| Plan Review Stops For Permit 10010491 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2010-02-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-02-02 |
Time |
16:11 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2010-02-01 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2010-02-02 16:11:01 | BUILDING PLAN REVIEW | | | PERMIT: 09100416/ REV. 10010491 | | | ADD: 22420 MEDINA WAY | | | CONT: D & A BUILDERS | | | TEL: (561)662-6226 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). | | | | | | 1) ROOFING PRODUCT APPROVAL SUBMITTED: | | | TAMKO MODIFIED BITUMEN ROOFING OVER WOOD DECK | | | NOA: 07-0730.03 | | | PAGE 16 | | | DECK TYPE 1 WOOD NON-INSULATED | | | | | | OPTION #1 -52.5 LIMITATION# 7. | | | OPTION #2 -60.0 LIMITATION# 7. | | | | | | ROOFING CONTRACTOR WILL NEED TO SUBMIT WHICH OPTION | | | WILL BE INSTALLED, AND WILL ALSO NEED TO SUBMIT RAS 117 | | | CALCULATIONS, ENHANCED FASTENING FOR ZONES 2 & 3. | | | THIS REVIEW WILL BE UNDER SEPERATE PERMIT, WITH | | | ASSOCIATED FEES AND REVIEW. | | | | | | 2) STRUCTURAL REVISIONS ARE TO BE SUBMITTED TO THE CITY | | | FOR RECORD KEEPING PURPOSES, THE STRUCTURAL INSPECTIONS | | | BY LEN TYLKA ARE TO BE TURNED IN WEEKLY WITH WEEKLY | | | REPORTSAS PER THE BUILDING OFFICIAL DOUG WISE. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE | | | CUSTOMER SERVICE SURVEY AT: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2010-02-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-02-02 |
Time |
16:11 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2010-02-02 |
Time |
16:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2010-02-04 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-02-04 |
Time |
17:05 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-02-04 |
Time |
17:04 |
Sent To |
|
|
| Notes |
| 2010-02-04 17:07:53 | **********************EXPEDITED******************* | | | 2ND RUN | | | GAVE TO KEN STEVENS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2010-02-04 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-02-04 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-01-27 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2010-01-27 16:29:28 | ******************EXPEDITED********************* | | | R--3 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2010-02-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-02-09 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2010-02-09 |
Time |
11:55 |
Sent To |
|
|
| Notes |
| 2010-02-09 11:56:15 | PR# 2010-0204-181 ($977.49) |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2010-02-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-02-02 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2010-02-02 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2010-02-02 16:13:13 | BEFORE A REVISIONFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE | | | CUSTOMER SERVICE SURVEY AT: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2010-02-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2010-02-08 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2010-02-08 |
Time |
09:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2010-02-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2010-02-01 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2010-02-01 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2010-02-01 10:24:02 | DENIED | | | REFERENCE: | | | FBC-2007 PLUMBING | | | FBC-2007 RESIDENTIAL | | | FBC-2007 EXISTING BUILDING | | | FBC-2007 CHAPTER 1 | | | | | | 1. SHT A2-06 MORE INFORMATION REQUIRED. SECTION | | | 106.1.1. SUBMIT THE FOLLOWING: | | | | | | A. INDICATE THE TOTAL SQUARE FOOTAGE BEING DRAINED BY | | | THE EXISTING ROOF DRAIN. SHOW TOTAL SQUARE FOOTAGE OF | | | EXISTING ROOF SECTION WITH THE ROOF DRAIN, THE SQUARE | | | FOOTAGE OF THE NEW ROOF DRAINING ON TO THE ROOF, ONE | | | HALF THE ADDITIONAL SQUARE FOOTAGE OF THE VERTICAL | | | WALLS FOR THE NEW ROOF, THE SQUARE FOOT AREA OF THE HIP | | | ROOF THAT DRAINS ONTO THE ROOF & THE SQUARE