Plan Review Details - Permit 10020288
Plan Review Stops For Permit 10020288
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-05-11 Cont ID  
Sent By jwitmer Date 2010-05-11 Time 13:47 Rev Time 2.22
Received By jwitmer Date 2010-05-11 Time 13:47 Sent To  
Notes
2010-05-11 13:57:53BUILDING PROVISO:
 A SEPERATE ROOFING PERMIT WILL BE REQUIRED WITH
 ADDITIONAL REVIEW AND FEES. PRODUCT APPROVAL SUBMITTED
 REQUIRES RAS 117 CALCULATIONS TO BE PREPARED BY EITHER
 A ENGINEER, ARCHITECT OR A REGISTERED ROOFING
 CONSULTANT.
  
 ROOFING PRODUCT APPROVALS SUBMITTED:
 FL 479-R2
 CERTAINTEED CORPORATION- ROOFING
 MODIFIED BITUMEN ROOF SYSTEM
 PAGE 36 OF 39
 SBS MODIFIED
 DECK TYPE 1: WOOD, NON-INSULATED
 DECK DESCRIPTION: MIN 19/32" THICK PLYWOOD, NAILS
 SPACED 4" O.C. @ WOOD JOIST SPACED MAXIMUM 24" O. C.
 SYSTEM TYPE E(6)
 MAXIMUM DESIGN PRESSURE: -60 PSF (SEE GENERAL
 LIMITATION #7.
 LIMITATION #7 REQUIRES RAS 117 CALCULATIONS TO BE
 PREPARED BY EITHER A ENGINEER, ARCHITECT OR A
 REGISTERED ROOFING CONSULTANT.
  
 ROOF TILE
 FL8835-R1
 EAGLE ROOFING
 NOA: 07-1018.09 CAPISTRANO CONCRETE TILE
 PAGE 5 POLYFOAM POLY PRO LARGE 66.5/ SMALL 38.7

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-02 Cont ID  
Sent By jwitmer Date 2010-03-02 Time 11:59 Rev Time 0.00
Received By jwitmer Date 2010-03-02 Time 09:33 Sent To  
Notes
2010-03-02 15:54:19BUILDING PLAN REVIEW
 PERMIT: 10020288
 ADD: 3115 45TH ST
 CONT: SERRAES CONSTRUCTION
 TEL: (561)848-6607
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 MARCH 03/ 2010
  
 1) SHEET A-0.00 LIFE SAFETY PLAN:
  
 1A) THE PLANS INDICATE AN AREA OF FIXED SEATING
 CLAIMING THE REQUIREMENT OF 1004.7. THE OCCUPANT LOAD
 IS PROVIDED BY OCCUPANCY TYPE, NOT BY ROOM NUMBER, IT
 IS CONFUSING AS TO WHAT AREAS ARE BEING CONSIDERED AN
 ASSEMBLY AREA. TABLE 1004.1.1 & SECTION 1004.7.
  
 1B) ROOM# 103 THE TRAINING ROOM IF CONSIDERED WITH
 TABLES AND CHAIRS HAS AN OCCUPANT LOAD OF 738/15= 49.2
 OR 50 OCCUPANTS. SEE TABLE 1017.1, ASSEMBLY OCCUPANCY <
 30 REQUIRES A ONE HOUR RATED CORRIDOR. IF CHAIRS ( NOT
 FIXED) ARE FIGURED INTO THE EQUATION THEN
 738/7= 105.4 OR 106 OCCUPANTS. IN EITHER CASE TABLE
 1017.1 WILL REQUIRE A 1 HR RATED CORRIDOR.
  
 1C) THE OTHER ISSUE WITH ROOM 103 THE TRAINING ROOM IS
 THERE IS ONLY ONE MEANS OF EGRESS INTO THIS ROOM.
 PLEASE REVIEW TABLE 1019.2 FOR ASSEMBLY A3 OCCUPANCY
 WITH ONE MEANS OF EGRESS NO MORE THAN 49 OCCUPANTS MAY
 OCCUPY THIS ROOM.
  
