Plan Review Details - Permit 10020057
Plan Review Stops For Permit 10020057
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-02-18 Cont ID  
Sent By jwitmer Date 2010-02-18 Time 11:30 Rev Time 0.55
Received By jwitmer Date 2010-02-18 Time 11:30 Sent To  
Notes
2010-02-18 11:41:52BUILDING PLAN REVIEW
 PERMIT: 09100528/ REV 10020057
 ADD:101 NORTHPOINT PKWY # 105
 CONT: ANDERSON MOORE CONSTRUCTION
 TEL: (561)662-1819
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW REVISION
 SHEET LA-1
  
 BUILDING PROVISO:
  
 11-4.1.2 ACCESSIBLE SITE AND EXTERIOR FACILITIES:
 (7) BUILDING SIGNAGE. SIGNS WHICH DESIGNATE PERMANENT
 ROOMS AND SPACES SHALL COMPLY WITH SECTIONS 11-4.30.1,
 11-4.30.4, 11-4.30.5 AND 11-4.30.6. OTHER SIGNS WHICH
 PROVIDE DIRECTION TO, OR INFORMATION ABOUT, FUNCTIONAL
 SPACES OF THE BUILDING SHALL COMPLY WITH SECTIONS
 11-4.30.1, 11-4.30.2, 11-4.30.3, AND 11-4.30.5.
 ELEMENTS AND SPACES OF ACCESSIBLE FACILITIES WHICH
 SHALL BE IDENTIFIED BY THE INTERNATIONAL SYMBOL OF
 ACCESSIBILITY AND WHICH SHALL COMPLY WITH SECTION
 11-4.30.7 ARE:
  
 (C) ACCESSIBLE ENTRANCES WHEN NOT ALL ARE ACCESSIBLE
 (INACCESSIBLE ENTRANCES SHALL HAVE DIRECTIONAL SIGNAGE
 TO INDICATE THE ROUTE TO THE NEAREST ACCESSIBLE
 ENTRANCE);
  
 11-4.30 SIGNAGE:
 11-4.30.3 CHARACTER HEIGHT. CHARACTERS AND NUMBERS ON
 SIGNS SHALL BE SIZED ACCORDING TO THE VIEWING DISTANCE
 FROM WHICH THEY ARE TO BE READ. THE MINIMUM HEIGHT IS
 MEASURED USING AN UPPER CASE "X." LOWER CASE CHARACTERS
 ARE PERMITTED.
  
 MINIMUM CHARACTER HEIGHT 3 INCHES (75 MM) MINIMUM
  
 11-4.30.4 RAISED AND BRAILLED CHARACTERS AND PICTORIAL
 SYMBOL SIGNS (PICTOGRAMS). LETTERS AND NUMERALS SHALL
 BE RAISED 1/32 INCHES (.8 MM), UPPER CASE, SANS SERIF
 OR SIMPLE SERIF TYPE AND SHALL BE ACCOMPANIED WITH
 GRADE 2 BRAILLE. RAISED CHARACTERS SHALL BE AT LEAST
 5/8 INCHES (16 MM) HIGH, BUT NO HIGHER THAN 2 INCHES
 (51 MM). PICTOGRAMS SHALL BE ACCOMPANIED BY THE
 EQUIVALENT VERBAL DESCRIPTION PLACED DIRECTLY BELOW THE
 PICTOGRAM. THE BORDER DIMENSION OF THE PICTOGRAM SHALL
 BE 6 INCHES (152 MM) MINIMUM IN HEIGHT.
  
 11-4.30.5 FINISH AND CONTRAST. THE CHARACTERS AND
 BACKGROUND OF SIGNS SHALL BE EGGSHELL, MATTE, OR OTHER
 NONGLARE FINISH. CHARACTERS AND SYMBOLS SHALL CONTRAST
 WITH THEIR BACKGROUND???EITHER LIGHT CHARACTERS ON A
 DARK BACKGROUND OR DARK CHARACTERS ON A LIGHT
 BACKGROUND.
  
 11-4.30.6 MOUNTING LOCATION AND HEIGHT. WHERE PERMANENT
 IDENTIFICATION IS PROVIDED FOR ROOMS AND SPACES, SIGNS
 SHALL BE INSTALLED ON THE WALL ADJACENT TO THE LATCH
 SIDE OF THE DOOR. WHERE THERE IS NO WALL SPACE TO THE
 LATCH SIDE OF THE DOOR, INCLUDING AT DOUBLE LEAF DOORS,
 SIGNS SHALL BE PLACED ON THE NEAREST ADJACENT WALL.
 MOUNTING HEIGHT SHALL BE 60 INCHES (1525 MM) ABOVE THE
 FINISH FLOOR TO THE CENTERLINE OF THE SIGN. MOUNTING
 LOCATION FOR SUCH SIGNAGE SHALL BE SO THAT A PERSON MAY
 APPROACH WITHIN 3 INCHES (76 MM) OF SIGNAGE WITHOUT
 ENCOUNTERING PROTRUDING OBJECTS OR STANDING WITHIN THE
 SWING OF A DOOR.
  
