Plan Review Details - Permit 10020252
Plan Review Stops For Permit 10020252
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-03-30 Cont ID  
Sent By jwitmer Date 2010-03-30 Time 10:54 Rev Time 0.55
Received By jwitmer Date 2010-03-30 Time 10:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-02-24 Cont ID  
Sent By jwitmer Date 2010-02-24 Time 16:04 Rev Time 1.33
Received By jwitmer Date 2010-02-24 Time 16:04 Sent To  
Notes
2010-02-24 16:51:50BUILDING PLAN REVIEW
 PERMIT: 10020252
 ADD: 5707 S DIXIE # 3
 CONT: BROUGHTON CONSTRUCTION, LLC
 TEL: (561)644-4488
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 FEB. 24/ 2010
  
 1) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY: A) THE EDITION OF THE CODE UNDER WHICH
 THE PROJECT IS DESIGNED. PLEASE ALSO NOTE COMPLIANCE
 WITH THE 2007 FBC EXISTING BUILDING CODE AND SECTION
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) THE PERMIT APPLICATION INDICATES UNDER THE
 DESCRIPTION OF WORK THE CUTTING OF EXISTING SLAB.
 ADDITIONAL INFORMATION IS REQUIRED. 106.1.2
 ADMINISTRATIVE CODE.
 2A) PLANS FAIL TO INDICATE COMPLIANCE WITH TERMITE
 TREATMENT OF SOILS WHERE SLAB HAS BEEN CUT AND GRADE
 DISTURBED. 1816.1 TERMITE PROTECTION. TERMITE
 PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL-APPLIED PESTICIDES,
 BAITING SYSTEMS AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT.
 2B) PLANS FAIL TO INDICATE WHAT TYPE OF MATERIALS WILL
 BE USED FOR THE NEW FLOOR SYSTEM. IF CONCRETE AND HOW
 THE NEW SECTION OF FLOOR WILL BE SECURED TO THE
 EXISTING FLOOR SLAB.
  
 3) SHEET# 1 THE DOORWAY LEADING INTO THE BREAK ROOM
 DOES NOT PROVIDE THE SIZE OF THE DOOR, NOR DOES THE
 PLANS INDICATE COMPLIANCE WITH SECTION:
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 4) SHEET# 1 INDICATES A 2HR FIRE SEPARATION REQUIRED.
 TENANT SEPARATION WALLS COVERED UNDER FBC-B 708 ONLY
 REQUIRE 1 HOUR SEPARATION. IF OCCUPANCY SEPARATION IS
 TO BE CONSIDERED WE WILL NEED TO SEE WHAT OCCUPANCIES
 ARE ON BOTH SIDES OF THIS TENANT TO DETERMINE THE HOUR
 RATING, TABLE 508.3.3. NOTE PLANS INDICATE 2 HR
 SEPARATION. AN AREA OF CONCERN THE MECHANICAL REVIEW
 WILL DWELL ON WILL BE VENTILATION REQUIREMENTS FOR THE
 MANICURE AND PEDICURE STATIONS, HOW WILL THE
 VENTILATION REQUIREMENTS BE MET AND WILL THE
 TENANT SEPARATION WALLS BE CUT FOR THE ADDITIONAL
 DUCTWORK. DETAILS WILL BE NEEDED POSSIBLY FOR
 PENETRATIONS OF FIRE RATED TENANT SEPARATION WALLS,
 PLEASE SEE FBC-B SECTION 712.
  
 5) PLEASE PROVIDE DETAILS FOR BREAK ROOM COUNTER AND
 SINK. SINKS: 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER NO HIGHER THAN 34" ABOVE THE
 FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 6) PLANS FAIL TO INDICATE THE LOCATION OF THE PORTABLE
 FIRE EXTINGUISHER. FBC-B 906.1 GENERAL. PORTABLE FIRE
 EXTINGUISHERS SHALL BE PROVIDED IN OCCUPANCIES AND
 LOCATIONS AS REQUIRED BY THE FLORIDA FIRE PREVENTION
 CODE.
  
 7) PLEASE PROVIDE COMPLIANCE WITH: TABLE 803.3 MINIMUM
 INTERIOR FINISH CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS BASED ON
 OCCUPANCY.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-04-01 Cont ID  
Sent By btrobaug Date 2010-04-01 Time 14:01 Rev Time 0.00
Received By btrobaug Date 2010-04-01 Time 13:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-18 Cont ID  
Sent By dpalmer Date 2010-02-18 Time 13:24 Rev Time 0.00
Received By dpalmer Date 2010-02-18 Time 13:24 Sent To  
Notes
2010-02-18 13:24:21*DENIED **
  
 1) NOTE: PLANS ARE REQUIRED TO CONTAIN CODES FOR DESIGN
 BASED ON THE APPLICATION DATE.
 ALL PERMIT APPLICATIONS AFTER OCTOBER 1ST, 2009 SHALL
 BE UNDER THE FOLLOWING ADOPTED CODES.
 2008 NFPA-70
 2006 NFPA-101
 2007 FBC W/2009 SUPPLEMENTS.
  