 1D) ROOM 117 THE CHAPEL IS ALSO TO BE CONSIDERED A
 ASSEMBLY A3 OCCUPANCY CONSIDERING THE SQ FT AS 682 SQ
 FT/15= 46 OCCUPANTS. THE CORRIDOR WOULD ALSO NEED TO BE
 1 HOUR RATED, SEE TABLE 1017.1.
 PLEASE NOTE THE ASSEMBLY ROOMS MEET THE EXCEPTION <
 THAN 750 SQ FT AND WOULD NOT NEED OCCUPANCY SEPARATION
 BETWEEN OCCUPANCIES.508.3.1.
  
 1E) WITHIN THE CHAPEL IT APPEARS AT THE END OF THE ROOM
 WHERE AN ALTER IS LOCATED IT APPEARS A CHANGE IN
 ELEVATION? IF SO PLEASE INDICATE THE GRADE CHANGE.
 PROVIDE COMPLIANCE WITH VERTICAL ACCESSIBILITY.
 11-4.1.6(1)(K)(III).
  
  
 1F) OTHER INCIDENTAL USE AREAS THAT WOULD NEED
 SEPARATION PLEASE REVIEW 508.2, MECHANICAL ROOMS,
 STORAGE ROOMS> THAN 100 SQ FT (CLOTHES CLOSET # 125).
 ALSO NOTE ROOM ELECTRICAL, TECH/ DATA ROOM, IF THIS IS
 A TRUE IT ROOM REVIEW NEC 645.4(5) FOR 1 HR SEPARATION.
  
 1G) THE DOOR THAT LEADS INTO ROOM 108 IS MISSING THE
 REQUIRED 18 INCHES AT THE LATCH SIDE OF THE DOOR.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 1H) THE DOOR LEADING INTO THE DIRECTORS OFFICE ROOM#
 114 ALSO WILL NEED TO MEET THE REQUIREMENTS OF
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 2) SHEET AD 1.01 THE EXISTING ACCESSIBLE RAMP DOES NOT
 INDICATE COMPLIANCE WITH 11-4.29.5/ DUTY TO PROVIDE
 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.11-4.1.6(2) (2)(A).
  
 3) PRODUCT APPROVALS: THE CONTRACTOR HAS ONLY SUBMITTED
 THE FLORIDA COVERSHEETS, NOT THE ASSOCIATED REPORTS.
 WITH ONLY THE COVER SHEET AND NO SUB-SYSTEM HIGHLIGHTED
 NOR THE PRODUCT APPROVAL THEMSELVES THE POSITIVE AND
 NEGATIVE PRESSURES CAN NOT BE VERIFIED FOR THESE
 PRODUCTS;
 3A) FL 8835-R1/ 2007 EAGLE ROOFING PRODUCTS- ROOF TILE
 THE MIAMI-DADE NOA WAS SUBMITTED, NOR ROOFING
 SUB-SYSTEM IDENTIFIED WHICH WOULD IDENTIFY POSITIVE AND
 NEGATIVE PRESSURES AND LIMITATIONS.
  
 3B) FL 479-R2/ 2004 CERTAIN TEED CORPORATION MODIFIED
 BITUMEN ROOF SYSTEMS
 THE MIAMI-DADE NOA WAS SUBMITTED, NOR ROOFING
 SUB-SYSTEM IDENTIFIED WHICH WOULD IDENTIFY POSITIVE AND
 NEGATIVE PRESSURES AND LIMITATIONS.
  
 3C) FL 8712-R1 YKK AP EXTERIOR DOORS
 THE INSTALLATION INSTRUCTIONS NOR THE EVALUATION REPORT
 WAS NOT SUBMITTED WHICH WOULD HAVE IDENTIFIED THE
 POSITIVE AND NEGATIVE PRESSURES
  
 3D) FL 243-R8 PGT WINDOWS FIXED
 THE MIAMI-DADE NOA WAS SUBMITTED, NOR ROOFING
 SUB-SYSTEM IDENTIFIED WHICH WOULD IDENTIFY POSITIVE AND
 NEGATIVE PRESSURES AND LIMITATIONS.
  
 3E) FL 4553-R2 CECO DOOR EXTERIOR SWING DOOR-
 CERTIFICATION MARK OR LISTING MAY OR MAY NOT MEET
 PRESSURES SINCE PRESSURES ARE NOT GIVEN, NOR WERE
 INSTALLATION INSTRUCTIONS SUBMITTED.
 4) 106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL
 FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE
 ENGINEER OF RECORD FOR REVIEW.
  
