Plan Review Details - Permit 10020238
Plan Review Stops For Permit 10020238
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-03-31 Cont ID  
Sent By btrobaug Date 2010-03-31 Time 15:56 Rev Time 0.00
Received By btrobaug Date 2010-03-31 Time 15:02 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-17 Cont ID  
Sent By dpalmer Date 2010-02-17 Time 14:50 Rev Time 0.00
Received By dpalmer Date 2010-02-17 Time 14:50 Sent To  
Notes
2010-02-17 14:50:14*DENIED **
  
 1) NOTE: PLANS SHALL CONTAIN MINIMUM ADOPTED CODES.
 PLANS MAY NOT STATE * LATEST EDITION*. ALL PERMIT
 APPLICATIONS AFTER OCTOBER 1ST, 2009 SHALL BE UNDER THE
 2008 NEC.
 NO OTHER CODE EDITIONS WERE SHOWN.
  
 2) NOTE: NO CONDUCTORS, WIRING SIZES, OR CONDUIT
 INFORMATION IS SHOWN ON PLANS.
 310.16,240.4, SEE ALL OF NEC 514.,514.4,514.7,514.8
 CAN NOT REVIEW FOR CODE COMPLIANCE OF MINIMUM
 CONDUCTORS, CIRCUITING ETC WITH THE INFORMATION NOT
 SHOWN ON THE PLANS.
  
 3) NOTE: PLEASE SHOWN NEW OR EXISTING LOCATION FOR
 EMERGENCY SHUT OFF PER 514.11A,B,C.
  
 4) NOTE: PLEASE SEE 514.16 FOR GROUNDING REQUIREMENTS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-03-29 Cont ID  
Sent By mcarsill Date 2010-03-29 Time 12:32 Rev Time 0.00
Received By mcarsill Date 2010-03-29 Time 12:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-02-22 Cont ID  
Sent By mcarsill Date 2010-02-22 Time 14:03 Rev Time 0.00
Received By mcarsill Date 2010-02-22 Time 13:56 Sent To  
Notes
2010-02-22 14:03:38UNDERGROUND STORAGE TANK (UST)
 3031 OKEECHOBEE BOULEVARD
 PERMIT # 10020238
  
 1. THE REMOVAL AND INSTALLATION OF THE OLD AND NEW
 UNDERGROUND STORAGE TANKS SHALL COMPLY WITH NFPA 30 AND
 NFPA 30A.
  
 2. COULD NOT LOCATE EXISTING FUEL DISPENSING PUMPS AND
 EMERGENCY DISCONNECT TO BE USED WITH THE NEW
 UNDERGROUND STORAGE TANK.
  
 3. THE REMOVAL OF THE EXISTING FUEL TANK AND
 APPURTENANT EQUIPMENT MUST BE DONE SAFELY AND IN
 ACCORDANCE WITH RECOGNIZED SAFETY PRACTICES.
  
 4. PLEASE PROVIDE PRODUCT DATA ON THE PROPOSED
 UNDERGROUND STORAGE TANK.
  
 5. PLEASE EXPLAIN HOW THE EMERGENCY DISCONNECT FOR THE
 FUEL STORAGE TANK WILL BE IDENTIFIED.
  
 6. PLEASE INDICATE APPROPRIATE THIRD-PARTY LISTINGS FOR
 THE UNDERGROUND STORAGE TANK AND APPURTENANT EQUIPMENT.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-03-16 Cont ID  
Sent By rmcdouga Date 2010-03-15 Time 08:13 Rev Time 0.00
Received By rmcdouga Date 2010-03-15 Time 08:13 Sent To  
Notes
2010-03-16 08:31:00TO C4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-03-04 Time   Rev Time 0.00
Received By lmartine Date 2010-02-09 Time 17:04 Sent To  
Notes
2010-02-09 17:11:37********************EXPEDITED*********************
 C--8

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-03-26 Cont ID  
Sent By hmoser Date 2010-03-26 Time 09:47 Rev Time 0.00
Received By hmoser Date 2010-03-26 Time 09:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-03-04 Cont ID  
Sent By rregueir Date 2010-03-04 Time 10:16 Rev Time 0.00
Received By rregueir Date 2010-03-04 Time 10:16 Sent To  
Notes
2010-03-04 10:17:10PROVIDE LISTING INFORMATION FOR POLLUTANT STORAGE TANK.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2010-02-16 Cont ID  
Sent By kdfreema Date 2010-02-16 Time 14:34 Rev Time 0.00
Received By kdfreema Date 2010-02-16 Time 14:34 Sent To  
Notes
***NONE***