Plan Review Details - Permit 10010548
Plan Review Stops For Permit 10010548
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2010-12-27 Cont ID  
Sent By jwitmer Date 2010-12-27 Time 11:58 Rev Time 0.55
Received By jwitmer Date 2010-12-27 Time 11:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2010-11-18 Cont ID  
Sent By jwitmer Date 2010-11-18 Time 07:57 Rev Time 0.77
Received By jwitmer Date 2010-11-18 Time 07:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-08-17 Cont ID  
Sent By jwitmer Date 2010-08-17 Time 08:24 Rev Time 2.22
Received By jwitmer Date 2010-08-17 Time 08:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-08-16 Cont ID  
Sent By jwitmer Date 2010-08-16 Time 16:04 Rev Time 3.33
Received By jwitmer Date 2010-08-16 Time 16:04 Sent To  
Notes
2010-08-17 07:31:34BUILDING PLAN REVIEW
 PERMIT: 10010548
 ADD: 706 8TH STREET
 CONT: YOUCHAK& YOUCHAK, INC.
 TEL: (561)371-5548
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 COMMENT # 7 THIS BUILDING HAS (3) THREE AREAS WITH FLAT
 ROOFED AREAS. ONE AREA HAS OVER A THREE FOOT HIGH
 PARAPET WHICH ELIMINATES THE CORNER ZONES (ZONE# 3).
 THE OTHER TWO AREAS IN DETAILS 3/A-5 AND A-A/A-7 OR
 DETAIL 1/A6 BOTH WILL REQUIRE ENHANCED FASTENING FOR
 ZONE# 3. THE STRUCTURAL SHEET S-5 FLAT ROOF INDICATES A
 PRESSURE OF -140.2.
  
 ROOFING PRODUCT APPROVAL SUBMITTED FOR FLAT ROOFS:
 FL 2948-R4/ 2004
 JOHN MANVILLE
 MODIFIED BITUMEN ROOF SYSTEM
 PAGE 5 OF 6. LIMITATION 5.6 MECHANICALLY ATTACHED
 INSULATION OR MEMBRANE OR STRIP-BONDED INSULATION
 ALLOWS FOR ENHANCED FASTENING IN ZONES 2 & 3 BY A
 QUALIFIED DESIGN PROFESSIONAL COMMONLY USED METHODS ARE
 RAS 117 AND FM LPDS 1-29.
 APPENDIX 1 PAGE 9OF 26
 SYSTEM NO. S-26 -112.5 (PSF).
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-03-08 Cont ID  
Sent By jwitmer Date 2010-03-08 Time 09:05 Rev Time 6.00
Received By jwitmer Date 2010-03-08 Time 09:05 Sent To  
Notes
2010-03-08 09:52:24BUILDING PLAN REVIEW
 PERMIT: 10010548
 ADD: 706 8TH STREET
 CONT: YOUCHAK& YOUCHAK, INC.
 TEL: (561)371-5548
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 MARCH3/ 2010
  
 1) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 1A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 1B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 1C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 1D) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 1E) DOCUMENTS REQUIRED FOR THRESHOLD BUILDINGS. THREE
 SETS OF ALL DOCUMENTS WILL BE REQUIRED FOR THRESHOLD
 BUILDINGS. 109.3.6 WPB ADMINISTRATIVE CODE.
  
 2) SHEET LS-1:
  
 2A) BUILDING CODE ANALYSIS, THE PLANS INDICATE THE
 FIRST FLOOR IS 7564 SQ. FT. WHERE AS TABLE 503
 ALLOWABLE HEIGHT AND AREA FOR A A3 OCCUPANCY INDICATES
 FOR A BUILDING TYPE VB ONLY 6000SQ FT. PLEASE PROVIDE
 AREA MODIFICATIONS CALCULATIONS AS IN 506.1
 FBC-BUILDING.
  
 2B) OCCUPANT LOAD CALCULATIONS PLEASE SEE SECTION 303.1
 FOR ASSEMBLY OCCUPANCY TYPES A3
 READING ROOMS, LOBBIES AND KITCHEN. PLEASE REVIEW TABLE
 508.3.3PLEASE REVIEW FOOTNOTE E IN REGARDS TO
 SEPARATION.
  
 2C) OCCUPANT LOAD CALCULATIONS, SQUARE FOOT AREA PER
 OCCUPANT SHALL BE TAKEN FROM TABLE 1004.1.1. THIS WILL
 GREATLY CHANGE THE OCCUPANT LOADS LISTED IN THIS
 REVIEW. IN AREAS AS THE MULTIPURPOSE COMMUNITY ROOM WE
 HAVE TO LOOK AT THE WORST CASE SCENARIO OR 5 SQ FT PER
 PERSON.
 THE OTHER AREA OF CONCERN IS THE 2ND FLOOR MEETING
 ROOMS A& B.
  
 1004.1.1 AREAS WITHOUT FIXED SEATING. THE NUMBER OF
 OCCUPANTS SHALL BE COMPUTED AT THE RATE OF ONE OCCUPANT
 PER UNIT OF AREA AS PRESCRIBED IN TABLE 1004.1.1. FOR
 AREAS WITHOUT FIXED SEATING, THE OCCUPANT LOAD SHALL
 NOT BE LESS THAN THAT NUMBER DETERMINED BY DIVIDING THE
 FLOOR AREA UNDER CONSIDERATION BY THE OCCUPANT PER UNIT
 OF AREA FACTOR ASSIGNED TO THE OCCUPANCY AS SET FORTH
 IN TABLE 1004.1.1. WHERE AN INTENDED USE IS NOT LISTED
 IN TABLE 1004.1.1, THE BUILDING OFFICIAL SHALL
 ESTABLISH A USE BASED ON A LISTED USE THAT MOST NEARLY
 RESEMBLES THE INTENDED USE.
  
 2D) THE PLANS DO NOT INDICATE IF THIS MIXED USE
 OCCUPANCY BUILDING IS TRYING TO CLAIM OCCUPANCY
 SEPARATION PER 508.3.1.3 OR NON-SEPARATED OCCUPANCIES
 PER SECTION 508.3.2. PLEASE IDENTIFY, BEWARE SEPARATION
 OF NON-SEPARATED OCCUPANCIES WE STILL NEED TO REVIEW TO
 CORRIDOR FIRE RESISTANCE RATING PER TABLE 1017.1.
 PLEASE REVIEW FOR
 ASSEMBLY OCCUPANCY WITH OCCUPANT LOAD GREATER THAN 30,
 FIRE SPRINKLERED WILL STILL REQUIRE A 1 HR RATED
 CORRIDOR, INCLUDING CEILING IF WALLS ARE NOT RATED TO
 THE DECK ABOVE. NOTE WHEN TRAVELING THROUGH ADJOINING
 ROOMS THIS WOULD BE CONSIDERED PART OF A CORRIDOR,
 EDUCATIONAL ROOMS, CORRIDOR 117 THE READING ROOM, TO
 THE LOBBY AS WELL AS THE ELEVATOR LOBBY. PLEASE ALSO
 REVIEW SECTION 715 OPENING PROTECTIVE???S AND TABLE
 715.3.
  
 2E) ANOTHER ISSUE WITH THE ONE HOUR RATING OF THE
 CORRIDOR LEADING FROM THE ASSEMBLY AREA THE
 MULTIPURPOSE COMMUNITY ROOM WOULD BE THE ELEVATOR
 MACHINE ROOM LOCATED WITHIN THIS RATED CORRIDOR. 3006.1
 ACCESS. AN APPROVED MEANS OF ACCESS SHALL BE PROVIDED
 TO ELEVATOR MACHINE ROOMS AND OVERHEAD MACHINERY
 SPACES.
 3006.4 MACHINE ROOMS AND MACHINERY SPACES. ELEVATOR
 MACHINE ROOMS AND MACHINERY SPACES SHALL BE ENCLOSED
 WITH FIRE BARRIERS COMPLYING WITH SECTION 706 OR
 HORIZONTAL ASSEMBLIES COMPLYING WITH SECTION 711 HAVING
 A FIRE-RESISTANCE RATING NOT LESS THAN THE REQUIRED
 RATING OF THE HOISTWAY ENCLOSURE SERVED BY THE
 MACHINERY. OPENINGS SHALL BE PROTECTED WITH ASSEMBLIES
 HAVING A FIRE-PROTECTION RATING NOT LESS THAN THAT
 REQUIRED FOR THE HOISTWAY ENCLOSURE DOORS.
  
 2F) THE ELEVATOR SHAFT DOES NOT PROVIDE A FIRE RATING
 AS PER SHAFTS SECTION 707.4 FBC-BUILDING NOR RATING OF
 HOISTWAY ENCLOSURE DOORS.
  
 2G) CLOSET ROOM 101A PLEASE PROVIDE A 1HR DETAIL FOR
 SEPARATION FROM STAIRS LOCATED ABOVE, SHEET A-8 DETAIL#
 1 INDICATES A PRE-ENGINEERED STEEL STAIR WITH CONCRETE
 FILLED PAN. SEE SECTION 1009.5.3.
  
