Plan Review Details - Permit 10010491
Plan Review Stops For Permit 10010491
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-02-02 Cont ID  
Sent By jwitmer Date 2010-02-02 Time 16:11 Rev Time 1.50
Received By jwitmer Date 2010-02-01 Time 10:58 Sent To  
Notes
2010-02-02 16:11:01BUILDING PLAN REVIEW
 PERMIT: 09100416/ REV. 10010491
 ADD: 22420 MEDINA WAY
 CONT: D & A BUILDERS
 TEL: (561)662-6226
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 1) ROOFING PRODUCT APPROVAL SUBMITTED:
 TAMKO MODIFIED BITUMEN ROOFING OVER WOOD DECK
 NOA: 07-0730.03
 PAGE 16
 DECK TYPE 1 WOOD NON-INSULATED
  
 OPTION #1 -52.5 LIMITATION# 7.
 OPTION #2 -60.0 LIMITATION# 7.
  
 ROOFING CONTRACTOR WILL NEED TO SUBMIT WHICH OPTION
 WILL BE INSTALLED, AND WILL ALSO NEED TO SUBMIT RAS 117
 CALCULATIONS, ENHANCED FASTENING FOR ZONES 2 & 3.
 THIS REVIEW WILL BE UNDER SEPERATE PERMIT, WITH
 ASSOCIATED FEES AND REVIEW.
  
 2) STRUCTURAL REVISIONS ARE TO BE SUBMITTED TO THE CITY
 FOR RECORD KEEPING PURPOSES, THE STRUCTURAL INSPECTIONS
 BY LEN TYLKA ARE TO BE TURNED IN WEEKLY WITH WEEKLY
 REPORTSAS PER THE BUILDING OFFICIAL DOUG WISE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-02-02 Cont ID  
Sent By jwitmer Date 2010-02-02 Time 16:11 Rev Time 1.50
Received By jwitmer Date 2010-02-02 Time 16:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-02-04 Cont ID  
Sent By lmartine Date 2010-02-04 Time 17:05 Rev Time 0.00
Received By lmartine Date 2010-02-04 Time 17:04 Sent To  
Notes
2010-02-04 17:07:53**********************EXPEDITED*******************
 2ND RUN
 GAVE TO KEN STEVENS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-02-04 Cont ID  
Sent By lmartine Date 2010-02-04 Time 17:03 Rev Time 0.00
Received By lmartine Date 2010-01-27 Time 16:18 Sent To  
Notes
2010-01-27 16:29:28******************EXPEDITED*********************
 R--3

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2010-02-09 Cont ID  
Sent By jwitmer Date 2010-02-09 Time 11:55 Rev Time 0.00
Received By jwitmer Date 2010-02-09 Time 11:55 Sent To  
Notes
2010-02-09 11:56:15PR# 2010-0204-181 ($977.49)

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-02-02 Cont ID  
Sent By jwitmer Date 2010-02-02 Time 16:12 Rev Time 0.00
Received By jwitmer Date 2010-02-02 Time 16:12 Sent To  
Notes
2010-02-02 16:13:13BEFORE A REVISIONFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-02-08 Cont ID  
Sent By kstevens Date 2010-02-08 Time 09:29 Rev Time 0.00
Received By kstevens Date 2010-02-08 Time 09:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2010-02-01 Cont ID  
Sent By kstevens Date 2010-02-01 Time 09:46 Rev Time 0.00
Received By kstevens Date 2010-02-01 Time 09:46 Sent To  
Notes
2010-02-01 10:24:02DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 RESIDENTIAL
 FBC-2007 EXISTING BUILDING
 FBC-2007 CHAPTER 1
  
 1. SHT A2-06 MORE INFORMATION REQUIRED. SECTION
 106.1.1. SUBMIT THE FOLLOWING:
  
 A. INDICATE THE TOTAL SQUARE FOOTAGE BEING DRAINED BY
 THE EXISTING ROOF DRAIN. SHOW TOTAL SQUARE FOOTAGE OF
 EXISTING ROOF SECTION WITH THE ROOF DRAIN, THE SQUARE
 FOOTAGE OF THE NEW ROOF DRAINING ON TO THE ROOF, ONE
 HALF THE ADDITIONAL SQUARE FOOTAGE OF THE VERTICAL
 WALLS FOR THE NEW ROOF, THE SQUARE FOOT AREA OF THE HIP
 ROOF THAT DRAINS ONTO THE ROOF & THE SQUARE FOOTAGE OF
 THE CHANGE IN LEVEL INDICATED (PLEASE CLARIFY).
 SECTIONS 1101.2, 1106.4, 1107.1, 1107.2 & 1107.3 AS
 WELL AS TABLES 1106.2, 1106.3 & 1106.2.
  