 5) SHEET S1.01 & A-3.01 THE ELEVATIONS INDICATE A ROOF
 PITCH OF 5/12 AND A FLAT ROOF. SHEET S1.01 PROVIDES
 PRESSURES FOR ROOFING TRIBUTARY AREAS BUT NOT THE
 ACTUAL PRESSURES FOR COMPONENTS AND CLADDING. NOTE
 THERE WILL BE TWO DIFFERENT PRESSURE DUE TO A FLAT ROOF
 AS WELL AS A 5/12 PITCHED ROOF. IN BOTH CASES ZONES 1,
 2 AND 3 WILL NEED TO BE ADDRESSED.
 FOR EXAMPLE FOR A FLAT ROOF IN ZONE 3, THE NEGATIVE
 PRESSURES WILL BE -89 WITH MULTIPLIERS OF 1.21 FOR
 EXPOSURE ???C???.
  
 6) SHEET A-4.01 BUILDING SECTION# 1 INDICATES THE USE
 OF ICYNENE INSULATION AT THE CEILING LEVEL WHERE AS
 SECTION# 2 INDICATES THE ICYNENE INSULATION AT THE TOP
 CHORD OF THE TRUSS? 106.1.2 ADDITIONAL INFORMATION
 REQUIRED, DISCREPANCY.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-05-07 Cont ID  
Sent By btrobaug Date 2010-05-07 Time 12:27 Rev Time 0.00
Received By btrobaug Date 2010-05-07 Time 10:50 Sent To  
Notes
2010-05-07 12:27:40TO C-6

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-24 Cont ID  
Sent By dpalmer Date 2010-02-24 Time 15:57 Rev Time 0.00
Received By btrobaug Date 2010-02-24 Time 15:57 Sent To  
Notes
2010-02-24 15:57:37** DENIED **
  
  
 1) NOTE: PLEASE ADJUST NFPA-101 AS LISTED ON E-0.
 INDICATES 2003 EDITION HOWEVER PER FAC 69A-03.012 AND
 THE ADOPTION OF TH E2007 FBC W/2009 SUPPLEMENTS.
 * THIS COULD HAVE BEEN REDLINED HOWEVER PLANS ARE
 COMING BACK FOR OTHER NOTES.
  
 2) NOTE: PLEASE SUBMIT THE COMPLETED ENERGY
 CALCULATIONS FOR REVIEW. PLEASE BE SURE TO COMPLETE THE
 CALCULATIONS WITH ALL REQUIRED SYSTEMS IN FBC CHAPTER
 13 IN THE INPUT DATA REPORT AND COORDINATE WITH PLANS.
 PLEASE SEE PAGE TWO OF THE SUBMITTED CALCULATIONS WHICH
 STATES THE INPUT DATA REPORT MUST BE SUBMITTED WITH THE
 COMPLIANCE REPORT. THERE ARE NO INPUT DATA REPORT
 SHEETS SUBMITTED.
 PLEASE KNOW THAT ALL SYSTEMS INCLUDING HOT WATER PIPING
 SYSTEMS ARE REQUIRED. THE SUMMARY SHEETS STATES * NONE
 ENTERED*. PLEASE EXPLAIN HOW THIS IS POSSIBLE? SEE
 MINIMUM UNDER 13-411, 13-412.
 THE SUBMITTED FLA COM IS FOR METHOD *A* , WHOLE
 BUILDING COMPLIANCE. THIS IS AN EXISTING BUILDING
 MEETING THE DEFINITION OF A RENOVATION PER SECTION 202.
 PLEASE EXPLAIN THE USE OF METHOD *A*.
 PLEASE EXPLAIN WHAT APPEARS TO BE METHOD *B* ON PLANS.
 PLEASE KNOW THAT THERE IS NO LONGER *ACCENT OR
 DECRETIVE* ALLOWANCES UNDER THE NEW CODE.
  