 2H) SECOND FLOOR READING ROOMS A & B, WITHOUT TABLES
 AND CHAIRS INDICATED IN THESE ROOMS THE OCCUPANT LOAD
 FIGURED AT 7 SQ FT PER PERSON THE OCCUPANT LOAD IS 50.
 THIS
 WILL REQUIRE THE DOORS TO SWING IN THE DIRECTION OF
 TRAVEL PER SECTION 1008.1.2.
  
 2I) SECOND FLOOR READING ROOM B WILL ALSO NEED TWO
 MEANS OF EGRESS TABLE 1015.1.
  
 2J) STAIR# 2 INDICATES A 3??? VERTICAL STORM DRAIN
 WITHIN THE STAIRWELL, PLEASE REVIEW 1023.6 EXTERIOR
 RAMPS AND STAIRWAY PROTECTION. EXTERIOR EXIT RAMPS AND
 STAIRWAYS SHALL BE SEPARATED FROM THE INTERIOR OF THE
 BUILDING AS REQUIRED IN SECTION 1020.1. OPENINGS SHALL
 BE LIMITED TO THOSE NECESSARY FOR EGRESS FROM NORMALLY
 OCCUPIED SPACES.
  
 3) SHEET LA-1 PLEASE PROVIDE COMPLIANCE WITH :
 11-4.1.3 ACCESSIBLE BUILDINGS: NEW CONSTRUCTION.
 8) IN NEW CONSTRUCTION, AT A MINIMUM, THE REQUIREMENTS
 IN SECTION 11-4.1.3(8)(A) AND SECTION 11-4.1.3(8)(B)
 BELOW SHALL BE SATISFIED INDEPENDENTLY:
  
 (A)(I) AT LEAST 50 PERCENT OF ALL PUBLIC ENTRANCES
 [EXCLUDING THOSE IN SECTION 11-4.1.3(8)(B) BELOW] MUST
 BE ACCESSIBLE. AT LEAST ONE MUST BE A GROUND-FLOOR
 ENTRANCE. PUBLIC ENTRANCES ARE ANY ENTRANCES THAT ARE
 NOT LOADING OR SERVICE ENTRANCES.
  
 (II) ACCESSIBLE ENTRANCES MUST BE PROVIDED IN A NUMBER
 AT LEAST EQUIVALENT TO THE NUMBER OF EXITS REQUIRED BY
 THE APPLICABLE BUILDING/FIRE CODES. (THIS PARAGRAPH
 DOES NOT REQUIRE AN INCREASE IN THE TOTAL NUMBER OF
 ENTRANCES PLANNED FOR A FACILITY.)
  
 4) SHEET A1 DOORS 103A, 112 & 112A NEED TO COMPLY WITH:
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL
 BE AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 5) STRUCTURAL SHEET S7 DETAIL 8 & 9 INDICATE A METAL
 DECK ROOFING WITH 5/8??? CDX PLYWOOD SHEATHING, THE
 SCHEDULE SHEET S5 DOES NOT PROVIDE TYPE OF FASTENERS,
 LENGTH NOR QUANTITY FOR ROOF ZONES 1, 2 & 3.
  
 6)SHEET A-5 DETAILS 2 & 3 INDICATE THE USE OF 5/8???
 PLYWOOD OVER STEEL DECK WITH USE OF BAR-JOIST AT
 4???-0??? O. C. THE ROOFING REPORT FOR METAL ROOFING ,
 PRODUCT NAME ???ZEE-LOCK??? HAS A OPTIONAL RIGID
 INSULATION. UNDER THE LISTING OF SYSTEMS LIMITATION THE
 REPORT STATES ??? RATIONAL ANALYSIS FOR THIS PRODUCT
 OUTSIDE OF USE AS DESCRIBED IN THIS REPORT SHALL BE
 PREPARED BY A QUALIFIED DESIGN PROFESSIONAL AND IN
 COMPLIANCE WITH FBC 2007. WILL THE FASTENERS FOR THE
 METAL ROOF ONLY PENETRATE THE 5/8??? CDX PLY WOOD OR
 WILL THEY ALSO NEED TO PENETRATE THE METAL ROOF
 DECKING.
  
 7) SHEET A3 DOES INDICATE THE USE IN TWO AREAS OF FLAT
 ROOF CONSTRUCTION, CONCRETE DECK WITH BUILT-UP ROOF ON
 TAPERED INSULATION. PLEASE PROVIDE INSULATION
 CALCULATIONS FOR ROOF ZONES. THE PRODUCT APPROVAL FOR
 FLAT ROOF AND TAPERED INSULATION INDICATES THE USE OF
 SYSTEM # S-26, APPENDIX 1, PAGE 9 OF 26. ENHANCED
 FASTENING WILL BE
 REQUIRED FOR ROOF ZONE# 3. PRODUCT APPROVAL GOOD FOR
 -112.5 WHERE AS PLANS INDICATE ROOF ZONE 3 A -130.9. A
 SHOP DRAWING WILL BE REQUIRED INDICATING THE TAPERED
 INSULATION AND MINIMUM R-VALUE LOCATED AT ROOF DRAIN,
 THIS VALUE SHALL ALSO MATCH THE ENERGY CALCULATIONS.
  
 8) S-7 DETAILS 12 & 13 THE SIZE AND SPACING OF THE
 BOTTOM STEEL IS NOT PROVIDED.
  
  
 9) STRUCTURAL SHEET S7, S8 & S9 ALL INDICATE A BRICK
 VENEER ATTACHMENT METHODS, WALL ANGLES FOR SUPPORT
 LEDGES BUT THE PLANS DO NOT INDICATE WHERE THE BRICK
 VENEER WILL STOP, AT GRADE, BELOW GRADE, THIS IS STEM
 WALL CONSTRUCTION?
 2114.2 CONCRETE BEARING LEDGE. BRICK, STONE OR OTHER
 VENEER SHALL BE SUPPORTED BY A CONCRETE-BEARING LEDGE
 AT LEAST EQUAL TO THE TOTAL THICKNESS OF THE BRICK,
 STONE OR OTHER VENEER, WHICH IS POURED INTEGRALLY WITH
 THE CONCRETE FOUNDATION. NO SUPPLEMENTAL CONCRETE
 FOUNDATION POURS WHICH WILL CREATE A HIDDEN COLD JOINT
 SHALL BE USED WITHOUT SUPPLEMENTAL TREATMENT IN THE
 FOUNDATION UNLESS THERE IS AN APPROVED PHYSICAL
 BARRIER. AN APPROVED PHYSICAL BARRIER SHALL ALSO BE
 INSTALLED FROM BELOW THE WALL SILL PLATE OR FIRST BLOCK
 COURSE HORIZONTALLY TO EMBED IN A MORTAR JOINT. IF
 MASONRY VENEER EXTENDS BELOW GRADE, A TERMITE
 PROTECTIVE TREATMENT MUST BE APPLIED TO THE CAVITY
 CREATED BETWEEN THE VENEER AND THE FOUNDATION, IN LIEU
 OF A PHYSICAL BARRIER.
  
 10) A8 DETAILS 1A-1B BOTH INDICATE A ELEVATOR SHAFT,
 A-3 INDICATES A ELEVATOR SHAFT BELOW THE ROOF LINE, S1
 & S2 BOTH INDICATE A OPEN SHAFT, PLEASE REVIEW:
 3002.1.1 OPENING PROTECTIVE???S. OPENINGS IN HOIST WAY
 ENCLOSURES SHALL BE PROTECTED AS REQUIRED IN CHAPTER 7.
 707.2 SHAFT ENCLOSURE REQUIRED. OPENINGS THROUGH A
 FLOOR/CEILING ASSEMBLY SHALL BE PROTECTED BY A SHAFT
 ENCLOSURE COMPLYING WITH THIS SECTION.
 707.4 FIRE-RESISTANCE RATING. SHAFT ENCLOSURES SHALL
 HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS
 WHERE CONNECTING FOUR STORIES OR MORE, AND NOT LESS
 THAN 1 HOUR WHERE CONNECTING LESS THAN FOUR STORIES.
 THE NUMBER OF STORIES CONNECTED BY THE SHAFT ENCLOSURE
 SHALL INCLUDE ANY BASEMENTS BUT NOT ANY MEZZANINES.
 SHAFT ENCLOSURES SHALL HAVE A FIRE-RESISTANCE RATING
 NOT LESS THAN THE FLOOR ASSEMBLY PENETRATED, BUT NEED
 NOT EXCEED 2 HOURS.
  
 707.5 CONTINUITY. SHAFT ENCLOSURES SHALL BE CONSTRUCTED
 AS FIRE BARRIERS IN ACCORDANCE WITH SECTION 706 OR
 HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH, AND SHALL HAVE CONTINUITY IN
 ACCORDANCE WITH SECTION 706.5 FOR FIRE BARRIERS OR
 SECTION 711.4 FOR HORIZONTAL ASSEMBLIES AS APPLICABLE.
  
  
 11) SHEET A-4 THE EAST ELEVATION INDICATES THE USE OF
 SIMULATED 6 INCH HORIZONTAL LAP
 SIDING STUCCO FINISH. PLEASE PROVIDE PRODUCT APPROVAL
 FOR SIDING. COMPONENTS AND CLADDING. FL BLD CODE
 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 3
 SETS OF PRODUCT APPROVALS FOR THESHOLD BUILDINGS.
 NOTE ONLY TWO REPORTS WERE SUPPLIED FOR THE OTHER
 APPROVALS SUBMITTED!
  