 2) NOTE: PLANS ARE MISSING A REQUIRED DESIGN
 PROFESSIONAL PER FS 471.003, 481.229, 489. ALL SHEETS
 EXCEPT ELECTRICAL CONTAIN A TITLE BLOCK FOR AN ENGINEER
 ALONG WITH SIGNATURE AND SEAL. HOWEVER ELECTRICAL
 SHEETS DO NOT CONTAIN ANY RESPONSIBLE DESIGNER AS
 REQUIRED.
  
 3) NOTE: PLEASE SHOW ALL CIRCUITING ON PLANS AND
 COORDINATE WITH THE SUBMITTED PANEL SCHEDULE. LOADS ON
 CIRCUITS, WIRING, OVER CURRENT PROTECTION ETC NEEDS TO
 BE VERIFIED.
 PLEASE ALSO SEE 700.12F FOR CIRCUITING OF EMERGENCY
 LIGHTS TO LOCAL LIGHTING BRANCH CIRCUIT.
 240.4,408.4, 310.16 ETC
  
 3) NOTE: MISSING REQUIRED LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.AB.5. NOT ALL LIGHTING IS SHOWN
 ON PLANS AS EXISTING. PLEASE ALSO INCLUDE SPECIFIC
 FIXTURE INFORMATION AS REQUIRED TO VERIFY MINIMUM CODE
 COMPLIANCE.
  
 4) NOTE: PLEASE SEE FBC 13-415.AB.1.1,.1.2, .1.3 FOR
 MISSING REQUIRED AUTOMATED LIGHTING CONTROLS. THIS IS A
 TENANT SPACE IN A BUILDING GREATER THAN 5K SQ FT.
  
 5) NOTE: PLEASE SEE THE LOAD CALCULATIONS AS THE LOAD
 SHOWN FOR SHOW WINDOW ONLY INCLUDES WHAT IS SHOWN AS
 FIVE LINEAR FT OF WINDOW.
 THE PLANS INDICATE TWO FIVE FOOT WINDOWS. PLEASE ADJUST
 LOADS.
 220.43A, 220.14G
  
 6) NOTE: PLEASE SEE 600.5 FOR REQUIRED MISSING SIGN
 CIRCUIT. PLEASE ALSO BE SURE TO ADD REQUIRED MINIMUM
 LOAD.
  
 7) NOTE: PLEASE VERIFY THE METHOD OF EQUIPMENT
 GROUNDING FROM MAIN TO PANEL.
 250.110,250.122
  
 8) NOTE: PLEASE SEE 422.13 WHICH REQUIRE STORAGE TYPE
 WATER HEATER LOADS TO BE FIGURED AT 125%. PLEASE SEE
 COMMENTARY WHICH WAS REVISED IN THE 2005 NEC AS THIS
 LOAD IS CONSIDERED CONTINUOUS.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-03-29 Cont ID  
Sent By mcarsill Date 2010-03-29 Time 11:55 Rev Time 0.00
Received By mcarsill Date 2010-03-29 Time 11:50 Sent To  
Notes
2010-03-29 11:55:16 
 5707 SOUTH DIXIE HIGHWAY
  
  
 1. INTERIOR FINISH CLASSIFICATIONS SHALL BE CLASS A OR
 B IN EXITS AND IN EXIT ACCESS CORRIDORS. RE: FFPC
 SECTION 38.3.3.2.1 INTERIOR WALL AND CEILING FINISHES
 SHALL BE CLASS A, CLASS B, OR CLASS C IN AREAS OTHER
 THAN THOSE SPECIFIED IN 38.3.3.2.1. RE: FFPC SECTION
 38.3.3.2.2.
  
 APPROVED PROVISIO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4724 PHONE
 (561) 804-4774 FAX
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-02-22 Cont ID  
Sent By mawillia Date 2010-02-22 Time 15:59 Rev Time 0.00
Received By mawillia Date 2010-02-22 Time 15:21 Sent To  
Notes
2010-02-22 15:59:03*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS TO COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 3. SPECIFY THE NEW BREAK/UTILITY ROOM'S INTERIOR FINISH
 MATERIALS FOR THE WALLS AND CEILINGS IN TERMS OF CLASS
 A, CLASS B, OR CLASS C.
  
