| 2010-02-25 11:06:34 | ****PROVISOS**** |
| | ****ISSUED AT CONTRACTOR'S RISK**** |
| | ****REVISION REQUIRED PRIOR TO FIRST INSPECTION**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS, |
| | SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING |
| | CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR |
| | BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING |
| | CANNOT BE REDUCED BY MORE THAN 5%. SOME OF THIS |
| | INFORMATION WAS PROVIDED BUT NOT ENOUGH INFORMATION |
| | PROVIDED TO DETERMINE CODE COMPLIANCE. |
| | |
| | 2. PROVIDE PRODUCT APPROVAL FOR THE GARAGE DOOR. |
| | PRODUCT APPROVAL, IF SUBMITTING A FLORIDA STATE PRODUCT |
| | APPROVAL, SHOULD INCLUDE THE COVER SHEET FROM THE DCA |
| | WEBSITE SHOWING THAT THE PRODUCT HAS AN "APPROVED" |
| | STATUS FOR 2007 (WWW.FLORIDABUILDING.ORG) AS WELL AS |
| | THE EVALUATION REPORT/INSTALLATION INSTRUCTIONS |
| | PROVIDED AS A LINK FROM THE INTERNET PAGE. THE |
| | DOCUMENTS SUBMITTED HAVE "FLORIDA PRODUCT APPROVAL |
| | 5675.51" ON THE EVALUATION REPORT BUT THIS IS NOT ONE |
| | OF THE OPTIONS FOR FL 5675. ON THE COVER SHEET, PLEASE |
| | CIRCLE THE DOOR WHICH YOU PROPOSE TO INSTALL. |
| | |
| | 3. REVISE PLAN TO SHOW HOW YOU WILL COMPLY WITH FBC |
| | R703.6.3, BOND BREAK. |