FOOTAGE OF | | | THE CHANGE IN LEVEL INDICATED (PLEASE CLARIFY). | | | SECTIONS 1101.2, 1106.4, 1107.1, 1107.2 & 1107.3 AS | | | WELL AS TABLES 1106.2, 1106.3 & 1106.2. | | | | | | B. SUBMIT A DETAIL FOR THE SCUPPER ON THE NEW ROOF. | | | INDICATE HEIGHT, WIDTH, LENGTH. TABLE 1106.7. | | | | | | C. INDICATE THE SIZE OF THE EXISTING ROOF DRAIN AS WELL | | | AS THE SIZE OF THE VERTICAL & HORIZONTAL CONDUCTOR & | | | LEADER. TABLES 1106.2, 1106.3 & 1106.7. | | | | | | D. INDICATE THE SIZE OF THE EXISTING OVERFLOW SCUPPERS | | | SERVING THE EXISTING ROOF WITH THE ROOF DRAIN. TABLE | | | 1106.1. | | | | | | E. FOR THE NEW ROOF, A SEPARATE SECONDARY ROOF DRAIN IS | | | REQUIRED PER SECTIONS 1107.1 & 1107.2. PLEASE SUBMIT A | | | DETAIL AND SHOW THE LOCATION OF THE SECONDARY ROOF | | | DRAIN. ALSO SEE SECTION R903.4.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2010-02-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2010-02-01 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2010-01-28 |
Time |
19:05 |
Sent To |
|
|
| Notes |
| 2010-02-01 09:46:04 | REVISIONS OK -- SHTS P-01 & P2-01. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2010-02-04 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2010-02-04 |
Time |
09:42 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2010-02-04 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2010-02-04 09:48:27 | PASSED W/PROVISO | | | | | | 1) PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF | | | THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE | | | (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE | | | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF | | | THE ZLDR. PAPA SHOWS THE IMPROVEMENT VALUE AS $734,432 | | | AND THE PERMIT VALUES FOR PHASE I AND PHASE II TOTALS | | | $443,500 (GREATER THAN 50%). | | | | | | 2) PRIOR TO THE CERTIFICATE OF OCCUPANCY (C.O.), A | | | LANDSCAPE PERMIT SHOWING COMPLIANCE WITH SECTIONS | | | 94-442 AND 94-445 OF THE ZLDR IS REQUIRED TO BE | | | SUBMITTED TO THE CONSTRUCTION SERVICES DEPARTMENT AND | | | THE LANDSCAPE SHALL BE INSTALLED AND RECEIVE A FINAL | | | (502) INSPECTION APPROVAL. NOTE: IT APPEARS FROM THE | | | AERIAL OF THE SITE THAT THERE ARE PALM TREES BEING | | | REMOVED IN THE LOCATION OF THE NEW LOGGIA, THE PLANS | | | INDICATE THERE IS NEW LANDSCAPE BEING INSTALLED, AND | | | LANDSCAPE IS BEING REMOVED FOR THE INSTALLATION OF THE | | | GENERATOR. | | | | | | 3) THE GENERATOR REQUIRES A SEPARATE PERMIT. THE | | | GENERATOR SHALL BE SCREENED WITH LANDSCAPE FROM THE | | | PROPERTY TO THE NORTH. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2010-02-03 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2010-02-03 |
Time |
14:40 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2010-02-03 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2010-02-03 14:57:05 | FAILED | | | | | | 1) PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF | | | THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE | | | (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE | | | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF | | | THE ZLDR. PAPA SHOWS THE IMPROVEMENT VALUE AS $734,432 | | | AND THE PERMIT VALUES FOR PHASE I AND PHASE II TOTALS | | | $443,500 (GREATER THAN 50%). | | | | | | 2) PRIOR TO THE ZONING DIVISION APPROVING THIS PERMIT A | | | LANDSCAPE, A LANDSCAPE PERMIT SHOWING COMPLIANCE WITH | | | SECTIONS 94-442 AND 94-445 OF THE ZLDR IS REQUIRED TO | | | BE SUBMITTED TO THE CONSTRUCTION SERVICES DEPARTMENT. | | | NOTE: IT APPREARS FROM THE AERIAL OF THE SITE THAT | | | THERE ARE PALM TREES BEING REMOVED IN THE LOCATION OF | | | THE NEW LOGGIA, THE PLANS INDICATE THERE IS NEW | | | LANDSCAPE BEING INSTALLED, AND LANDSCAPE IS BEING | | | REMOVED FOR THE INSTALLATION OF THE GENERATOR. | | | | | | 3) THE GENERATOR REQUIRES A SEPARATE PERMIT. THE | | | GENERATOR SHALL BE SCREENED WITH LANDSCAPE FROM THE | | | PROPERTY TO THE NORTH. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|