 12) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2014-01-02 Cont ID  
Sent By dharvey Date 2014-01-02 Time 09:20 Rev Time 0.00
Received By dharvey Date 2014-01-02 Time 09:18 Sent To  
Notes
2014-01-02 09:20:27ALL WORK IS TO COMPLY WITH THE GOVERNING CODES. PLANS
 INDICATE THE 2007 FBC IS THE APPLICABLE CODE, MAKING
 THE 2005 NEC THE APPLICABLE ELECTRICAL CODE. WIRING
 METHODS ARE TO BE APPROPRIATE TO THE TYPE OF
 CONSTRUCTION REGARDING COMBUSTIBILITY AND FLAMMIBILITY
 AND COVER REQUIREMENTS. PROJECT IS APPROVED AS NOTED.

Review Stop E ELECTRICAL
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2010-12-28 Time   Rev Time 0.00
Received By rlecky Date 2010-12-28 Time 13:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-08-09 Cont ID  
Sent By lmartine Date 2010-08-09 Time 16:13 Rev Time 0.00
Received By lmartine Date 2010-08-09 Time 16:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-09 Cont ID  
Sent By dpalmer Date 2010-02-09 Time 15:56 Rev Time 0.00
Received By dpalmer Date 2010-02-09 Time 15:56 Sent To  
Notes
2010-02-09 15:56:34*DENIED*
  
 ** ORIGINALLY REVIEWED UNDER EXPIRED PERMIT APPLICATION
 08050795
  
  
 1) NOTE: THE PROJECT HAS BEEN SUBMITTED FOR PERMIT
 AFTER OCTOBER 1ST, 2009 AND MARCH 1ST, 2009 WHICH
 PLACES DESIGN REQUIREMENTS UNDER THE 2007 FBC W/2009
 SUPPLEMENTS AS WELL AS THE 2008 NFPA-70.
  
 2) NOTE: THE SUBMITTED FLORIDA ENERGY CALCULATIONS ARE
 NOT FROM THE CURRENT CODE CYCLE. IN FACT THEY ARE FROM
 THE 2004 FLA/COM 2.5.
 THEY ARE SUBSTANTIALLY DIFFERENT FROM NEWER CODE CYCLE
 REQUIREMENTS.
 PLEASE SEE 13-415.AB.5 FOR INTERIOR LIGHTING AND
 13-415.AB.2.2 FOR EXTERIOR LIGHTING.
 PLEASE KNOW THAT ALL ITEMS ON THE PLANS FOR THE
 CONSTRUCTION, TYPE, BUILDING CHARACTERISTICS ARE
 REQUIRED TO BE IN THE INPUT DATA REPORT OF THE
 SUBMITTED CALCULATIONS.
 THERE ARE ITEMS EVEN ON THE IDR OF THE 2004 WHICH ARE
 NOT CORRELATING WITH THE PLANS. ONE EXAMPLE IS ALL THE
 FLOOR AREAS IN THE BUILDING ARE USING CREDIT FOR CARPET
 AND RUBBER PADDING HOWEVER THIS IS NOT POSSIBLE. AREAS
 SUCH AS BATHROOMS, ELECTRICAL ROOMS/AREAS, MECHANICAL
 ROOMS AND KITCHEN ARE NOT GOING TO HAVE CARPET AND
 RUBBER PADDING NOR ARE THEY PERMITTED TO HAVE CARPET
 INSTALLED.
 THERE ARE OTHER ITEMS HOWEVER AS THE VERSION IS
 COMPLETELY DIFFERENT WE ARE NOT ABLE TO REVIEW FOR
 CURRENT CODE.
 ** PLEASE BE SURE TO GO THROUGH ALL SYSTEMS AND
 COMPONENTS. THIS WAS SPECIFICALLY MENTIONED ON THE
 ORIGINAL REVIEW. THIS OFFICE ONCE AGAIN EMPHASIZES THE
 IMPORTANCE OF ALL SYSTEMS ON PLANS TO COORDINATE WITH
 THE INPUT DATA REPORT OF THE SUBMITTED ENERGY
 CALCULATIONS. IF THERE ARE QUESTIONS, PLEASE CALL.
  
 ** THIS INCLUDES THE POWER DENSITIES ON PLANS.
 ** PLEASE BE SURE TO SEE APPENDIX B FOR TRACK LIGHTING
 AND OTHER LIGHTING FOR CALCULATIONS.
  
 3) NOTE: PLEASE SEE CODE REFERENCES ON PLANS SUCH AS
 THE 13-413 NOTES ON E001. THE SECTIONS NOTED ARE FROM
 THE ORIGINAL PRINTING OF THE 2007 FBC HOWEVER THAT
 VERSION AND PRINTING WAS NEVER ADOPTED. THE FIRST
 ADOPTED VERSION WAS THE 2007 WITH THE FIRST SET OF 2009
 SUPPLEMENTS. THIS INCLUDED A COMPLETE RE-WRITE OF FBC
 CHAPTER 13. PRESCRIPTIVE C METHODS ARE NOT IN ANY OF
 THE ADOPTED CODES.
 PLEASE VISIT THE FOLLOWING WEBSITE TO LOOK AT THE
 ADOPTED CODES, ADJUST TEXT, AND ADJUSTED CODES WHICH
 WERE SUBSTANTIALLY CHANGED AND REVISED.
  
 4) NOTE: SAME COMMENT AS PREVIOUS REVIEW WITH RESPECT
 TO RUBBER STAMPED SIGNATURE ON COMPASS SURVEYING
 SHEETS. PLEASE SEE FS 472.025.
  
 5) NOTE: PLEASE EXPLAIN RESPONSE TO PREVIOUS NOTE #10.
 THE RESPONSE STATES THE TRACK LIGHTING IS EXEMPT.
 PLEASE EXPLAIN WHERE THERE IS AN EXEMPTION IN THE
 PREVIOUS CODE OR THIS APPLICABLE CODE.
 THIS OCCUPANCY AND USE DOES NOT APPLY TO EXEMPTIONS.
 THIS IS IMPORTANT AS THE TRACK LIGHTING AS MENTIONED IN
 NOTE #2 ABOVE TRACK LIGHTING IN APPENDIX B FOR IDR IS
 MENTIONED.
  
  
 6) NOTE: LIGHTING CONTROLS FOR BATHROOMS DO NOT MEET
 13-415.AB.1.1,.1.2.
 AUTOMATED CONTROL REQUIRED ALONG WITH OVER RIDE. THE
 USE OF OCCUPANCY SENSORS TYPE DEVICES ARE PERMITTED
 HOWEVER THEY WOULD BE REQUIRED TO BE FAIL SAFE ON. THE
 RESPONSE MENTIONS ALONG WITH PLANS SHOWING A KEYED
 SWITCH TO BE LOCATED ABOVE THE CEILING. THIS IS NOT
 WHAT WAS MEANT BY THE PREVIOUS COMMENTS AND DOES NOT
 MEET FBC. PLEASE ADJUST PLANS.
 FBC 1006.1.2, NFPA-101 7.2.1.2.2
  
 7) NOTE: PLEASE SEE 13-415.AB.1.1,.1.2 FOR AREAS WHERE
 THE PLANS ONLY INDICATE SINGLE POLE SWITCHES FOR THE
 LIGHTING CONTROLS. THESE ARE SEPARATE SPACES LOCATED IN
 A BUILDING GREATER THAN 5K SQ FT.
 101A, 117A.
  
 8) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR NEW PROPOSED MTS. THE RESPONSE MENTIONS TO SEE
 ATTACHED HOWEVER NO SPECS COULD BE LOCATED IN PACKAGE.
  
 9) NOTE: AS NOTED ON PREVIOUS REVIEW AS KITCHEN
 EQUIPMENT AND ELECTRICAL SYSTEMS IS NOT YET COMPLETE,
 SEVERAL ITEMS TO BE REVIEWED FOR CODE COMPLIANCE CAN
 NOT BE DONE AT THIS TIME.
 ** THIS MAY AFFECT FUTURE EQUIPMENT/SERVICE.
  
 10) NOTE: ALTHOUGH NOT UNDER THE TECHNICAL REVIEW OF
 THIS OFFICE. THE STATE ELEVATOR CODE REQUIREMENTS HAVE
 CHANGED.
 PLEASE SEE CURRENT ADOPTED ASME A-17.
 PIT LEVELS 10FT CANDLES
 MECHANICAL AREAS/ROOMS, 19FTCANDLES
 SILL AREA IN LOBBY/LANDING AREA 10FT CANDLES.
  
 THIS INFORMATION IS GIVEN AS A BENEFIT SO AS NOT TO
 DELAY THE PROJECT AT THE FINAL INSPECTIONS.
  
