| 2010-02-11 10:38:06 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. FBC1008.1.3.5, MEANS OF EGRESS CONTINUITY (CANNOT |
| | BLOCK MEANS OF EGRESS WITH ANY ELEMENT OTHER THAN |
| | ALLOWED IN FBC CHAPTER 10). PLEASE CLARIFY BY REVISING |
| | THE FLOOR PLAN, DOES THIS PROPOSE TO COVER A REQUIRED |
| | EXIT DOOR? "STOREFRONT EGRESS" WAS WRITTEN WITH A LINE, |
| | NOT CLEAR WHETHER THE LINE DEPICTS A DOOR (WITH |
| | INSWING) OR WHETHER THIS IS AN ARROW. PLEASE REVISE |
| | PLAN SO THAT CODE COMPLIANCE CAN BE DETERMINED. |
| | |
| | PLEASE NOTE THAT THE FBC DOES NOT HAVE A PROVISION TO |
| | COVER A REQUIRED EXIT DOOR WITH HURRICANE SHUTTERS - |
| | THIS IS PERMITTED ON A CASE BY CASE BASIS |
| | PLANS SUBMITTED DO NOT PROVIDE ENOUGH INFORMATION TO |
| | SHOW THAT LIFE SAFETY REQUIREMENTS ARE MET. |
| | |
| | PLEASE REVISE THE PLAN TO INCLUDE LIFE SAFETY |
| | INFORMATION: |
| | |
| | OVERALL DIMENSIONS - CANNOT DETERMINE TRAVEL DISTANCE, |
| | OCCUPANT LOAD (BASED ON TOTAL SQUARE FOOT AREA) AS NO |
| | DIMENSIONS ARE ON THE PLAN |
| | FLOOR PLAN - NO INTERIOR WALLS? |
| | ROOM DESIGNATIONS |
| | LOCATION OF EXIT LIGHTS |
| | OCCUPANCY CLASSIFICATION FBC CHAPTER 3 |
| | SHOW DOOR SWING (IS THE ACCORDION OPERABLE FROM THE |
| | INSIDE?) |
| | OCCUPANT LOAD |
| | |
| | 2. FBC1008.1.3.5, PLEASE DECLARE OCCUPANCY |
| | CLASSIFICATION PER FBC CHAPTER 3. OTHER INFORMATION MAY |
| | BE REQUIRED SUCH AS: EXIT DOOR SWING, OTHER EXITS, |
| | FLOOR PLAN, OCCUPANT LOAD. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. PLEASE DECLARE OCCUPANCY |
| | CLASSIFICATION FBC CHAPTER 3 OR PROVIDE ENOUGH |
| | INFORMATION ABOUT THE USE OF THE SPACE SO THAT AN |
| | OCCUPANCY CLASSIFICATION CAN BE DETERMINED. |
| | |
| | YOU MAY SUBMIT THE REVISED FLOOR PLAN BY EMAIL, |
| | [email protected]. PLEASE BE SURE TO INCLUDE ALL |
| | INFORMATION REQUESTED. |
| | |