Plan Review Details - Permit 10020203
Plan Review Stops For Permit 10020203
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-03-18 Cont ID  
Sent By shill Date 2010-03-18 Time 16:39 Rev Time 0.00
Received By shill Date 2010-03-18 Time 13:59 Sent To  
Notes
2010-03-18 16:39:58ESFR SPRINKLERS PER CONTRACTOR
 FRP AT TOILETS & URINALS PER CONTRACTOR PER FBC1210
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-03 Cont ID  
Sent By shill Date 2010-03-03 Time 15:56 Rev Time 0.00
Received By shill Date 2010-03-03 Time 15:56 Sent To  
Notes
2010-03-03 15:57:51****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE PROVIDE RACK HEIGHT AND DISTANCE BETWEEN
 RACKS, FBC106, FBC1005, FBC903.
  
 2. SPECIFY INTERIOR FINISH CLASSIFICATION FBC803.
  
 3. REFERENCE IS MADE TO DOOR RATINGS BUT NONE
 SPECIFIED, FBC715.
  
 4. BREAK ROOM SINK TO BE ACCESSIBLE; PLEASE PROVIDE
 DETAILS FBC11-4.24. THE BASE IS SHOWN CONTINUOUS;
 PLEASE SHOW HOW THIS COMPLIES WITH THE REQUIREMENTS OF
 FBC11-4.24.
  
 5. SEE FBC TABLE 1004.1 AND EXPLAIN OCCUPANT LOAD. F1
 IS DECLARED AS OCCUPANCY CLASSIFICATION, BUT 500 SF PER
 PERSON WAS CALCULATED. THIS IS FOR WAREHOUSE SPACE;
 MANUFACTURING AREAS ARE TO BE 200SF PER PERSON,
 STORAGE/STOCK/SHIPPING AREAS ARE TO BE 300 SF PER
 PERSON. IF THIS IS A DISTRIBUTION CENTER, IT APPEARS
 THAT AT A MINIMUM 300SF PER PERSON SHOULD BE USED TO
 CALCULATE OCCUPANT LOAD.
  
 6. FBC1210, SEE REQUIREMENT FOR WALL FINISH
 (BATHROOMS).
  
 7. FIRE SPRINKLER PLANS (AT MINIMUM, HEAD LAYOUT)
 REQUIRED PRIOR TO PERMIT ISSUANCE PER
 FBC*106.3.5.1.1(5), FS553.79 (2). WILL THIS BE APPLIED
 FOR PRIOR TO PERMIT ISSUANCE?
  
 8. PLEASE CHECK ENERGY CALCS. NO DOORS SHOWN (3 DOORS
 IN COMMON WALL SHOWN), R21 SHOWN FOR ROOF (PLEASE SHOW
 WHERE ACOUSTIC CEILING CAN BE USED; R19 IS SHOWN ON
 SHELL). CONFIRM THAT OTHER ITEMS ARE ACCURATE.
  
 9. VALUATION HAS BEEN ADJUSTED PER ICC VALUATION
 TABLES, FEBRUARY 2010. AT TIME OF SHELL CONSTRUCTION,
 THE OWNER PROVIDED A VALUE OF APPROXIMATELY $55.72 PER
 SQ FT. ($3,082,427 FOR 55,312 SF). BASED ON ICC TABLES,
 THE VALUE OF OFFICE SPACE CONSTRUCTION IS $122.71, F1
 IS $69.92. THE VALUE HAS BEEN ADJUSTED TO A TOTAL OF
 $1,845,881 LESS CREDIT FOR AMOUNT PAID ON THIS PORTION
 OF THE SHELL ($1,350,122). TOTAL VALUATION $495,759.
 PLEASE CONTACT ME IF YOU WISH TO DISCUSS.
  
 IF YOU WISH TO DISCUSS ANY OF THE ABOVE ITEMS, PLEASE
 DO NOT HESITATE TO CONTACT ME AT YOUR CONVENIENCE.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-03-23 Cont ID  
Sent By lmartine Date 2010-03-23 Time 11:57 Rev Time 0.00
Received By lmartine Date 2010-03-23 Time 11:57 Sent To  
Notes
2010-03-23 11:57:47SEE APPROVAL ON PLANS BY DOUG WISE

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-23 Cont ID  
Sent By btrobaug Date 2010-02-23 Time 10:43 Rev Time 0.00
Received By btrobaug Date 2010-02-23 Time 10:38 Sent To  
Notes
2010-02-23 10:43:11 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING.
  