 11) NOTE: THE CIRCUITING FOR THE ELEVATOR EQUIPMENT
 ROOM FOR LIGHTS AND RECEPTACLES IS NOT LOCATED ON
 PLANS. 620.23 REQUIRED TO BE DEDICATED.
 PLEASE EXPLAIN THE SYMBOL ON THE PLANS FOR THE SAME
 ROOM LOCATION SHOWN ON E301. BY THE SYMBOL IT LOOKS TO
 BE A TRANSFORMER OR PERHAPS EVEN A ROOF-HATCH.
  
 12) NOTE: AS NOTED ON PREVIOUS NOTE #32, THE SITE
 CONDUITS FOR THE ELECTRICAL SERVICE ON SHEET ES101 ARE
 STILL SHOWN GOING FROM FPL TRANSFORMER TO THE MAIN
 ELECTRICAL ROOM.
 THE RISER AND PLANS INDICATE A MAIN OUTSIDE, A MTS
 OUTSIDE ETC.
 HOW IS IT THESE CONDUITS ARE NOT SHOWN TO THE OUTSIDE
 SERVICE AND LOW VOLTAGE SERVICE LOCATIONS?
  
 13) NOTE: INTER-SYSTEM GROUNDING IS REQUIRED AT MAIN
 SERVICE PER 250.94 OF THE REVISED 2008 NEC.
  
 14) NOTE: ALL OUTSIDE RECEPTACLES SHALL BE WR TYPE PER
 REVISED 2008 NEC 406.8A.
  
 16) NOTE: PREVIOUS NOTE #38. THE TRANSFORMER ON ES 101
 SITE PLANS IS STILL SHOWN AS 100KVA, YET CALCULATIONS
 FOR AIC RATING STILL INDICATE A 225 KVA UNIT.
 PLEASE CORRELATE PLANS. IT IS UNCLEAR WHAT THE RESPONSE
 LETTER IS RESPONDING TO.
  
 17) NOTE: PREVIOUS NOTE #40. THE RISER STILL INDICATES
 A 125AMP BREAKER FEEDING A 100AMP RATED DISCONNECT.
 RESPONSE MENTIONS THE OVER CURRENT PROTECTION AND
 SIZING FOR ELEVATOR MOTOR. THAT IS NOT THE COMMENT
 PREVIOUSLY MADE. THIS REVIEWER UNDERSTANDS THE OVER
 CURRENT PROTECTION AS LISTED IN THE CODE AND AS
 RESPONDED TO HOWEVER THE COMMENT WAS BASED ON THE FACT
 THE RATING OF THE DISCONNECT NEEDS TO COORDINATE WITH
 THE BREAKER OCP.
  
 18) NOTE: PREVIOUS NOTE #29. SYSTEM IS REQUIRED TO BE
 DEDICATED FOR ELEVATOR EQUIPMENT ROOM. SHARING THE VRV
 AS RESPONDED WITH THE ANY OTHER AREAS ETC IS NOT
 PERMITTED. PLEASE SEE FBC 3006.2 AS THIS REQUIRES AND
 *INDEPENDENT* SYSTEM.
 IT HAS ALSO BEEN CONFIRMED ON NUMEROUS PREVIOUS
 PROJECTS WITH THE STATE ELEVATOR INSPECTOR.
  
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2010-10-13 Cont ID  
Sent By mgonzale Date 2010-10-13 Time 09:17 Rev Time 1.00
Received By mgonzale Date 2010-10-13 Time 09:17 Sent To  
Notes
2010-10-13 09:20:45PASSED:
  
 CIVIL PLANS HAVE BEEN APPROVED THRU ENGINEERING
 SERVICES.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2010-03-24 Cont ID  
Sent By efabian Date 2010-03-24 Time 15:47 Rev Time 0.00
Received By efabian Date 2010-03-24 Time 15:46 Sent To  
Notes
2010-03-24 16:42:13LAST (CIVIL SET OF) PRELIMINARY PLANS REVIEWED WERE
 OVER ONE YEAR AGO AND SUBSEQUENTLY SENT TO RECORDS
 RETENTION DUE TO INACTIVE STATUS. THESE PLANS ARE TO BE
 RETRIEVED FROM STORAGE IN ORDER TO BE COMPARED TO THE
 CURRENT SET FOR CONSISTENCY AND REQUIRE FURTHER
 DISCUSSION, FOR EXAMPLE: 1. A 3RD DUMPSTER ENCLOSURE
 FACES THE ALLEY WITH 2 CURBS, WHICH EXTEND INTO THE
 ALLEY RIGHT-OF-WAY BEYOND PRIVATE PROPERTY. 2. IT IS
 NOT CLEAR IF THE ALLEY WAS EVER PETITIONED OR APPROVED
 AS A ONE-WAY TRAFFIC LANE. 3. RIM ELEVATION OF THE
 SANITARY MANHOLE WHICH WILL CONNECT TO THE BUILDING IS
 NOT KNOWN OR SHOWN.
  
 IN ADDITION, AN ENGINEERING SERVICES APPLICATION FOR
 SITE DEVELOPMENT, AND ALL OTHER PERTINENT DOCUMENTATION
 INCLUDING A CERTIFIED CONSTRUCTION COST ESTIMATE FORM;
 FDEP NOTICE OF INTENT (NOI) FORM 62-621.20; STORM WATER
 QUALITY AND CACLCULATIONS, GEOTECHNICAL REPORT; LAND
 STABILIZATION - EROSION CONTROL BOND MUST BE SUBMITTED.
 THESE AND PLAN REVIEW/CONSTRUCTION ADMINISTRARION FEES
 MUST ALL BE RECONCILED WITH ENGINEERING SERVICES -
 PRIOR TO APPROVAL FROM THIS DEPARTMENT AND PRIOR TO
 COMMENCEMENT OF ANY SITE WORK.
  
 WHEN CONTACTING THE REVIEWER PLEASE REFERENCE THE
 PERMIT NUMBER.
 IF YOU HAVE ANY QUESTIONS PLEASE FEEL FREE TO CONTACT
 THE REVIEWER:
  
 EMERY P. FABIAN, PROJECT COORDINATOR
 CITY OF WEST PALM BEACH
  ENGINEERING SERVICES DEPARTMENT
  401 CLEMATIS STREET, 4TH FLOOR
  WEST PALM BEACH FL 33401
 (561)-494-1078 OFFICE
  
  EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2010-12-27 Cont ID  
Sent By wjolin Date 2010-12-27 Time 15:10 Rev Time 0.00
Received By wjolin Date 2010-12-27 Time 14:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2010-11-08 Cont ID  
Sent By wjolin Date 2010-11-08 Time 16:25 Rev Time 0.00
Received By wjolin Date 2010-11-08 Time 14:29 Sent To  
Notes
2010-11-08 16:25:42720 8TH STREET
 PERMIT #10010548
  
 REVIEW COMMENTS - FIRE
  
 1) SHEET C-3: WHY ARE THERE SO MANY VALVES BETWEEN THE
 TAPPING VALVE/SLEEVE AND THE INCOMING SERVICE RISER
 (GATE, BACKFLOW, PIV)? ABOVE GROUND CONTROL VALVES NEED
 TO BE SUPERVISED. PROVIDE CHECK VALVE FOR FIRE
 DEPARTMENT CONNECTION.
 11/8/10 - REVIEW COMMENT HAS BEEN SATISFIED. WJ
  
 2) SHEET LA-1: PER FFPC NFPA 1, SECTION 18.3.3.1 &
 18.3.4.2 NO GROWTH, VEGETATION ETC. IS ALLOWED WITHIN
 7'-6" (FRONT AND SIDES) OF FIRE PROTECTION DEVICES
 (FIRE DEPARTMENT CONNECTION). THE FIRE DEPARTMENT
 CONNECTION SHALL BE VISIBLE AT ALL TIMES.
 11/8/10 - REPEAT COMMENT. WJ
  
 3) SHEET LS1: ELEVATOR EQUIPMENT DOOR NOT PERMITTED TO
 OPEN INTO STAIR ENCLOSURE PER FFPC NFPA 101, SECTION
 7.1.3.2.1 (5).
 11/8/10 - REPEAT COMMENT. WJ
  
 4) SHEET LS1: ELEVATORS ARE NOT PERMITTED TO OPEN INTO
 A STAIR EXIT PER FFPC NFPA 101, SECTION 9.4.7.
 11/8/10 - REPEAT COMMENT. WJ
  
 5) SHEET LS1: AN EXIT ENCLOSURE SHALL NOT BE USED FOR
 ANY PURPOSE (LOBBY/RECEPTION) THAT HAS THE POTENTIAL TO
 INTERFERE WITH USE AS AN EXIT PER FFPC NFPA 101,
 SECTION 7.1.3.2.3.
 11/8/10 - REPEAT COMMENT. WJ
  
 6) SHEET LS1: ACCESS TO THE ENCLOSED USABLE SPACE BELOW
 THE STAIR SHALL NOT BE FROM WITHIN THE STAIR ENCLOSURE
 PER FFPC NFPA 101, SECTION 7.2.2.5.3.2.
 11/8/10 - REPEAT COMMENT. WJ
  