 ** PLEASE BE SURE TO SEE APPENDIX B4.1.1 FOR TRACK
 LIGHTING AND OTHER LUMINAIRE WATTAGES.
  
 3) NOTE: PLEASE EXPLAIN THE MSB AS SHOWN. THE MSB
 SCHEDULE STATES THE MAIN OVER CURRENT PROTECTION IS
 600AMPS YET THE RISER DOES NOT INDICATE ANY 600AMP OCP.
 NEED TO VERIFY.
 230.70.230.71.230.76, 310.16 ETC
  
 4) NOTE: PLEASE VERIFY THE MAIN OVER CURRENT PROTECTION
 FRO EACH OF THE TWO SUB PANELS. THE MSB SCHEDULE
 INDICATES 225AMP OCP FOR EACH PANEL HOWEVER THE FEEDERS
 TO EACH OF THE PANELS *LPA AND LPB* ARE ONLY RATED FOR
 200AMPS PER 310.16, 110.14.
 THE OTHER ITEM WHICH IS NOT CLEAR IS THE RISER
 INDICATES 200AMP OCP FOR THE SAME TWO PANELS WHICH IS
 NOT THE SAME AS THE INFORMATION PROVIDED ON THE MSB
 SCHEDULE.
 PLEASE COORDINATE THE OCP AND CONDUCTOR SIZES FOR EACH.
  
 5) NOTE: PLEASE SEE 406.8 AND MAKE NOTE OF RECEPTACLES
 IN WET/DAMP LOCATIONS.
  
 6) NOTE: PLANS DO CONTAIN A NOTE THAT STATES EXTERIOR
 LIGHTING TO OPERATE THROUGH A TIME CLOCK. HOWEVER A
 STANDARD TIME CLOCK DOES NOT MEET MINIMUM REQUIRED BY
 FBC 13-415.AB.1.4.
 ONE OF THE TWO METHODS OF CONTROLS FOR MINIMUM CONTROLS
 IS REQUIRED.
 PHOTO-SENSOR TYPE CONTROLS OR
 ASTRONOMICAL TIME CLOCK WITH A MINIMUM OF 10HR
 PROGRAMMING BATTERY BACK UP.
  
 7) NOTE: PLEASE SEE FBC 13-415.AB.1.2.
 EVEN WHEN LIGHTING IS IN A BUILDING SMALLER THAN 5K SQ
 FT IN THE FOLLOWING ROOMS AUTOMATED LIGHTING CONTROLS
 LISTED ARE REQUIRED TO MEET MINIMUM CODE.
 THIS HAS BEEN CONFIRMED WITH THE STATE OF FLORIDA.
  
 CLASSROOMS,
 CONFERENCE ROOMS/MEETING ROOMS AND
 LUNCH/BREAK ROOMS.
  
 8) NOTE: PLEASE SEE COMMENTS FROM FIRE MARSHAL FOR A
 FEW POSSIBLE MISSING EXIT SIGNS PER NFPA-101.
 PLEASE SEE NFPA_101 7.8.1.3,7.9.1.2,.2.2 FOR MINIMUM
 FOOT CANDLE LEVELS REQUIRED FOR EMERGENCY EGRESS
 LIGHTING. THERE NO PHOTO-METRICS SUBMITTED AND
 DESIGNATED EGRESS PATH TO SOME AREAS APPEAR TO BE
 DEFICIENT FOR SOME LIGHTS.
 PLEASE SEE FOYER AREA.
  
 9) NOTE: THE PLANS INDICATE CARE AREAS, WILL THERE BE
 ANY DOCTORS, NURSES PRESENT PERFORMING EXAMS? PLEASE
 SEE NEC 517.10 AND REDUNDANT GROUNDING REQUIRED IN EXAM
 ROOMS IN 517.13.
  
 10) NOTE: LOW VOLTAGE AS SHOWN ON PLANS SUCH AS CATV,
 PHONE, DATA OR SPEAKERS WILL BE UNDER SEPARATE PERMITS.
 ANY PROPOSED EGRESS/ACCESS CONTROLS WILL BE UNDER
 SEPARATE PERMIT AND PLANS.
 THESE PLANS MAY BE REFERENCED FOR TV, PHONE, DATA AND
 LV SPEAKERS ONLY FOR TURN-AROUND LV PERMITS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-05-07 Cont ID  
Sent By mawillia Date 2010-05-07 Time 13:40 Rev Time 0.00
Received By mawillia Date 2010-05-07 Time 13:00 Sent To  
Notes
2010-05-07 13:39:59*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A-0.00, A-1.01, A-3.01, A-8.01,
 E-2, AND E-2.1 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-03-08 Cont ID  
Sent By mcarsill Date 2010-03-08 Time 08:28 Rev Time 0.00
Received By mcarsill Date 2010-03-08 Time 08:20 Sent To  
Notes
2010-03-08 08:28:26MIRACLE HOUSE
 PREGNANCY CARE CENTER
 3115-45TH STREET
 PERMIT # 10020288
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. CODE ANALYSIS BOX HAS INCORRECT INFORMATION. PLAM
 BEACH COUNTY FIRE RESCUE IS NOT THE JURISDICTION BUT
 WEST PALM BEACH FIRE RESCUE IS.
  