 1} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1*** SHOW COMPLIANCE ON THE PLAN. THIS
 CAN BE DEMONSTRATED ON THE PLANS INDICATING THE
 WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT
 CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES
 ON THE FIXTURE SCHEDULE TO CORRELATE WITH THE ONES IN
 THE CALCULATIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-03-22 Cont ID  
Sent By mawillia Date 2010-03-22 Time 14:21 Rev Time 0.00
Received By mawillia Date 2010-03-22 Time 13:49 Sent To  
Notes
2010-03-22 13:54:54*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS A-1, A-2, A-3, A-5, A-7,
 E1, AND E3 WERE STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-03-01 Cont ID  
Sent By mawillia Date 2010-03-01 Time 14:04 Rev Time 0.00
Received By mawillia Date 2010-03-01 Time 12:41 Sent To  
Notes
2010-03-01 13:23:28*****DENIED*****
  
  
 1. THE ACTUAL PROJECT SITE ADDRESS SHALL BE INCLUDED ON
 THE COVER SHEET OF ANY SUBMITTALS AND IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2. ARE THERE MORE THAN ONE BUILDING USING THE SAME
 NUMERICAL ADDRESS DESIGNATION? THE USE OF BUILDING
 NUMBERS SHALL NOT BE LISTED UNLESS THERE ARE MORE THAN
 ONE BUILDING USING THE SAME NUMERICAL ADDRESS.
  
 3. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 4. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 5. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS
 AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6. LIST THE RATING FOR ALL FIRE-RATED DOORS.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-03-09 Cont ID  
Sent By btrobaug Date 2010-03-09 Time 16:34 Rev Time 0.00
Received By btrobaug Date 2010-03-09 Time 16:34 Sent To  
Notes
2010-03-09 16:34:51B-7

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-03-03 Cont ID  
Sent By shill Date 2010-03-03 Time 16:08 Rev Time 0.00
Received By shill Date 2010-02-08 Time 16:48 Sent To  
Notes
2010-02-08 16:48:31B-5

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-03-03 Cont ID  
Sent By shill Date 2010-03-03 Time 15:28 Rev Time 0.00
Received By shill Date 2010-03-03 Time 15:28 Sent To  
Notes
2010-03-03 15:28:56PR 08005359 CHECKED BY GWEN - NO IMPACT FEES REQUIRED
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-03-23 Cont ID  
Sent By rregueir Date 2010-03-23 Time 10:23 Rev Time 0.00
Received By rregueir Date 2010-03-23 Time 10:22 Sent To  
Notes
2010-03-23 10:22:36NEW SHEETS SUBMITTED, PROVISOS WERE NOT ADDRESSED.
  
 **PROVISO**
  
 1. PROVIDE MANUFACTURER'S DATA FOR WIND RESISTANCE
 CAPABILITIES OF RTU AND ROOF EXHAUST FAN. ALSO PROVIDE
 INSTALLATION DETAIL FOR EXHAUST FAN. FBC-M 301.12.
  
 2. EXHAUST FANS EF-1 AND EF-3 ARE REQUIRED TO PROVIDE
 MINIMUM 100 CFM EACH PER ASHRAE 62.1 TABLE 6-4.
  
 3. RETURN AIR TRANSFER DUCTS IN TOOMS 102 AND 110 ARE
 TOO SMALL TO MEET THE BALANCED RETURN AIR EXCEPTIONS
 UNDER FBC-M 601.4.
  
 REVISE PLANS AND RESUBMIT ACCORDINGLY PRIOR TO
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-03-02 Cont ID  
Sent By rregueir Date 2010-03-02 Time 10:57 Rev Time 0.00
Received By rregueir Date 2010-03-02 Time 10:57 Sent To  
Notes
2010-03-02 11:03:00**PROVISO**
  
 1. PROVIDE MANUFACTURER'S DATA FOR WIND RESISTANCE
 CAPABILITIES OF RTU AND ROOF EXHAUST FAN. ALSO PROVIDE
 INSTALLATION DETAIL FOR EXHAUST FAN. FBC-M 301.12.
  
 2. EXHAUST FANS EF-1 AND EF-3 ARE REQUIRED TO PROVIDE
 MINIMUM 100 CFM EACH PER ASHRAE 62.1 TABLE 6-4.
  
 3. RETURN AIR TRANSFER DUCTS IN TOOMS 102 AND 110 ARE
 TOO SMALL TO MEET THE BALANCED RETURN AIR EXCEPTIONS
 UNDER FBC-M 601.4.
  
 REVISE PLANS AND RESUBMIT ACCORDINGLY PRIOR TO
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-03-22 Cont ID  
Sent By lwagner Date 2010-03-22 Time 12:53 Rev Time 0.00
Received By lwagner Date 2010-03-22 Time 12:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-02-18 Cont ID  
Sent By kstevens Date 2010-02-18 Time 13:35 Rev Time 0.00
Received By kstevens Date 2010-02-17 Time 16:50 Sent To  
Notes
2010-02-18 13:55:48DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 BUILDING
 FBC-2007 CHAPTER 11
  
 1. PER TABLE 403.1 TWO DRINKING FOUNTAINS ARE REQUIRED.
 (ONE FOR BUSINESS OCCUPANCY & ONE FOR STORAGE
 OCCUPANCY). A HI/LOW DRINKING FOUNTAIN IS CONSIDERED
 ONE FIXTURE AS IT HAS ONLY ONE SUPPLY & ONE TRAP.
 SECTION 1002.1. (ALSO SEE SECTION 410.1).
  
 2. SUBMIT A DETAIL FOR THE BREAK ROOM SINK SHOWING
 COMPLIANCE WITH SECTION 11-4.24 WITH ALL SUBSECTIONS.
 SUBMIT AN ELEVATION SHOWING THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED - CABINET DOORS NOT APPROVED)
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
  
 3. SHT A-3 PER SECTION 1210.2 OF THE BUILDING CODE,
 WALLS WITHIN 2 FEET OF URINALS & WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE TO A HEIGHT
 UP TO 4 FEET ABOVE THE FLOOR. PAINTED WRB DOES NOT
 COMPLY WITH THE REQUIREMENT FOR A HARD SURFACE.
  
 4. SHTS P1 FLOOR PLAN AND P3 SANT RISER DIAGRAM. THE
 BREAK ROOM SINK SHALL NOT DRAIN THROUGH THE WET VENT
 FOR THE TOILET ROOM FIXTURES. SECTION 909.1. THE
 FIXTURE SHALL DISCHARGE DOWNSTREAM OF THE TOILET ROOM
 FIXTURES.
  
 5. SHT P3 WATER ISOMETRIC RISER DIAGRAM. AIR CHAMBERS
 ARE NOT APPROVED. PLEASE DELETE. THE WATER HAMMER
 ARRESTOR LOCATED IN THE CEILING ABOVE THE DRINKING
 FOUNTAIN SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE". PDI-WH 201.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2010-03-16 Cont ID  
Sent By eschneid Date 2010-03-16 Time 13:56 Rev Time 0.50
Received By eschneid Date 2010-03-16 Time 13:56 Sent To  
Notes
2010-03-16 13:58:35PASSED W/PROVISO
  
 SUBMIT REVISED TRAFFIC EQUIVILANCY LETTER PRIOR TO C.O.
 IF PERMIT IS ISSUED PRIOR TO SUBMITTAL THEN LETTER
 SHALL BE A REVISION. IF PERMIT IS NOT ISSUED PRIOR TO
 SUBMITTAL THEN LETTER SHALL BE A RESUBMITTAL.
  
 CONTACT ERIC SCHNEIDER (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-02-16 Cont ID  
Sent By eschneid Date 2010-02-16 Time 10:29 Rev Time 0.25
Received By eschneid Date 2010-02-16 Time 10:29 Sent To  
Notes
2010-02-16 10:42:16FAILED
  
 1) THE PLANS COMPLY WITH ZONING REQUIREMENTS. THE
 INFORMATION TO SATISFY THE TRAFFIC CONDITION IN #2
 BELOW HAS NOT BEEN PROVIDED. ONCE THE INFORMATION IS
 SUFFICIENTLY PROVIDED, ZONING WILL CHANGE TO A "PASS"
 STATUS.
  
 2) PER ORDINANCE NO. 3987-06:
  
 A. A USE CHART SHALL BE SUBMITTED TO THE PLANNING AND
 ZONING AND CONSTRUCTION SERVICES DEPARTMENTS CONCURRENT
 WITH ALL BUILDING PERMIT AND/OR OCCUPATIONAL LICENSE
 APPLICATIONS STATING THE SQUARE FOOTAGE DEVOTED TO THE
 USES WITHIN BUILDINGS 1, 2 AND 3. THE SPECIFIC SQUARE
 FOOTAGE USE WITHIN EACH BUILDING MAY NOT EXCEED THE
 ALLOWANCES OUTLINED IN THE BUILDING USE SQUARE FOOTAGE
 TABLE (BELOW FOR BUILDING #1), UNLESS THE PROPERTY
 OWNER PROVIDES A TRAFFIC EQUIVALENCY STATEMENT,
 PREPARED BY A LICENSED TRAFFIC ENGINEER, DEMONSTRATING
 THAT THE APPROVED TRAFFIC CONCURRENCY FOR THE PROJECT
 IS NOT EXCEEDED.
  
 USE MAXIMUM SQUARE FOOTAGE
 OFFICE/SHOWROOM 13,607
 INDUSTRIAL 8,164
 WHOLESALE 8,164
 WAREHOUSE 24,957
 STORAGE MEZZANINE 13,760
  
  
 B. A TRAFFIC STATEMENT, PREPARED BY A LICENSED TRAFFIC
 ENGINEER, SHALL BE SUBMITTED TO THE PLANNING AND ZONING
 AND CONSTRUCTION SERVICES DEPARTMENTS CONCURRENT WITH
 ALL BUILDING PERMIT APPLICATIONS OUTLINING THE NUMBER
 OF DAILY TRIPS, AM TRIPS AND PM TRIPS GENERATED FOR
 EACH USE AND ITS SQUARE FOOTAGE FOR EACH BUILDING. THE
 TRAFFIC STATEMENT SHALL INCLUDE THE TRIPS ASSOCIATED
 WITH THE SPECIFIC USE AND A CUMULATIVE TABLE FOR ALL OF
 THE USES APPROVED IN THE PREMIER PARK OF COMMERCE CPD.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  