CLASSIFIED IN ACCORDANCE WITH ASTM E
 84. SUCH INTERIOR FINISH MATERIALS SHALL BE GROUPED IN
 THE FOLLOWING CLASSES IN ACCORDANCE WITH THEIR FLAME
 SPREAD AND SMOKE-DEVELOPED INDEXES.
  
 CLASS A: FLAME SPREAD 0-25; SMOKE-DEVELOPED 0-450.
  
 CLASS B: FLAME SPREAD 26-75; SMOKE-DEVELOPED 0-450.
  
 CLASS C: FLAME SPREAD 76-200; SMOKE-DEVELOPED 0-450.
  
 5) EXT BLD CODE 905.1 GENERAL. MEANS OF EGRESS IN
 PORTIONS OF BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 912.
  
 EXT BLD CODE 912.4.1 MEANS OF EGRESS FOR CHANGE TO
 HIGHER HAZARD CATEGORY. WHEN A CHANGE OF OCCUPANCY
 GROUP IS MADE TO A HIGHER HAZARD CATEGORY (LOWER
 NUMBER) AS SHOWN IN TABLE 912.4, THE MEANS OF EGRESS
 SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 10 OF THE
 FLORIDA BUILDING CODE, BUILDING .
  
  
 FBC-BUILDING 1026.1 GENERAL. IN ADDITION TO THE MEANS
 OF EGRESS REQUIRED BY THIS CHAPTER, PROVISIONS SHALL BE
 MADE FOR EMERGENCY ESCAPE AND RESCUE IN GROUP R
 OCCUPANCY. BASEMENTS AND SLEEPING ROOMS BELOW THE
 FOURTH STORY ABOVE GRADE PLANE SHALL HAVE AT LEAST ONE
 EXTERIOR EMERGENCY ESCAPE AND RESCUE OPENING IN
 ACCORDANCE WITH THIS SECTION. WHERE BASEMENTS CONTAIN
 ONE OR MORE SLEEPING ROOMS, EMERGENCY EGRESS AND RESCUE
 OPENINGS SHALL BE REQUIRED IN EACH SLEEPING ROOM, BUT
 SHALL NOT BE REQUIRED IN ADJOINING AREAS OF THE
 BASEMENT. SUCH OPENINGS SHALL OPEN DIRECTLY INTO A
 PUBLIC WAY OR TO A YARD OR COURT THAT OPENS TO A PUBLIC
 WAY. THE EMERGENCY ESCAPE AND RESCUE OPENING SHALL BE
 PERMITTED TO OPEN INTO A SCREEN ENCLOSURE, OPEN TO THE
 ATMOSPHERE, WHERE A SCREEN DOOR IS PROVIDED LEADING
 AWAY FROM THE RESIDENCE. SUCH OPENING SHALL BE
 OPERATIONAL FROM THE INSIDE WITHOUT THE USE OF SPECIAL
 KNOWLEDGE, KEYS OR TOOLS.
  
 1026.2 MINIMUM SIZE. EMERGENCY ESCAPE AND RESCUE
 OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7
 SQUARE FEET (0.53 M2).
  
 EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR EMERGENCY
 ESCAPE AND RESCUE GRADE-FLOOR OPENINGS SHALL BE 5
 SQUARE FEET (0.46 M2).
  
 1026.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET CLEAR
 OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610 MM).
 THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION SHALL BE
 20 INCHES (508 MM). THE NET CLEAR OPENING DIMENSIONS
 SHALL BE THE RESULT OF NORMAL OPERATION OF THE OPENING.
  
 1026.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY ESCAPE AND
 RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE CLEAR
 OPENING NOT GREATER THAN 44 INCHES (1118 MM) MEASURED
 FROM THE FLOOR.
  
 6)EXT BLD CODE 906.1 GENERAL. ACCESSIBILITY IN PORTIONS
 OF BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING .
 EXT BLD CODE912.8 ACCESSIBILITY. EXISTING BUILDINGS OR
 PORTIONS THEREOF THAT UNDERGO A CHANGE OF GROUP OR
 OCCUPANCY CLASSIFICATION SHALL COMPLY WITH CHAPTER 11
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-04-01 Cont ID  
Sent By btrobaug Date 2010-04-01 Time 13:01 Rev Time 0.00
Received By btrobaug Date 2010-04-01 Time 11:00 Sent To  
Notes
2010-04-01 11:25:54THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 1} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS
 DESIGNED UNDER. 2007 FBC, 2008 NEC ETC. ADD TO NOTES
 FOR CLARITY IN THE FIELD AND COMPLIANCE WITH 106.1.3
 FBC AS AMENDED. THE CODE CYCLES INDICATED ON THE PLAN
 ARE INCORRECT.
  
 2} INDICATE COMPLIANCE WITH SECTION 908 OF THE 2007
 EXISTING BUILDING CODE FOR BUILDING ELECTRICAL.
  
 FURTHER COMMENTS MAY BE MADE WHEN MORE INFORMATION IS
 SUBMITTED .
  