 3. BUILDING ADDRESS IS REQUIRED. A MINIMUM OF AT LEAST
 6" HIGH AND AT LEAST 1" WIDE IS REQUIRED.
  
 4. ON PAGE E-0 WRONG EDITION OF NFPA 101 IS LISTED.
 SHOULD READ NFPA 101 2006 EDITION.
  
 5. THE FLOOR PLAN ON THE LIFE SAFETY DRAWING DOES NOT
 MATCH THE FLOOR PLAN ON PAGE E-2.
  
 6. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 7. GENERAL STORAGE ROOMS, BOILER OR FURNACE ROOMS NEED
 TO BE PROTECTED BY EITHER 1 HOUR FIRE RESISTANCE, FIRE
 SPRINKLERS OR BOTH.
  
 8. EMPLOYEES SHALL BE TRAINED IN THE USE OF PORTABLE
 FIRE EXTINGUISHERS.
  
 9. PLEASE DESCRIBE EXIT DISCHARGE LOCATIONS.
  
 10. PLEASE INDICATE HOURS OF OPERATION AND HOW THE
 FACILITY OPERATES.
  
 DENIED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 WEST PALM BEACH FIRE RESCUE
 (561) 804-4709 PHONE
 (561) 804-4774

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-04-21 Cont ID  
Sent By lmartine Date 2010-04-15 Time 13:06 Rev Time 0.00
Received By lmartine Date 2010-04-15 Time 13:05 Sent To  
Notes
2010-04-21 13:06:55C--6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-28 Cont ID  
Sent By lmartine Date 2010-03-21 Time 11:40 Rev Time 0.00
Received By lmartine Date 2010-02-11 Time 16:18 Sent To  
Notes
2010-02-16 16:18:38C--2

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2010-05-11 Cont ID  
Sent By jwitmer Date 2010-05-11 Time 08:53 Rev Time 0.00
Received By jwitmer Date 2010-05-11 Time 08:53 Sent To  
Notes
2010-05-11 08:54:09IIMPACT FEES: NO FEES DUE

Review Stop L LANDSCAPING
Rev No 3 Status N Date 2010-05-19 Cont ID  
Sent By rkussner Date 2010-05-19 Time 09:16 Rev Time 0.00
Received By rkussner Date 2010-05-19 Time 09:16 Sent To  
Notes
2010-05-19 09:23:43***LANDSCAPE REVIEW NOT REQUIRED* WITH 'PROVISO' **
  
 1. A SEPARATE IRRIGATION PERMIT IS REQUIRED. THE
 APPLICATION AND TWO SETS OF PLANS MUST BE SUBMITTED,
 APPROVED, IMPLEMENTED AND SUCCESSFULLY INSPECTED PRIOR
 TO C/O.
  
 2. A SEPARATE LANDSCAPE PERMIT IS REQUIRED. THE
 APPLICATION, TWO SETS OF PLANS AND A CERTIFIED COST
 ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE
 MATERIALS AND LABOR, BROKEN DOWN INTO UNIT COST SHALL
 BE SUBMITTED, APPROVED, IMPLEMENTED AND SUCCESSFULLY
 INSPECTED PRIOR TO C/O.
  
