FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2010-02-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2010-02-03 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2010-02-03 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2010-02-03 15:29:14 | *****PROVISO***** | | | | | | | | | READY FOR PERMIT ISSUANSE; PLAN SHEET FA-1 (1OF 1) | | | STAMPED, INITIALED, AND DATED WITH THE FOLLOWING BELOW | | | PROVISO: | | | | | | REVISED PLANS NEEDED (PRIOR TO OBTAINING A FIRE FINAL - | | | 302 ) DEPICTING THE FOLLOWING: | | | | | | 1. THE 2002 EDITION OF NFPA 72 SHALL BE REFERENCED (NOT | | | 1999) IN NOTE #4. | | | 2. A SMOKE DETECTOR SHALL BE INSTALLED IN THE VICINITY | | | OF THE FIRE ALARM ANNUNCIATOR LOCATED IN THE RECEPTION | | | AREA. THE ADDITION OF THIS DEVICE SHALL BE REFLECTED IN | | | THE FLOOR PLAN, RISER DIAGRAM, BATTERY CALCS, ETC. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|
|