 4. PROVIDE DETAILS FOR THE NEW BREAK/UTILITY ROOM'S
 DOOR.
  
 5. SHOW THE LOCATION OF THE PORTABLE FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-03-17 Cont ID  
Sent By rmcdouga Date 2010-03-16 Time 10:49 Rev Time 0.00
Received By rmcdouga Date 2010-03-16 Time 10:49 Sent To  
Notes
2010-03-17 10:54:57TO C-20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-03-04 Time   Rev Time 0.00
Received By kstevens Date 2010-02-11 Time 09:15 Sent To  
Notes
2010-02-11 09:23:26SENT TO C-15.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2010-04-14 Cont ID  
Sent By hmoser Date 2010-04-14 Time 13:36 Rev Time 0.00
Received By hmoser Date 2010-04-14 Time 13:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2010-04-01 Cont ID  
Sent By hmoser Date 2010-04-01 Time 14:35 Rev Time 0.00
Received By hmoser Date 2010-04-01 Time 14:35 Sent To  
Notes
2010-04-01 14:39:13PLAN DENIED
 PLEASE REFER TO TABLE 403.3 FOOT NOTE (I) 2007 FBC (M)
 .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-03-04 Cont ID  
Sent By rregueir Date 2010-03-04 Time 14:29 Rev Time 0.00
Received By rregueir Date 2010-03-04 Time 14:23 Sent To  
Notes
2010-03-04 14:29:01REVIEW #: 1SY
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLANS INDICATE SPACE BEING FITTED FOR HAIR AND NAIL
 SALON. NO MECHANICAL SCOPE OF WORK IS SHOWN ON
 SUBMITTED PLANS. HAIR AND NAIL SALONS HAVE SPECIFIC
 VENTILATION REQUIREMENTS. DEMONSTRATE ON PLANS HOW THE
 VENTILATION REQUIREMENTS FOR THIS USE OF THE SPACE ARE
 TO BE MET IN ACCORDANCE WITH FBC-EB 901.2 OR 901.3 AND
 FBC-M SECTION 403.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-04-07 Cont ID  
Sent By lwagner Date 2010-04-07 Time 09:32 Rev Time 0.00
Received By lwagner Date 2010-04-07 Time 09:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-03-03 Cont ID  
Sent By kstevens Date 2010-03-03 Time 10:00 Rev Time 0.00
Received By kstevens Date 2010-03-03 Time 10:00 Sent To  
Notes
2010-03-03 10:45:34DENIED
 REFERENCE;
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007CHAPTER 11
  
 1. SHT 1 THE BREAKROOM SINK SHALL BE ACCESSIBLE. SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCES
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED)
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
  
 1A. A 5 FOOT TURNING AREA IS REQUIRED IN THE BREAKROOM.
 SECTION 11-4.2.3.
  
 2. SHT P1 THE PRINTED NAME AND SIGNATURE OF THE PERSON
 DESIGNING THE PLUMBING SHALL BE ON THE SHEET. SECTION
 106.1.
  
 3. SHT P1 THE SANITARY RISER DIAGRAM DOES NOT MEET
 CODE. THE WASH MACHINE FIXTURE DRAIN SHALL CONNECT TO A
 BRANCH DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES IN
 DIAMETER PER SECTION 406.3 AND SHALL HAVE A STANDPIPE A
 MINIMUM 18 INCHES AND A MAXIMUM OF 48 INCHES ABOVE THE
 TRAP WEIR PER SECTION 802.4. ALSO THE PEDICURE CHAIR IS
 NOT VENTED. SECTIONS 901.2 & 901.2.1.
  
 4. SHT P1 THE WATER ISOMETRIC DOES NOT MEET CODE. WATER
 HAMMER ARRESTORS ARE REQUIRED AT THE WASH MACHINE PER
 SECTION 604.9 AND SHALL BE LOCATED NEAR THE FIXTURE IN
 AN "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201. --
 SHOW ALL PIPE SIZES FOR THE WATER PIPING, AS WELL AS
 ALL PIPING TO THE PEDICURE CHAIR & THE SHAMPOO SINKS.
 SECTION 106.3.5.1.3.
  
 5. SHT P1 WATER ISOMETRIC, A FULL OPEN VALVE IS
 REQUIRED ON THE WATER SUPPLY PIPE TO THE WATER HEATER
 PER SECTION 606.2(7) AND THERMAL EXPANSION CONTROL IS
 REQUIRED PER 607.3.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2010-02-16 Cont ID  
Sent By eschneid Date 2010-02-16 Time 09:57 Rev Time 0.20
Received By eschneid Date 2010-02-16 Time 09:54 Sent To  
Notes
2010-02-16 09:58:57PERMIT DOES NOT TRIGGER 50% OF BUILDING VALUE.