 7) SHEET LS1: PROVIDE ASSEMBLY OCCUPANT LOAD BASED UPON
 15 SQ.FT. NET PER PERSON FOR NON-FIXED SEATING IN
 ACCORDANCE WITH TABLE 7.3.1.2 OF FFPC NFPA 101 AND
 SECTION 12.7.9.2.2. DEDUCT TABLE AREAS AND EGRESS PATHS
 FROM AVAILABLE SQUARE FOOTAGE. MAINTAIN ADEQUATE AISLES
 TO REACH ALL EXITS SERVING THE ASSEMBLY SPACE.
 11/8/10 - REPEAT COMMENT. WJ
  
 8) SHEET EF101: WHY WAS THE VISIBLE NOTIFICATION
 APPLIANCE REMOVED FROM READING ROOM #103. THIS DEVICE
 IS REQUIRED.
 11/8/10 - REPEAT COMMENT. WJ
  
 9) SHEET EF101: PROVIDE TAMPER SWITCHES FOR CONTROL
 VALVES SHOWN ON CIVIL PLANS.
 11/8/10 - REPEAT COMMENT. WJ
  
 10) SHEET E401: PROVIDE NOTE AS TO HOW ELEVATOR POWER
 WILL BE SHUNTED IF SPRINKLER AT TOP OF SHAFT IS
 ACTIVATED.
 11/8/10 - REPEAT COMMENT. WJ
  
 11) SHEET EK103: PROVIDE AUDIBLE/VISIBLE NOTIFICATION
 OF HOOD SUPPRESSION SYSTEM ACTIVATION. TIE INTO FIRE
 ALARM SYSTEM.
 11/8/10 - REPEAT COMMENT. WJ
  
 12) SHEET FP101: PROVIDE AVAILABLE WATER SUPPLY DATA.
 11/8/10 - REPEAT COMMENT. WJ
  
 13) SHEET FP101: SHOP DRAWINGS CANNOT REQUIRE
 ENGINEER'S SIGN/SEAL PER FAC 61G15-32.002.
 11/8/10 - REPEAT COMMENT. WJ
  
 14) SHEET FP101: PROVIDE TAMPER SWITCH ON FLOOR CONTROL
 VALVES.
 11/8/10 - REVIEW COMMENT HAS BEEN SATISFIED. WJ
  
 15) SHEET FP101: PROVIDE CLOSELY SPACED SPRINKERS AND
 DRAFT STOPS AROUND CEILING OPENING ADJACENT TO STAIR #1
 PER NFPA 13, SECTION 8.14.4.1.
 11/8/10 - REVIEW COMMENT HAS BEEN SATISFIED ON FIRE
 PROTECTION DRAWINGS. ARCHITECTURAL PLANS TO SHOW
 18-INCH DEEP DRAFT STOPS. WJ
  
 16) SHEET FP701: CIVIL PLANS SHOW 6" BACKFLOW
 PREVENTER, A GATE VALVE AND A POST INDICATOR VALVE.
 COORDINATE VALVE QUANTITY AND SIZING BETWEEN
 ENGINEERING DISCIPLINES.
 11/8/10 - REPEAT COMMENT. WJ
  
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 561-805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2010-08-18 Cont ID  
Sent By wjolin Date 2010-08-18 Time 15:50 Rev Time 0.00
Received By wjolin Date 2010-08-17 Time 11:25 Sent To  
Notes
2010-08-18 15:50:15*****REVIEW COMMENTS - FIRE*****
  
 1) SHEET C-3: WHY ARE THERE SO MANY VALVES BETWEEN THE
 TAPPING VALVE/SLEEVE AND THE INCOMING SERVICE RISER
 (GATE, BACKFLOW, PIV)? ABOVE GROUND CONTROL VALVES NEED
 TO BE SUPERVISED. PROVIDE CHECK VALVE FOR FIRE
 DEPARTMENT CONNECTION.
  
 2) SHEET LA-1: PER FFPC NFPA 1, SECTION 18.3.3.1 &
 18.3.4.2 NO GROWTH, VEGETATION ETC. IS ALLOWED WITHIN
 7'-6" OF FIRE PROTECTION DEVICES (FIRE DEPARTMENT
 CONNECTION). THE FIRE DEPARTMENT CONNECTION SHALL BE
 VISIBLE AT ALL TIMES.
  
 3) SHEET LS1: ELEVATOR EQUIPMENT DOOR NOT PERMITTED TO
 OPEN INTO STAIR ENCLOSURE PER FFPC NFPA 101, SECTION
 7.1.3.2.1 (5).
  
 4) SHEET LS1: ELEVATORS ARE NOT PERMITTED TO OPEN INTO
 A STAIR EXIT PER FFPC NFPA 101, SECTION 9.4.7.
  
 5) SHEET LS1: AN EXIT ENCLOSURE SHALL NOT BE USED FOR
 ANY PURPOSE (LOBBY/RECEPTION) THAT HAS THE POTENTIAL TO
 INTERFERE WITH USE AS AN EXIT PER FFPC NFPA 101,
 SECTION 7.1.3.2.3.
  
 6) SHEET LS1: ACCESS TO THE ENCLOSED USABLE SPACE BELOW
 THE STAIR SHALL NOT BE FROM WITHIN THE STAIR ENCLOSURE
 PER FFPC NFPA 101, SECTION 7.2.2.5.3.2.
  
 7) SHEET LS1: PROVIDE ASSEMBLY OCCUPANT LOAD BASED UPON
 15 SQ.FT. NET PER PERSON FOR NON-FIXED SEATING IN
 ACCORDANCE WITH TABLE 7.3.1.2 OF FFPC NFPA 101 AND
 SECTION 12.7.9.2.2. DEDUCT TABLE AREAS AND EGRESS PATHS
 FROM AVAILABLE SQUARE FOOTAGE. MAINTAIN ADEQUATE AISLES
 TO REACH ALL EXITS SERVING THE ASSEMBLY SPACE.
  
 8) SHEET EF101: WHY WAS THE VISIBLE NOTIFICATION
 APPLIANCE REMOVED FROM READING ROOM #103. THIS DEVICE
 IS REQUIRED.
  
 9) SHEET EF101: PROVIDE TAMPER SWITCHES FOR CONTROL
 VALVES SHOWN ON CIVIL PLANS.
  
 10) SHEET E401: PROVIDE NOTE AS TO HOW ELEVATOR POWER
 WILL BE SHUNTED IF SPRINKLER AT TOP OF SHAFT IS
 ACTIVATED.
  
 11) SHEET EK103: PROVIDE AUDIBLE/VISIBLE NOTIFICATION
 OF HOOD SUPPRESSION SYSTEM ACTIVATION. TIE INTO FIRE
 ALARM SYSTEM.
  
 12) SHEET FP101: PROVIDE AVAILABLE WATER SUPPLY DATA.
  
 13) SHEET FP101: SHOP DRAWINGS DO NOT REQUIRE
 ENGINEER'S SIGN/SEAL PER FAC 61G15-32.002.
  
 14) SHEET FP101: PROVIDE TAMPER SWITCH ON FLOOR CONTROL
 VALVES.
  
 15) SHEET FP101: PROVIDE CLOSELY SPACED SPRINKERS AND
 DRAFT STOPS AROUND CEILING OPENING ADJACENT TO STAIR #1
 PER NFPA 13, SECTION 8.14.4.1.
  
 16) SHEET FP701: CIVIL PLANS SHOW 6" BACKFLOW
 PREVENTER, A GATE VALVE AND A POST INDICATOR VALVE.
 COORDINATE VALVE QUANTITY AND SIZING BETWEEN
 ENGINEERING DISCIPLINES.
  
  
 MIKE CARSILLO, BATTALION CHIEF/FIRE MARSHAL
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-04-05 Cont ID  
Sent By mcarsill Date 2010-04-05 Time 08:29 Rev Time 0.00
Received By mcarsill Date 2010-04-05 Time 08:25 Sent To  
Notes
2010-04-05 08:29:30 
  
 1. THE FIRE DEPARTMENT CONNECTION (FDC) WILL REQUIRE
 KNOX LOCKING CAPS.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 HOOD,DUCT, AND FIRE SUPPRESSION SYSTEM.
  
 3. A ROOF DRAIN APPEARS IN EXIT # 2.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 ALARM SYSTEM.
  
 5. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 SPRINKLER SYSTEM.
  
 6. THE FIRE DEPARTMENT CONNECTION SHOWN ON PAGE FP101
 DOES NOT MATCH C-3.
  
 7. IT APPEARS THAT NOT ALL PREVIOUS COMMENTS HAVE BEEN
 ADDRESSED.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2010-08-25 Cont ID  
Sent By lwagner Date 2010-08-25 Time 13:32 Rev Time 0.00
Received By lwagner Date 2010-08-25 Time 13:32 Sent To  
Notes
2010-08-25 13:34:14SEPERATE GAS PERMIT REQUIRED

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2010-02-16 Cont ID  
Sent By kstevens Date 2010-02-16 Time 11:16 Rev Time 0.00
Received By kstevens Date 2010-02-16 Time 11:16 Sent To  
Notes
2010-02-16 14:14:27DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 ****FROM PREVIOUS REVEIW, #08050795:
  
 1. SHT KP103 A SEPARATE GAS PERMIT IS REQUIRED. PLEASE
 SUPPLY THE FOLLOWING INFORMATION FOR GAS PERMIT
 APPROVAL:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (CUT SECTIONS FROM THE METER TO THE
 FIRST RISER, AND THE DROP WITH THE VALVES AND UNIONS DO
 NOT INDICATE THE LENGTHS).
 ****RESPONSE NOTED, BUT THE DROP WITH THE VALVES &
 UNIONS DOES NOT INDICATE THE LENGTH.
  
