Review Stop G GAS REVIEW
Rev No 2 Status P Date 2010-02-17 Cont ID  
Sent By kstevens Date 2010-02-17 Time 08:39 Rev Time 0.00
Received By kstevens Date 2010-02-17 Time 08:39 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2010-02-03 Cont ID  
Sent By kstevens Date 2010-02-03 Time 10:48 Rev Time 0.00
Received By kstevens Date 2010-02-02 Time 16:52 Sent To  
Notes
2010-02-03 11:08:59REVISION DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. SEPARATE GAS PERMIT REQUIRED. THE VALUE FOR THE
 MATERIAL, LABOR, DESIGN, APPLIANCES ETC. SHALL BE
 INDICATED ON THE APPLICATION FOR PERMIT.
  
 1. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU
 G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8). -- THE
 CHAR-BROILER IS NOT INDICATED IN THE GAS CALCULATION ON
 SHT 3.1P.
  
 2. SHT 3.1P GAS ISOMETRIC RISER DIAGRAM. PLEASE
 INDICATE THE LOCATION OF THE STEAM TABLE.
  
 3. THE SPECIFICATION SHEET FOR THE GAS REGULATOR DOES
 NOT SHOW A MODEL WITH THE CAPACITY FOR ALL APPLIANCES.
 MAXIMUM SHOWN IS 1,000,000 FOR MODEL 325-7L. THE BTU
 LOAD DOWNSTREAM OF THE REGULATOR IS SHOWN AS 1, 136,000
 MBTU WITHOUT ADDING THE CHAR-BROILER. PLEASE SUBMIT
 REGULATOR SPECIFICATION SHEETS FOR AN APPROVED
 REGULATOR. SECTION 410.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-02-03 Cont ID  
Sent By kstevens Date 2010-02-03 Time 13:19 Rev Time 0.00
Received By kstevens Date 2010-01-28 Time 10:25 Sent To  
Notes
2010-01-28 10:25:40SENT TO PLUMBING, (GAS).