 3. PLEASE PROVIDE THE CORRECT CITY APPROVED STRIPING
 DETAIL FOR THIS PERMIT PRIOR TO C/O.
  
 4. APPLY FOR A TREE ALTERATION PERMIT WITHIN 30 DAYS
 FROM THIS PERMIT ISSUE DATE IF ANY TREES WILL BE
 REMOVED. THE APPLICATION IS AVAILABLE AT THE FRONT DESK
 OF THE PLANNING AND ZONING DEPARTMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  
  
  
  
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2010-04-28 Cont ID  
Sent By rkussner Date 2010-04-28 Time 10:22 Rev Time 0.00
Received By rkussner Date 2010-04-28 Time 10:22 Sent To  
Notes
2010-04-28 12:04:41***LANDSCAPE REVIEW FAILED****
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
  
 1. A SEPARATE LANDSCAPE PERMIT IS REQUIRED. PLEASE
 SUBMIT A APPLICATION AND TWO SETS OF LANDSCAPE PLANS. A
 CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST OF
 ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST SHALL BE INCLUDED WITH THE PERMIT
 APPLICATION.
  
 2. THE STRIPING DETAIL WAS INCORRECT. PLEASE PROVIDE
 THE CITY APPROVED STRIPING DETAIL FOR THE MAIN PERMIT.
 A COPY OF THE APPROVED DETAIL CAN BE OBTAINED AT THE
 FRONT DESK OF THE PLANNING AND ZONING DEPARTMENT.
  
 3. THE SYMBOL SHOWS THAT NINE CRINUM LILIES WILL BE
 INSTALLED BUT ONLY THREE WERE SHOWN.
  
 4. IF THE IRRIGATION SYSTEM NEEDS TO BE MODIFIED, A
 SEPARATE IRRIGATION PERMIT IS REQUIRED. PLEASE SUBMIT
 TWO COPIES OF THE IRRIGATION PLAN. THE SYSTEM MUST HAVE
 A RAIN SENSING DEVICE AND PVB VALVE IF IT IS ON CITY
 WATER. CREDIT WAS TAKEN FOR A MOISTURE SENSING DEVICE
 OTHER THAT RAINSWITCH. IF THIS IS PROPOSED AS A
 SUBSTITUTE FOR THE RAIN SENSING DEVICE, PLEASE IDENTIFY
 THE TYPE OF EQUIPMENT PROPOSED.
  
 5. PURSUANT TO SECTION 94-443 (B) (4), AT LEAST ONE
 SHADE OR FLOWERING TREE CAHLL BE PLANTED IN THE
 REQUIRED BUFFER STRIP FOR EACH 30 LINEAR FEET OR
 PORTION THEREOL. THIS APPLIES TO THE WEST SIDE OF THE
 SITE. THE SPACING OF THE PROPOSED TREES EXCEEDS 30
 FEET.
  
 7. PLEASE APPLY FOR A TREE ALTERATION PERMIT AND
 IDENTIFY ALL TREES THAT WILL BE REMOVED.
  
 8. THE OPEN SPACE IS DETERMINED BY TAKING THE TOTAL LOT
 AREA AND DEDUCTING THE BUILDING FOOTPRINT. THE
 DIFFERENCE IS THE OPEN SPACE. PLEASE REVISE THE
 CALCULATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-03-09 Cont ID  
Sent By rkussner Date 2010-03-09 Time 14:39 Rev Time 0.00
Received By rkussner Date 2010-03-09 Time 14:39 Sent To  
Notes
2010-03-09 15:12:27***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 2 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR. ALL UTILITIES, EASEMENTS, SITE LIGHTING,
 OVERHEAD LINES AND ANYTHING ELSE THAT MAY BE IN
 CONFLICT WITH PROPOSED LANDSCAPING SHALL BE SHOWN ON
 THE LANDSCAPE PLAN.
  
 3. PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS.
  
 4. PURSUANT TO SECTION 94-448 (D) (1), PLEASE APPLY FOR
 A TREE ALTERATION PERMIT AND IDENTIFY THE STATUS OF ALL
 TREES ON SITE---THOSE TO BE REMOVED, SAVED OR
 RELOCATED.
  
 5. PURSUANT TO SECTION 94-448 (D) 2), ALL OF THE ITEMS
 ENUMERATED IN THIS SECTION SHALL BE PART OF THE
 LANDSCAPE PLAN.
  
 6. PURSUANT TO SECTION 94-444 (B), GARBAGE OR TRASH
 RECEPTACLES, AIR CONDITIONING UNITS, GENERATORS AND
 OTHER MECHANICAL EQUIPMENT SHALL NOT BE PERMITTED
 UNLESS APPROPRIATE SCREENING IS PROVIDED. THE DUMPSTER
 ENCLOSURE SHALL HAVE VISION OBSCURING GATES.
  