 B. OK
 C. OK
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE VERIFIED WHEN
 COMMENT "21-A" ADDRESSED).
 ****RESPONSE NOTED, TO BE VERIFIED WHEN COMMENT 21-A IS
 ADDRESSED.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 F. N/A
 G. N/A
 H. N/A
 I. N/A
  
 ******NEW COMMENTS******
  
 1B. SHT PK103 CODE REFERENCE IN NOTE UNDER BUILDING GAS
 REQUIREMENT IS INDICATED AS FBC-2004. CODE IN EFFECT
 FOR THIS REVIEW IS FBC-2007. PLEASE UPDATE CODE
 REFERENCE.
  
 2B. SHT PK103 PLEASE SUBMIT MANUF. SPECIFICATIONS FOR
 THE SECOND STAGE REGULATOR SHOWING LISTING/APPROVAL,
 MODEL NUMBER AND OUTLET CAPACITY. SECTIONS 410.1 &
 410.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date   Cont ID  
Sent By   Date 2011-01-07 Time   Rev Time 0.00
Received By rmcdouga Date 2010-12-13 Time 07:27 Sent To  
Notes
2010-12-15 07:27:34C4

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2010-10-18 Cont ID  
Sent By lmartine Date 2010-10-18 Time 13:32 Rev Time 0.00
Received By lmartine Date 2010-10-18 Time 13:32 Sent To  
Notes
2010-10-18 13:32:55C--26

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2010-09-29 Cont ID  
Sent By lmartine Date 2010-09-29 Time 11:54 Rev Time 0.00
Received By lmartine Date 2010-09-29 Time 11:54 Sent To  
Notes
2010-09-29 11:55:56IN ZONING BOX
2010-09-29 11:55:01LANDSCAPE AND ENGINEERING RESPONCES ONLY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-09-28 Cont ID  
Sent By rmcdouga Date 2010-09-28 Time 16:27 Rev Time 0.00
Received By rmcdouga Date 2010-09-27 Time 16:27 Sent To  
Notes
2010-09-28 16:28:00SENT TO L. MARTINEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-08-26 Cont ID  
Sent By lmartine Date 2010-07-28 Time 15:41 Rev Time 0.00
Received By lmartine Date 2010-07-28 Time 15:41 Sent To  
Notes
2010-08-26 15:42:13C--27

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-08-26 Cont ID  
Sent By lmartine Date 2010-04-05 Time 15:43 Rev Time 0.00
Received By lmartine Date 2010-02-01 Time 15:43 Sent To  
Notes
2010-02-01 15:56:46SENT TO C1.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2011-04-08 Cont ID  
Sent By lmartine Date 2011-04-08 Time 14:48 Rev Time 0.00
Received By lmartine Date 2011-04-08 Time 14:48 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-08-16 Cont ID  
Sent By jwitmer Date 2010-08-16 Time 16:04 Rev Time 0.00
Received By jwitmer Date 2010-08-16 Time 16:03 Sent To  
Notes
2010-08-16 16:03:57BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop L LANDSCAPING
Rev No 4 Status N Date 2010-10-20 Cont ID  
Sent By rkussner Date 2010-10-20 Time 16:14 Rev Time 0.00
Received By rkussner Date 2010-10-20 Time 16:14 Sent To  
Notes
2010-10-20 16:15:31***LANDSCAPE REVIEW NOT REQUIRED***
  
 PLEASE REFER TO PERMIT #10100313 FOR LANDSCAPE PERMIT
 AND PLANS.

Review Stop L LANDSCAPING
Rev No 3 Status F Date 2010-10-04 Cont ID  
Sent By rkussner Date 2010-10-04 Time 08:43 Rev Time 0.00
Received By rkussner Date 2010-10-04 Time 08:43 Sent To  
Notes
2010-10-04 08:47:08***LANDSCAPE REVIEW FAILED***
  
 1. PLEASE APPLY FOR THE LANDSCAPE PERMIT AND SUBMIT TWO
 (2) COPIES OF THE SIGNED AND SEALED LANDSCAPE PLAN AND
 COST ESTIMATE. THE FEES MAY NEED TO BE ADJUSTED WITH
 CONSTRUCTION SERVICES.
  
 2. PLEASE APPLY FOR AN IRRIGATION PERMIT AND SUBMIT TWO
 (2) COPIES OF THE IRRIGATION PLAN.
  
 3. THE HEDGE SURROUNDING THE TRANSFORMER SHALL BE
 ADJACENT TO THE TRANSFORMER ON THREE (3) SIDES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2010-08-12 Cont ID  
Sent By rkussner Date 2010-08-12 Time 13:18 Rev Time 0.00
Received By rkussner Date 2010-08-12 Time 13:18 Sent To  
Notes
2010-08-12 13:57:35***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. REPEAT COMMENT: PLEASE APPLY FOR SEPARATE LANDSCAPE
 AND IRRIGATION PERMITS. WHEN APPLYING FOR THE LANDSCAPE
 PERMIT, PLEASE PROVIDE TWO (2) COPIES OF THE LANDSCAPE
 PLAN AND A CERTIFIED COST ESTIMATE THAT INCLUDES THE
 TOTAL COST OF ALL LANDSCAPE MATERIALS AND LABOR, BROKEN
 DOWN INTO UNIT COST.
  
 2. THE CAR STOP DETAIL PROVIDED IS INCORRECT.
 DOUBLE-SIDED CAR STOPS ARE NOT PERMITTED BY CITY CODE.
  
 3. REPEAT COMMENT: A TREE ALTERATION PERMIT WILL BE
 REQUIRED. THE APPLICATION IS AVAILABLE AT THE FRONT
 DESK OF THE PLANNING AND ZONING DEPARTMENT.
  
 4. THE HEDGE THAT WAS TO SCREEN THE DUMPSTER AT THE
 SOUTHEAST CORNER OF THE SITE WAS LEFT ON THE LANDSCAPE
 PLAN, EVEN THOUGH THE DUMPSTER PAD HAS BEEN REMOVED.
 PLEASE REDESIGN THE LANDSCAPING OF THAT AREA.
  
 5. SOME OF THE PROPOSED TREES APPEAR TO BE CLOSE TO
 OVERHEAD LINES. YOU ARE REQUIRED TO ABIDE BY FPL'S
 "PLANT THE RIGHT TREE IN THE RIGHT PLACE" PROGRAM WHICH
 REGULATES WHICH TREES CAN BE PLANTED NEAR OR UNDER
 POWER LINES. SOME OF THE TREE SPECIES MAY NEED TO BE
 CHANGED.
  
 6. THE EXISTING TREE IN THE RIGHT-OF-WAY ALONG DIVISION
 AVENUE TOWARD THE NORTH END SHALL REMAIN OR BE
 REPLACED. IT IS REQUIRED TO TERMINATE THE ON-STREET
 PARALLEL PARKING ROW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2010-03-26 Cont ID  
Sent By rkussner Date 2010-03-26 Time 15:56 Rev Time 0.00
Received By rkussner Date 2010-03-26 Time 15:56 Sent To  
Notes
2010-03-26 16:30:51***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. PLEASE APPLY FOR SEPARATE LANDSCAPE AND IRRIGATION
 PERMITS.
  
 2. CREDIT WAS TAKEN FOR THE USE OF THREE (3) INCHES OF
 MULCH BUT THE DETAIL SHOWS ONLY A TWO (2) INCH LAYER.
 PLEASE NOTE THAT THE SHRUBS SHALL BE PLANTED ONE AND
 ONE HAVE INCHES ABOVE GRADE AND THE THREE (3) INCH
 LAYER OF MULCH IS PLACED OUTSIDE OF THE ROOTBALL, WITH
 ONLY A SMALL AMOUNT OF MULCH PLACED DIRECTLY ABOVE THE
 ROOTBALL.
  
 3. THE PARKING DETAIL PROVIDED IS INCORRECT. PLEASE USE
 THE STANDARD CITY STRIPING DETAIL. A COPY OF THIS
 DETAIL IS AVAILABLE AT THE FRONT DESK OF THE PLANNING
 AND ZONING DEPARTMENT.
  
 4. PURSUANT TO SECTION 94-445 (4) (G) (3) (II), IN ALL
 AREAS THAT ARE TO BE PLANTED IN A CULTIVATED LANDSCAPE,
 IRRIGATION SYSTEMS SHALL BE DESIGNED TO HAVE 120
 PERCENT COVERAGE. THIS INCLUDES THE RIGHTS-OF-WAY.
  
 5. PURSUANT TO SECTION 94-448 (D) (2), THE LANDSCAPE
 PLAN SHALL CONTAIN ALL OF THE ITEMS LISTED IN THIS
 SECTION. ALL UTILITIES, SITE LIGHTING, EASEMENTS,
 OVERHEAD WIRES AND ANYTHING ELSE THAT MIGHT INTERFERE
 WITH THE PROPOSED LANDSCAPING SHALL BE SHOWN ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS.
  