 11-4.30.7 SYMBOLS OF ACCESSIBILITY.
 (1) FACILITIES AND ELEMENTS REQUIRED TO BE IDENTIFIED
 AS ACCESSIBLE BY SECTION 11-4.1 SHALL USE THE
 INTERNATIONAL SYMBOL OF ACCESSIBILITY. THE SYMBOL SHALL
 BE DISPLAYED AS SHOWN IN FIGURE 43(A) AND FIGURE 43(B).
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-02-17 Cont ID  
Sent By jwitmer Date 2010-02-17 Time 15:49 Rev Time 0.00
Received By jwitmer Date 2010-02-17 Time 15:49 Sent To  
Notes
2010-02-17 16:49:55BUILDING PLAN REVIEW
 PERMIT: 09100528/ REV 10020057
 ADD:101 NORTHPOINT PKWY # 105
 CONT: ANDERSON MOORE CONSTRUCTION
 TEL: (561)662-1819
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW REVISION
 ACTION: DENIED
  
 1) PLANS SUBMITTED ARE THE LANDSCAPE LA-1 PLEASE ALSO
 UPDATE SHEET A1.0 AND SHEET A3.0. SHEET LA-1 INDICATES
 A NEW STOOP TO PARKING LOT, PLEASE PROVIDE WHERE THE
 ACCESSIBLE ENTRANCE WILL BE FOR THIS OFFICE. THE PLANS
 ONLY INDICATE DOOR # 18 LEADING THROUGH INTO ANOTHER
 PORTION OF THIS OFFICE CURRENTLY WE DO NOT KNOW IF THIS
 IS A REQUIRED
 MEANS OF EGRESS. IF THE OCCUPANT LOAD WOULD REQUIRE TWO
 ENTRANCES TABLE 1019.2OR COMMON PATH OF TRAVEL 1014.3.
 THE OTHER ISSUE IS ACCESSIBILITY.
  
 11-4.1.6 ACCESSIBLE BUILDINGS: ALTERATIONS.
 (B) IF EXISTING ELEMENTS, SPACES, OR COMMON AREAS ARE
 ALTERED, THEN EACH SUCH ALTERED ELEMENT, SPACE,
 FEATURE, OR AREA SHALL COMPLY WITH THE APPLICABLE
 PROVISIONS OF SECTION 11-4.1.1 TO SECTION 11-4.1.3,
 MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION. IF THE
 APPLICABLE PROVISION FOR NEW CONSTRUCTION REQUIRES THAT
 AN ELEMENT, SPACE, OR COMMON AREA BE ON AN ACCESSIBLE
 ROUTE, THE ALTERED ELEMENT, SPACE, OR COMMON AREA IS
 NOT REQUIRED TO BE ON AN ACCESSIBLE ROUTE EXCEPT AS
 PROVIDED IN SECTION 11-4.1.6(2), ALTERATIONS TO AN AREA
 CONTAINING A PRIMARY FUNCTION.
 11-4.1.3(8)
 (A)(I) AT LEAST 50 PERCENT OF ALL PUBLIC ENTRANCES
 [EXCLUDING THOSE IN SECTION 11-4.1.3(8)(B) BELOW] MUST
 BE ACCESSIBLE. AT LEAST ONE MUST BE A GROUND-FLOOR
 ENTRANCE. PUBLIC ENTRANCES ARE ANY ENTRANCES THAT ARE
 NOT LOADING OR SERVICE ENTRANCES.
  
 (II) ACCESSIBLE ENTRANCES MUST BE PROVIDED IN A NUMBER
 AT LEAST EQUIVALENT TO THE NUMBER OF EXITS REQUIRED BY
 THE APPLICABLE BUILDING/FIRE CODES. (THIS PARAGRAPH
 DOES NOT REQUIRE AN INCREASE IN THE TOTAL NUMBER OF
 ENTRANCES PLANNED FOR A FACILITY.
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-02-18 Cont ID  
Sent By jwitmer Date 2010-02-18 Time 11:41 Rev Time 0.00
Received By jwitmer Date 2010-02-03 Time 09:46 Sent To  
Notes
2010-02-03 09:47:43TO ZONING BOX

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2010-02-12 Cont ID  
Sent By eschneid Date 2010-02-12 Time 15:37 Rev Time 0.00
Received By eschneid Date 2010-02-12 Time 15:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-02-12 Cont ID  
Sent By eschneid Date 2010-02-12 Time 15:32 Rev Time 0.15
Received By eschneid Date 2010-02-12 Time 15:32 Sent To B
Notes
***NONE***