  
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-03-31 Cont ID  
Sent By mcarsill Date 2010-03-31 Time 10:26 Rev Time 0.00
Received By mcarsill Date 2010-03-31 Time 10:03 Sent To  
Notes
2010-03-31 10:26:51 
 1387 10TH STREET
 PERMIT NUMBER 10020355
  
 1. THE SMOKE ALARMS DISPLAYED ON THE PLANS ARE TO BE
 MULTI-STATION. WHEN ONE ACTIVATES, THEY SHALL ALL
 OPERATE.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 ALARM SYSTEM.
  
 3. THE PLANS DESIGNATE SIX OCCUPANTS. HOWEVER NO
 EVACUATION CRITERIA FOR THE RESIDENTS HAS BEEN
 ESTABLISHED. WILL THE EVACUATION CAPABILITIES OF THE
 RESIDENTS BE DEFINED AS SLOW, PROMPT, OR IMPRACTICAL?
  
 4. PLEASE SUBMIT AN EMERGENCY EVACUATION PLAN TO THIS
 OFFICE FOR REVIEW.
  
 5. A 4" STEP DOWN IS LOCATED IN THE TV ROOM. CHANGES IN
 ELEVATIONS LESS THAN 12" SHALL BE BY RAMPS. (NFPA 101,
 SECTION 7.1.7.1)
  
 6. COULD NOT LOCATE ANY PORTABLE FIRE EXTINGUISHERS.
  
 7. SLEEPING ROOM DOORS SHALL BE AT LEAST 1-3/4 " SOLID
 BONDED WOOD CORE CONSTRUCTION.
  
 8. ZONING APPROVAL WILL BE REQUIRED FOR THIS
 RESIDENTIAL BOARD AND CARE FACILITY, SMALL FACILITY
 LESS THAN 16 RESIDENTS.
  
 9. PLEASE DESIGNATE ON THE PLANS THE PRIMARY AND
 SECONDARY MEANS OF ESCAPE.
  
 10. PLEASE DESCRIBE DOOR HARDWARE AND LOCKING DEVICES
 ON PRIMARY AND SECONDARY MEANS OF ESCAPE.
  
  
 DENIED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX
  
 WESLEY JOLIN, FIRE PROTECTION ENGINEER
 BUREAU OF FIRE PREVENTION
 (561) 805-6730 PHONE
 (561) 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-04-07 Cont ID  
Sent By lwagner Date 2010-04-07 Time 12:28 Rev Time 0.00
Received By lwagner Date 2010-03-16 Time 09:28 Sent To  
Notes
2010-03-16 09:30:28C 14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-04-01 Cont ID  
Sent By hmoser Date 2010-04-01 Time 13:26 Rev Time 0.00
Received By hmoser Date 2010-04-01 Time 13:26 Sent To  
Notes
2010-04-01 13:38:35PLAN DENIED
 1) NO MECHANICAL PLANS SUBMITTED .
 2) CHANGE OF OCCUPANCY PLEASE REFER TO SECTION 901.1
 MECHANICAL REQUIREMENTS 2007 EXISTING BUILDING CODE
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-04-07 Cont ID  
Sent By lwagner Date 2010-04-07 Time 12:08 Rev Time 0.00
Received By lwagner Date 2010-04-07 Time 10:07 Sent To  
Notes
2010-04-07 12:21:47NOT ENOUGH INFORMATION FOR PLUMBING REVIEW.
 IF OCCUPANCY IS R-4, DRINKING FOUNTAIN AND
 SERVICE SINK ARE REQUIRED. SEE BUILDING COMMENTS
 FOR ACCESSIBILITY
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2010-04-05 Cont ID  
Sent By lfranco Date 2010-04-05 Time 17:13 Rev Time 0.00
Received By lfranco Date 2010-04-05 Time 17:13 Sent To B
Notes
2010-04-05 17:58:07PLANNING AND ZONING: **** PASSED WITH PROVISO- A
 TEMPORARY APPROVAL FOR A GROUP HOME TYPE I FOR THE
 BUFFER REQUIREMENTS, PURSUANT TO SECTION 94-272 (28) -
 NO SUCH HOME SHALL BE LOCATED WITHIN A RADIUS OF 1,000
 FEET OF ANOTHER TYPE I GROUP HOME OR WITHIN A RADIUS OF
 1,200 FEET OF A TYPE II, TYPE III OR TYPE V GROUP HOME
 HAS BEEN GIVEN, THE APPLICANT MUST OBTAIN A FINAL CITY
 BUISNESS TAX RECEIPT BY 7/6/10 OR APPLICANT WILL NEED
 TO COME IN FOR A RENEWAL OF THE DISTANCE REQUIREMENT.
  
 FINAL ZONING SIGN-OFF IS CONTIGENT UPON APPLICANT
 RECEIVING APPROVAL BY ALL CITY DEPARTMENTS REVIEWING
 THE GROUP HOME TYPE I (CHANGE OF OCCUPANCY)
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  