 6. PURSUANT TO SECTION 94-443 (C) (3) (A), EVERY
 TERMINAL LANDSCAPE ISLAND SHALL CONTAIN ONE SHADE OR
 FLOWERING TREE. THE REQUIRED TREE WAS NOT SHOWN IN THE
 LANDSCAPE ISLAND AT THE WEST END OF THE ANGLED PARKING
 ROW OR AT THE NORTH END OF THE PARALLEL PARKING ROW ON
 THE EAST SIDE OF THE SITE. THE PROPOSED TREE AT THE
 EAST END OF THE ANGLED PARKING ROW SHOULD BE CENTERED
 WITHIN THE ISLAND.
  
 7. A TREE ALTERATION PERMIT WILL BE REQUIRED. THE
 APPLICATION IS AVAILABLE AT THE FRONT DESK OF THE
 PLANNING AND ZONING DEPARTMENT.
  
 8. A NOTE ON THE PLAN INDICATES THAT THE LIVE OAK TREES
 ON DIVISION STREET ARE TO REMAIN BUT ANOTHER NOTE
 INDICATES THAT ONE OF THE TREES IS TO BE REMOVED.
 PLEASE CLARIFY.
  
 9. CURBING IS SHOWN IN THE ALLEY, OUTSIDE OF THE
 PROPERTY LINE. THE CITY ENGINEERING DEPARTMENT WILL
 NEED TO DETERMINE IF THIS IS ACCEPTABLE.
  
 10. THREE (3) SCREENED DUMPSTERS ARE SHOWN ALONG THE
 EAST SIDE OF THE BUILDING. THE DUMPSTER PAD AT THE
 SOUTHEAST CORNER OF THE SITE SHOULD NOT BE INSTALLED.
 SHOULD A DUMPSTER BE PLACED ON THAT PAD, IT MUST BE
 SCREENED BY A WALL OR OTHER FENCING AND LANDSCAPING.
 VISION OBSCURING GATES ARE REQUIRED AND THEY CANNOT
 OPEN INTO THE TRAVEL LANE (ALLEY).

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2010-12-29 Cont ID  
Sent By hmoser Date 2010-12-29 Time 14:41 Rev Time 0.00
Received By hmoser Date 2010-12-29 Time 14:41 Sent To  
Notes
2010-12-29 14:43:17NO MECHANICAL SUBMITTED WITH PLANS .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-08-31 Cont ID  
Sent By hmoser Date 2010-08-31 Time 10:50 Rev Time 0.00
Received By hmoser Date 2010-08-31 Time 10:50 Sent To  
Notes
2010-08-31 11:05:01PASS PROVISO
 1) SEPARATE PERMITS ARE REQUIRED FOR THE HOOD AND WALK
 IN COOLERS.
 2) DETAILS MUST BE SUBMITTED TO THE INSPECTOR AT THE
 TIME OF THE FIRST INSPECTION ON ALL ROOF MOUNTED CURBS
 AND STANDS.
 3) PLEASE PROVIDE MODEL NUMBERS AND SEER RATINGS ON THE
 EQUIPMENT SCHEDULE FOR ROUGH INSPECTION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-02-02 Cont ID  
Sent By rregueir Date 2010-02-02 Time 16:51 Rev Time 0.00
Received By rregueir Date 2010-02-02 Time 08:27 Sent To  
Notes
2010-02-02 16:51:17REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW CYCLE COMMENTS FOR CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. OK
  
 4. PAGES M101 AND M102: KEY NOTE #4 ON PAGE M101 CALLS
 FOR CARBON DIOXIDE DETECTORS FOR DEMAND CONTROL
 VENTILATION WHILE KEY NOTE #4 ON PAGE M102 CALLS FOR
 CARBON MONOXIDE DETECTORS. MAKE CORRECTIONS AND SHOW
 HOW THE REQUIRED RATE OF VENTILATION IS TO BE PROVIDED
 FOR THE SECOND FLOOR IN ACCORDANCE WITH FBCM SECTION
 403.
  
 5. OK
  
 6. PAGE M102: THE 10 INCH ROUND DUCT PENETRATING THE
 CORRIDOR WALL AT ALCOVE 217 REQUIRES A SMOKE DAMPER IN
 ADDITION TO THE FIRE DAMPER SHOWN ON PLANS IN
 ACCORDANCE WITH FBCM 607.5.4. SHOW HOW THE SMOKE DAMPER
 IS TO BE ACTUATED IN ACCORDANCE WITH FBCM 607.3.2.1.
  
 7. PAGE M102: OK. KITCHEN GREASE EXHAUST SYSTEM
 REQUIRES SEPARATE PLANS AND PERMIT APPLICATION. NO
 LONGER PART OF THIS REVIEW.
  
 8. OK
  
 9. OK
  
 10. PAGE M202 DETAILS FOR ALL ROOF MOUNTED AND OUTDOOR
 EQUIPMENT AND APPLIANCES: DETAIL REFERENCES STRUCTURAL
 DRAWINGS. NO DETAIL FOR ROOF CURB INSTALLATION COULD BE
 FOUND IN STRUCTURAL DRAWINGS. ALSO, PROVIDE
 MANUFACTURER'S DATA FOR ALL OUTDOOR APPLIANCES SHOWING
 THEY ARE DESIGNED FOR WIND RESISTANCE PER FBCM 301.12.
  
 11. OK
  
 12. OK
  
 13. OK. KITCHEN GREASE EXHAUST SYSTEM REQUIRES SEPARATE
 PLANS AND PERMIT APPLICATION. NO LONGER PART OF THIS
 REVIEW.
  
 14. THE ENERGY CODE COMPLIANCE FOR SUBMITTED IS NO
 LONGER VALID AS OF MARCH 1, 2009. SUBMIT THE CORRECT
 METHOD A ENERGY CODE COMPLIANCE FORM FOR REVIEW. ALSO,
 COOLING LOAD CALCULATIONS SHALL BE APPENDED TO THE
 ENERGY CODE COMPLIANCE FORM IN ACCORDANCE WITH FBCB
 13-407.AB.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2010-12-29 Cont ID  
Sent By lwagner Date 2010-12-29 Time 10:56 Rev Time 0.00
Received By lwagner Date 2010-12-29 Time 10:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2010-12-16 Cont ID  
Sent By lwagner Date 2010-12-16 Time 14:42 Rev Time 0.00
Received By lwagner Date 2010-12-16 Time 09:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-10-27 Cont ID  
Sent By lwagner Date 2010-10-27 Time 09:09 Rev Time 0.00
Received By lwagner Date 2010-10-26 Time 09:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2010-08-25 Cont ID  
Sent By lwagner Date 2010-08-25 Time 14:01 Rev Time 0.00
Received By lwagner Date 2010-08-05 Time 14:18 Sent To  
Notes
2010-08-23 12:55:04FBC PLUMBING 2007
 FBC GAS 2007
 PLUMBING REVIEW #2
 DENIED:
  
 FROM PREVIOUS REVIEW OK
  
 NEW
  
 1. ICE MACHINE FLOOR SINK IS REQUIRED TO DRAIN TO
 SANITARY.
 FBC PLUMBING 1003.2
  
 2. THE WASHING MACHINE IS SHOWN IN GREASE LINE. IS
 THERE A SPECIAL REASON? OTHERWISE, THE WASHING MACHINE
 SHOULD BE ROUTED TO THE SANITARY. 1003.2
  
 3. IF THE STEAM TABLE IS CLEAR WATER ONLY TO HEAT
 CONTAINERS, THE WASTE IS REQUIRED TO GO TO THE
 SANITARY. 1003.2
  
 3. THE DISHWASHER WASTE IS REQUIRED TO BE THROUGH AN
 INDIRECT WASTE, SUCH AS A FLOOR SINK.
 802.1.7
  
 4. PLEASE INCLUDE CALCULATIONS FOR ALL FLOW FROM THE
 KITCHEN GREASE LINE AND DETERMINE THE SIZE OF THE
 GREASE INTERSEPTOR/S. NOTE*** MORE THAN ONE GREASE
 INTERCEPTOR MAY BE REQUIRED, DEPENDING ON THE
 CALCULATED FLOW FROM ALL FIXTURES. PDI G101 METHODS MAY
 BE USED TO SIZE THE INTERCEPTOR/S. USING THIS METHOD A
 1011 GALLON CAPACITY WOULD BE REQUIRED FOR A TYPICAL 3
 COMPARTMENT SINK ALONE. THE CHART ON SHEET C-7 LOOKS TO
 BE FOR AN OIL SEPARATOR FOR GARAGES. THE TABLE
 1003.3.4.1 IS CALLED FOR IN THE PLUMBING CODE.
  
