| 2010-02-24 16:51:50 | BUILDING PLAN REVIEW |
| | PERMIT: 10020252 |
| | ADD: 5707 S DIXIE # 3 |
| | CONT: BROUGHTON CONSTRUCTION, LLC |
| | TEL: (561)644-4488 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | FEB. 24/ 2010 |
| | |
| | 1) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: A) THE EDITION OF THE CODE UNDER WHICH |
| | THE PROJECT IS DESIGNED. PLEASE ALSO NOTE COMPLIANCE |
| | WITH THE 2007 FBC EXISTING BUILDING CODE AND SECTION |
| | 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 403, 404 AND 405 OF THIS CODE. |
| | |
| | 2) THE PERMIT APPLICATION INDICATES UNDER THE |
| | DESCRIPTION OF WORK THE CUTTING OF EXISTING SLAB. |
| | ADDITIONAL INFORMATION IS REQUIRED. 106.1.2 |
| | ADMINISTRATIVE CODE. |
| | 2A) PLANS FAIL TO INDICATE COMPLIANCE WITH TERMITE |
| | TREATMENT OF SOILS WHERE SLAB HAS BEEN CUT AND GRADE |
| | DISTURBED. 1816.1 TERMITE PROTECTION. TERMITE |
| | PROTECTION SHALL BE PROVIDED BY REGISTERED |
| | TERMITICIDES, INCLUDING SOIL-APPLIED PESTICIDES, |
| | BAITING SYSTEMS AND PESTICIDES APPLIED TO WOOD, OR |
| | OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED |
| | FOR USE AS A PREVENTATIVE TREATMENT. |
| | 2B) PLANS FAIL TO INDICATE WHAT TYPE OF MATERIALS WILL |
| | BE USED FOR THE NEW FLOOR SYSTEM. IF CONCRETE AND HOW |
| | THE NEW SECTION OF FLOOR WILL BE SECURED TO THE |
| | EXISTING FLOOR SLAB. |
| | |
| | 3) SHEET# 1 THE DOORWAY LEADING INTO THE BREAK ROOM |
| | DOES NOT PROVIDE THE SIZE OF THE DOOR, NOR DOES THE |
| | PLANS INDICATE COMPLIANCE WITH SECTION: |
| | 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM |
| | MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC |
| | OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE |
| | FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES |
| | SHALL BE CLEAR & LEVEL. |
| | |
| | 4) SHEET# 1 INDICATES A 2HR FIRE SEPARATION REQUIRED. |
| | TENANT SEPARATION WALLS COVERED UNDER FBC-B 708 ONLY |
| | REQUIRE 1 HOUR SEPARATION. IF OCCUPANCY SEPARATION IS |
| | TO BE CONSIDERED WE WILL NEED TO SEE WHAT OCCUPANCIES |
| | ARE ON BOTH SIDES OF THIS TENANT TO DETERMINE THE HOUR |
| | RATING, TABLE 508.3.3. NOTE PLANS INDICATE 2 HR |
| | SEPARATION. AN AREA OF CONCERN THE MECHANICAL REVIEW |
| | WILL DWELL ON WILL BE VENTILATION REQUIREMENTS FOR THE |
| | MANICURE AND PEDICURE STATIONS, HOW WILL THE |
| | VENTILATION REQUIREMENTS BE MET AND WILL THE |
| | TENANT SEPARATION WALLS BE CUT FOR THE ADDITIONAL |
| | DUCTWORK. DETAILS WILL BE NEEDED POSSIBLY FOR |
| | PENETRATIONS OF FIRE RATED TENANT SEPARATION WALLS, |
| | PLEASE SEE FBC-B SECTION 712. |
| | |
| | 5) PLEASE PROVIDE DETAILS FOR BREAK ROOM COUNTER AND |
| | SINK. SINKS: 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE |
| | MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE |
| | FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" |
| | WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| | SINK. |
| | |
| | 6) PLANS FAIL TO INDICATE THE LOCATION OF THE PORTABLE |
| | FIRE EXTINGUISHER. FBC-B 906.1 GENERAL. PORTABLE FIRE |
| | EXTINGUISHERS SHALL BE PROVIDED IN OCCUPANCIES AND |
| | LOCATIONS AS REQUIRED BY THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | |
| | 7) PLEASE PROVIDE COMPLIANCE WITH: TABLE 803.3 MINIMUM |
| | INTERIOR FINISH CLASSIFICATION; PROVIDE INFORMATION |
| | BASED ON INTERIOR FINISH REQUIREMENTS BASED ON |
| | OCCUPANCY. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |