Plan Review Details - Permit 10020094
Plan Review Stops For Permit 10020094
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-03-15 Cont ID  
Sent By jwitmer Date 2010-03-15 Time 09:54 Rev Time 0.40
Received By jwitmer Date 2010-03-15 Time 09:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-02-11 Cont ID  
Sent By jwitmer Date 2010-02-11 Time 15:52 Rev Time 0.55
Received By jwitmer Date 2010-02-11 Time 15:52 Sent To  
Notes
2010-02-11 15:59:15BUILDING PLAN REVIEW
 PERMIT: 10020094
 ADD: 410 N OLIVE
 CONT: METRO ELECTRIC SERV
 TEL: (305)945-1991
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET E2 INDICATES IN THE NOTES A POLE LENGTH OF 34
 FEET AND A EMBEDMENT DEPTH OF 9 FEET BUT THTE DETAILS
 INDICATE THE 3"X5" HAND HOLE TO BE 7'-6" ABOVE THE
 BOTTOM OF THE POLE, THIS PLACES THTE HAND HOLE WITH
 ALUMINUM COVER 1'-6" BELOW GRADE!
  
 106.1.2 PLEASE PROVIDE EXPLANATION AS TO THE 3"X5" HAND
 HOLE BEING BELOW GRADE!
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-03-18 Cont ID  
Sent By btrobaug Date 2010-03-18 Time 14:11 Rev Time 0.00
Received By btrobaug Date 2010-03-18 Time 13:33 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2010-03-03 Cont ID  
Sent By dpalmer Date 2010-03-03 Time 14:18 Rev Time 0.00
Received By dpalmer Date 2010-03-03 Time 14:18 Sent To  
Notes
2010-03-03 14:19:13* DENIED 2ND REVIEW**
  
 1) NOTE: PLEASE SEE NOTES FORM PREVIOUS REVIEW.
  
 IF THERE ARE QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-10 Cont ID  
Sent By dpalmer Date 2010-02-10 Time 16:14 Rev Time 0.00
Received By dpalmer Date 2010-02-10 Time 16:14 Sent To  
Notes
2010-02-10 16:15:06 
 ** DENIED
  
 1) NOTE: PLEASE SEE FBC 13-415.AB.1.4 FOR EXTERIOR
 LIGHTING CONTROLS REQUIRED. IT IS NOT PERMISSIBLE TO
 USE SINGLE POLE SWITCHES AS THE OVER RIDES/CONTROLS.
  
 2) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE/DENSITY
 CALCULATIONS PER 13-415.AB.2.2.
  
 3) NOTE: PLEASE COORDINATE PLANS. THE SERVICE RISER
 INDICATES A 120/208V SERVICE YET, THE SITE PLANS
 INDICATE PANEL AS 120/240V.
 220,215,230, GIVEN AS GENERAL FOR COORDINATION.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-03-16 Cont ID  
Sent By shill Date 2010-03-16 Time 09:40 Rev Time 0.00
Received By shill Date 2010-03-16 Time 09:40 Sent To  
Notes
2010-03-18 11:15:13CLERICAL ERROR, PLANS WERE PROPERLY ROUTED TO THE
 ELECTRICAL REVIEWER
 LM 3/18
2010-03-16 09:41:07TO PLUMBING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-02-25 Cont ID  
Sent By kstevens Date 2010-02-25 Time 08:27 Rev Time 0.00
Received By kstevens Date 2010-02-25 Time 08:27 Sent To  
Notes
2010-02-25 08:27:21SENT TO C-14.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-02-04 Cont ID  
Sent By jwitmer Date 2010-02-04 Time 08:35 Rev Time 0.00
Received By jwitmer Date 2010-02-04 Time 08:35 Sent To  
Notes
2010-02-04 08:36:23INCOMING TO C-6

Review Stop Z ZONING
Rev No 2 Status P Date 2010-03-09 Cont ID  
Sent By aaponte Date 2010-03-09 Time 14:54 Rev Time 0.00
Received By aaponte Date 2010-03-09 Time 14:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-02-17 Cont ID  
Sent By aaponte Date 2010-02-17 Time 15:12 Rev Time 0.00
Received By aaponte Date 2010-02-17 Time 15:12 Sent To  
Notes
2010-02-17 15:14:36PLEASE INDICATE PROPERTY LINE AND EDGE OFCURB LINE TO
 VERIFY THAT THE MAXIMUM FOOTCANDLE AT THE EDGE OF CURB
 DOES NOT EXCEEDS 1.0 FOOTCANDLE. (SECTION 94-113(B))
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE 561-822-1439