 5. SHEET P201 SHOWS CONDENSATE TO GROUND. FOR A SINGLE
 UNIT UNDER 5 TONS THIS WILL BE OK. MULTIPLE UNITS ARE
 REQUIRED TO BE CONVEYED TO AN APPROVED PLACE OF
 DISPOSAL SO AS NOT CAUSE A NUISANCE.
 FBC PLUMBING 314.2.1
  
 NOTE*** SHEET P201 & KD101 A DEEP SEAL FOR FLOOR DRAINS
 IS NO LONGER PERMITTED. A TRAP PRIMER WHICH IS ALREADY
 SHOWN ON THE PLAN IS REQUIRED.
 FBC 2007 PLUMBING 1002.4
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-02-16 Cont ID  
Sent By kstevens Date 2010-02-16 Time 11:16 Rev Time 0.00
Received By kstevens Date 2010-02-16 Time 11:16 Sent To  
Notes
2010-02-16 13:41:28DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW, #08050795:
  
 1. OK
 2. OK
  
 3. SHTS 1 OF 2 IRRIGATION SHOW THE LOCATION OF THE
 CONTROLLER AND THE RAIN SENSOR. SECTION 106.1.2 & FS
 373.62.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 4. OK
 5. OK
  
 6. SHT 1 OF 15 SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLES 1004.1.2 & 403.1. INDICATE IF
 EACH SPACE IS CONSENTRATED, STANDING SPACE OR
 UNCONSENTRATED. (EDUCATIONAL - MEETING ROOMS - WORKROOM
 - MULTIPURPOSE COMMUNITY ROOM). THE OCCUPANCY INDICATED
 372 & 216 SHALL BE VERIFIED.
 ****RESPONSE NOTED, BUT THE FLOOR AREA IN SQUARE FOOT
 OCCUPANT SHALL REFLECT TABLE 1004.1.1 OF THE BUILDING
 CODE. RECHECK AREA AT THE LOBBY/RECEPTION AREA, (NET
 SF). THE MULTIPURPOSE ROOM SHALL BE 5 NET NOT 15 NET.
 THE OFFICE AREAS SHALL BE 100 GROSS NOT 3. THE
 EDUCATIONAL ROOM 20 NET. THE READING ROOM SHALL BE 50
 NET OR 100 GROSS DEPENDING ON BOOK STACKS ETC. PLEASE
 RECHECK ALL AREAS. DEPENDING ON THE COMMENT RESPONSES,
 MORE COMMENTS MAY FOLLOW.
  
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
  
 12. SHT P401 SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN AS THERE ARE OFFSETS IN THE PIPING SHOWN
 ON THE FLOOR PLAN THAT ARE NOT SHOWN ON THE RISER
 DIAGRAM AS WELL AS THE BASE OF THE STACK TO TOILET
 ROOMS 223 & 224 DOES NOT REFLECT THE FLOOR PLAN. (RISER
 TURNS SOUTH & FLOOR PLAN TURNS NORTH). SECTION 106.1.1.
 PLEASE CORRELATE.
 ****RESPONSE NOTED, BUT THE COMMENT NOT ADDRESSED FOR
 THE OFFSETS AND THE BASE OF THE RISER TO TOILET ROOMS
 223 & 224 IS NOT SHOWN ON THE FLOOR PLAN.
  
 13. SHT P401 CONDENSATE RISER DIAGRAM THE PIPE SIZES DO
 NOT REFLECT THE FLOOR PLAN IN MANY AREAS. PLEASE
 CORRELATE AND SHOW ALL PIPE SIZES. ALSO THE CONDENSATE
 LINE DOWNSTREAM OF UNIT 1FC:6 IS SHOWN CONNECTING TO
 THE 2ND FLOOR CONDENSATE RISER ON THE RISER BUT NOT ON
 THE FLOOR PLAN. SECTION 106.1.1 & 314.
 ****RESPONSE NOTED, BUT SOME PIPE SIZES ARE STILL
 DIFFERENT AND SOME PIPE SIZES ARE NOT SHOWN.
  
 14. SHT P401 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN IN ABOUT 7 OR 8 AREAS. THE STUB-OUTS FOR THE
 FIXTURES IN THE GANG BATHS ARE SHOWN TURNING THE WRONG
 WAY, (AWAY FROM THE FIXTURES), AND PIPING THE THE
 CEILING FOR BRANCH CONNECTIONS TO THE WATER MAINS DOES
 NOT RELFECT IN SOME AREAS. THE DRINKING FOUNTAIN
 SUPPLIES ARE NOT SHOWN ON THE RISER AS WELL AS THE
 SUPPLY LINES TO THE SHOWER AND A "BS" FOR THE SECOND
 FLOOR. SECTIONS 106.1.1 & 601.1.
 ****RESPONSE NOTED, BUT THE SHOWER SHOWN BETWEEN THE
 "BS" FIXTURES ON THE FLOOR PLAN IS SHOWN BEFORE THE
 FIRST BS FIXTURE ON THE RISER DIAGRAM. THE DRINKING
 FOUNTAINS AND ONE SINK SHOWN ON THE FLOOR PLAN FOR THE
 SECOND FLOOR ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE
 CORRELATE.
  
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
  
 21. SHT KP103 A SEPARATE GAS PERMIT IS REQUIRED. PLEASE
 SUPPLY THE FOLLOWING INFORMATION FOR GAS PERMIT
 APPROVAL:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (CUT SECTIONS FROM THE METER TO THE
 FIRST RISER, AND THE DROP WITH THE VALVES AND UNIONS DO
 NOT INDICATE THE LENGTHS).
 ****RESPONSE NOTED, BUT THE DROP WITH THE VALVES &
 UNIONS DOES NOT INDICATE THE LENGTH.
  
 B. OK
 C. OK
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE VERIFIED WHEN
 COMMENT "21-A" ADDRESSED).
 ****RESPONSE NOTED, TO BE VERIFIED WHEN COMMENT 21-A IS
 ADDRESSED.
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 F. N/A
 G. N/A
 H. N/A
 I. N/A
  
 22. OK
  
 ******NEW COMMENTS******
  
 1B. SHTS P101 FLOOR PLAN & P401 SANITARY ISOMETRIC
 RISER DIAGRAM. THE FLOOR DRAINS IN TOILET ROOMS 105 &
 108 ARE NOT VENTED AS PIPED. SECTION 901.2.
  
 2B. SHT PK103 CODE REFERENCE IN NOTE UNDER BUILDING GAS
 REQUIREMENT IS INDICATED AS FBC-2004. CODE IN EFFECT
 FOR THIS REVIEW IS FBC-2007. PLEASE UPDATE CODE
 REFERENCE.
  
 3B. SHT PK103 PLEASE SUBMIT MANUF. SPECIFICATIONS FOR
 THE SECOND STAGE REGULATOR SHOWING LISTING/APPROVAL,
 MODEL NUMBER AND OUTLET CAPACITY. SECTIONS 410.1 &
 410.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2010-12-21 Cont ID  
Sent By astelly Date 2010-12-21 Time 16:04 Rev Time 0.00
Received By astelly Date 2010-12-21 Time 16:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2010-08-24 Cont ID  
Sent By astelly Date 2010-08-24 Time 08:22 Rev Time 0.00
Received By astelly Date 2010-08-24 Time 08:22 Sent To  
Notes
2010-08-24 08:35:12AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PROVISO
 ALL LANDSCAPE COMMENTS MUST BE SATISFIED.

Review Stop Z ZONING
Rev No 2 Status F Date 2010-08-17 Cont ID  
Sent By astelly Date 2010-08-17 Time 17:53 Rev Time 0.00
Received By astelly Date 2010-08-17 Time 14:52 Sent To  
Notes
2010-08-17 18:02:36AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 REPEAT COMMENT:
 SEVERAL DRAWINGS INDICATE THAT THE CURBING STILL SEEMS
 TO BE ENCROACHING INTO THE ALLEY. CURBING SHOULD BE
 CONFINED TO THE LIMITS OF THE PROPERTY.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-03-26 Cont ID  
Sent By aaponte Date 2010-03-26 Time 10:10 Rev Time 0.00
Received By aaponte Date 2010-03-26 Time 10:10 Sent To  
Notes
2010-03-26 10:24:551. DUMPSTER CONFIGURATION SHALL BE APPROVED BY ENG.
 DEPARTMENT. IF PROPOSED LAYOUR IS APPROVED, DUMPSTER
 WALLLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS.
 2. DAC FINAL ORDER REQUIREMENT REGARDING A ROW OF HEDGE
 BETWEEN THE SIDEWALK AND THE ACCESIBILITY RAMP WILL BE
 ADMINISTRATIVELY WAIVED.
 3. PLEASE CONFIRM THERE ARE NO CONFLICTS BETWEEN THE
 GRADE ELEVATION AT THE SIDEWALK AND THE GRADE ELEVATION
 AT THE VEHICULAR DRIVE EXIT.
 4. PLEASE CONFIRM THE MINIMUM CLEARANCE FOR THE
 HANDICAP RAMP IS MET. BOLLARDS HAVE BEEN LOCATED ALONG
 THE RAMP.
 5. A TREE REMOVAL PERMIT IS REQUIRED. PLEASE CONTACT
 ROBER KUSSNER AT 561-822-1462.
 6. DRAWINGS SHOW SOME CURBS ENCROACHING INTO THE ALLEY.
 PLEASE CLARIFY AND CORRECT.


Account Summary | Usage Policy | Privacy Policy