 7. OTHER COMMENTS WILL BE FORTHCOMING ONCE WE RECEIVE A
 LANDSCAPE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-03-04 Cont ID  
Sent By rregueir Date 2010-03-04 Time 15:33 Rev Time 0.00
Received By rregueir Date 2010-03-04 Time 15:00 Sent To  
Notes
2010-03-04 15:33:42**PROVISO**
  
 AHU #2 DUCT SMOKE DETECTOR IS SHOWN LOCATED IN THE
 TRUNK LINE, DOWNSTREAM OF THE FIRST SUPPLY BRANCH.
 REQUIRED SMOKE DETECTORS SHALL BE INSTALLED TO MONITOR
 THE ENTIRE AIRFLOW IN ACCORDANCE WITH FBC-M 606.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-04-26 Cont ID  
Sent By lwagner Date 2010-04-26 Time 09:37 Rev Time 0.00
Received By lwagner Date 2010-04-26 Time 09:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-03-03 Cont ID  
Sent By kstevens Date 2010-03-03 Time 15:50 Rev Time 0.00
Received By kstevens Date 2010-03-03 Time 15:50 Sent To  
Notes
2010-03-03 16:04:22DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 BUILDING
  
 1. SHT A-0.00 THE OCCUPANCY LOAD IS INDICATED AS 90
 OCCUPANTS. PLEASE SEE THE COMMENTS OF JWITMER BUILDING
 PLANS EXAMINER 1A THRU 1D CONCERNING THE OCCUPANT LOAD.
 MINIMUM FACILITIES FOR PLUMBING FIXTURES IS BASED ON
 TABLES 1104.1.1 & 403.1. AFTER VERIFICATION OF THE
 OCCUPANCY LOAD, MORE COMMENTS MAY BE FORTHCOMING.
  
 2. SHT A-1.02 GALVANIZED SCUPPER DETAIL SHOWS AN 8 INCH
 X 2 INCH OVERFLOW SCUPPER. PER SECTION 1107.3 SCUPPERS
 SHALL NOT HAVE AN OPENING DIMENSION OF LESS THAN 4
 INCHES. ALSO PLEASE INDICATE THE SIZE OF THE EXISTING
 ROOF DRAINS TO VERIFY THE REQUIRED SIZE OF THE OVERFLOW
 SCUPPERS.
  
 3. SHT A-5.01 TOILET ROOMS 112, 115 & 116. WALLS WITHIN
 2 FEET OF THE WATER CLOSETS SHALL COMPLY WITH SECTION
 1210.2. THE INFORMATION SHOWN ON THE FLOOR PLAN, 112
 (W-5.11), 115 (W-1.11) & 116 (W-1.10) DOES NOT REFLECT
 THE INFORMATION ON THE FINISH SCHEDULE. PLEASE CLARIFY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2010-05-20 Cont ID  
Sent By kdfreema Date 2010-05-20 Time 14:44 Rev Time 0.00
Received By kdfreema Date 2010-05-20 Time 14:44 Sent To  
Notes
2010-05-20 14:45:10***PROVISO***
  
 SIGNAGE REQUIRES SEPARATE PERMITS AND WILL BE REVIEWED
 AT THAT TIME.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-03-21 Cont ID  
Sent By astelly Date 2010-03-21 Time 15:09 Rev Time 0.00
Received By astelly Date 2010-03-21 Time 15:09 Sent To  
Notes
2010-03-21 15:14:30AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 A SITE PLAN SHOWING PROPERLY STRIPED PARKING AND AN
 ENLARGED STALL DETAIL IS REQUIRED.
 A LANDSCAPE PLAN IS REQUIRED FOR PERMIT REVIEW.
 A DETAIL ILLUSTRATING THE EXISTING DUMPSTER ENCLOSURE
 IS REQUIRED.
 THERE IS AN EXISTING MONUMENT SIGN ASSOCIATED WITH THE
 PARCEL. PLEASE INDICATE WHETHER THE SIGN WILL BE
 REINSTATED; OTHERWISE NOTE THAT THE SIGN STRUCTURE WILL
 BE DEMOLISHED.
 A SEPARATE PERMIT IS REQUIRED FOR ALL SIGNAGE.
 YOUR RESUBMISSION MAY GENERATE ADDITIONAL COMMENTS.