 B. SUBMIT A DETAIL FOR THE SCUPPER ON THE NEW ROOF.
 INDICATE HEIGHT, WIDTH, LENGTH. TABLE 1106.7.
  
 C. INDICATE THE SIZE OF THE EXISTING ROOF DRAIN AS WELL
 AS THE SIZE OF THE VERTICAL & HORIZONTAL CONDUCTOR &
 LEADER. TABLES 1106.2, 1106.3 & 1106.7.
  
 D. INDICATE THE SIZE OF THE EXISTING OVERFLOW SCUPPERS
 SERVING THE EXISTING ROOF WITH THE ROOF DRAIN. TABLE
 1106.1.
  
 E. FOR THE NEW ROOF, A SEPARATE SECONDARY ROOF DRAIN IS
 REQUIRED PER SECTIONS 1107.1 & 1107.2. PLEASE SUBMIT A
 DETAIL AND SHOW THE LOCATION OF THE SECONDARY ROOF
 DRAIN. ALSO SEE SECTION R903.4.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-02-01 Cont ID  
Sent By kstevens Date 2010-02-01 Time 09:45 Rev Time 0.00
Received By kstevens Date 2010-01-28 Time 19:05 Sent To  
Notes
2010-02-01 09:46:04REVISIONS OK -- SHTS P-01 & P2-01.

Review Stop Z ZONING
Rev No 2 Status P Date 2010-02-04 Cont ID  
Sent By eschneid Date 2010-02-04 Time 09:42 Rev Time 0.50
Received By eschneid Date 2010-02-04 Time 09:42 Sent To  
Notes
2010-02-04 09:48:27PASSED W/PROVISO
  
 1) PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR. PAPA SHOWS THE IMPROVEMENT VALUE AS $734,432
 AND THE PERMIT VALUES FOR PHASE I AND PHASE II TOTALS
 $443,500 (GREATER THAN 50%).
  
 2) PRIOR TO THE CERTIFICATE OF OCCUPANCY (C.O.), A
 LANDSCAPE PERMIT SHOWING COMPLIANCE WITH SECTIONS
 94-442 AND 94-445 OF THE ZLDR IS REQUIRED TO BE
 SUBMITTED TO THE CONSTRUCTION SERVICES DEPARTMENT AND
 THE LANDSCAPE SHALL BE INSTALLED AND RECEIVE A FINAL
 (502) INSPECTION APPROVAL. NOTE: IT APPEARS FROM THE
 AERIAL OF THE SITE THAT THERE ARE PALM TREES BEING
 REMOVED IN THE LOCATION OF THE NEW LOGGIA, THE PLANS
 INDICATE THERE IS NEW LANDSCAPE BEING INSTALLED, AND
 LANDSCAPE IS BEING REMOVED FOR THE INSTALLATION OF THE
 GENERATOR.
  
 3) THE GENERATOR REQUIRES A SEPARATE PERMIT. THE
 GENERATOR SHALL BE SCREENED WITH LANDSCAPE FROM THE
 PROPERTY TO THE NORTH.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-02-03 Cont ID  
Sent By eschneid Date 2010-02-03 Time 14:40 Rev Time 0.50
Received By eschneid Date 2010-02-03 Time 14:40 Sent To  
Notes
2010-02-03 14:57:05FAILED
  
 1) PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (LISTED AS "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR. PAPA SHOWS THE IMPROVEMENT VALUE AS $734,432
 AND THE PERMIT VALUES FOR PHASE I AND PHASE II TOTALS
 $443,500 (GREATER THAN 50%).
  
 2) PRIOR TO THE ZONING DIVISION APPROVING THIS PERMIT A
 LANDSCAPE, A LANDSCAPE PERMIT SHOWING COMPLIANCE WITH
 SECTIONS 94-442 AND 94-445 OF THE ZLDR IS REQUIRED TO
 BE SUBMITTED TO THE CONSTRUCTION SERVICES DEPARTMENT.
 NOTE: IT APPREARS FROM THE AERIAL OF THE SITE THAT
 THERE ARE PALM TREES BEING REMOVED IN THE LOCATION OF
 THE NEW LOGGIA, THE PLANS INDICATE THERE IS NEW
 LANDSCAPE BEING INSTALLED, AND LANDSCAPE IS BEING
 REMOVED FOR THE INSTALLATION OF THE GENERATOR.
  
 3) THE GENERATOR REQUIRES A SEPARATE PERMIT. THE
 GENERATOR SHALL BE SCREENED WITH LANDSCAPE FROM THE
 PROPERTY TO THE NORTH.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.