Plan Review Details - Permit 10010448
Plan Review Stops For Permit 10010448
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-02-25 Cont ID  
Sent By jgomez Date 2010-02-25 Time 11:25 Rev Time 0.00
Received By jgomez Date 2010-02-25 Time 10:06 Sent To  
Notes
2010-02-25 11:31:22BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- RESUBMIT ENERGY CALCULATIONS USING CORRECT UPDATED
 FORM REQUIRED ON 2009 REVISIONS.
  
 2- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 BALCONY RAILING TO SHOW COMPLIANCE WITH TABLE R301.5
 AND SEC. R312 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ROOF
 DRAINAGE AND OVERFLOW SCUPPERS AS REQUIRED BY SECTIONS
 R903.4 AND R903.4.1 OF 2007 FLORIDA RESIDENTIAL CODE.
 SPECIFY ALL SIZES AND SPECIFIC LOCATION.
  
 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 BALCONY FLOOR ASSEMBLY. SPECIFY FINISH FLOORING AND
 COMPLETE SPECIFICATIONS TO SHOW COMPLIANCE WITH THE
 WIND LOADS OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL
 CODE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-02-08 Cont ID  
Sent By jgomez Date 2010-02-08 Time 10:02 Rev Time 0.00
Received By jgomez Date 2010-02-08 Time 10:02 Sent To  
Notes
2010-02-08 10:12:05RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS. SEC. N1100.2 OF 2007
 FLORIDA RESIDENTIAL CODE. PLEASE MAKE SURE CORRECT
 UPDATED FORM IS PROVIDED (SEE 2009 REVISIONS) AND MAKE
 SURE ALL THE INFORMATION IS COMPLETED AND FORMS ARE
 SIGNED AND DATED BY ALL THE REQUIRED PERSONS.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT
 IF FEES ARE DUE.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 4- SHEET A.01: UPDATE BUILDING INFORMATION. CURRENT
 CODE IS THE 2007 FLORIDA RESIDENTIAL CODE NOT 2004. AND
 REVISE CODE SECTION CITED ON THE WIND LOAD INFORMATION.
 SEC. 1606 IS NOT FOR WIND LOAD, BUT FOR DEAD LOAD.
 REVISE AS REQUIRED.
  
 5- SHEET A.02: SPECIFY HOW ARE THE LEDGERS SPECIFIED ON
 THE SECOND FLOOR AND ROOF FRAMING PLANS ATTACHED TO THE
 STRUCTURE TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL
 CODE. SPECIFY ALL CONNECTORS.
  
 6- SHEET A.03:
 A) REVISE THICKNESS OF STUCCO . MIN. 7/8" THICKNESS
 REQUIRED. SEE TABLE R702.1(1) OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 B) SPECIFY 2 LAYERS OF WATER RESISTANT BARRIER AS
 REQUIRED BY SEC. R703.6.3 OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 BALCONY RAILING TO SHOW COMPLIANCE WITH TABLE R301.5
 AND SEC. R312 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ROOF
 DRAINAGE AND OVERFLOW SCUPPERS AS REQUIRED BY SECTIONS
 R903.4 AND R903.4.1 OF 2007 FLORIDA RESIDENTIAL CODE.
 SPECIFY ALL SIZES AND SPECIFIC LOCATION.
  
 E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 BALCONY FLOOR ASSEMBLY. SPECIFY FINISH FLOORING AND
 COMPLETE SPECIFICATIONS TO SHOW COMPLIANCE WITH THE
 WIND LOADS OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 F) PROVIDE COMPLETE SPECIFICATIONS FOR ROOF SHEATHING
 FASTENING TO SHOW COMPLIANCEWITH SEC. R803.2.3.1 OF
 2007 FLORIDA RESIDENTIAL CODE. NEED TO SPECIFY RING
 SHANK NAILS AND NAILING SPACING IS 4" O.C. IN ROOF ZONE
 3.
  
 7- FLAT ROOF PRODUCT APPROVAL SUBMITTED:
 A) MISSING THE TECHNICAL REPORT SHOWING SPECIFIC
 APPROVED ASSEMBLY TO BE INSTALLED AND SPECIFIC BASE
 SHEET FASTENING OPTION. ALSO, NEED TO PROVIDE THE
 SIGNED AND SEALED RAS 117 CALCULATIONS FOR THE NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS TO MEET THE
 DESIGN PRESSURES OF SEC. R301 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 8- OWES PERMIT FEE BALANCE OF $1043.50.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-02-18 Cont ID  
Sent By btrobaug Date 2010-02-18 Time 12:28 Rev Time 0.00
Received By btrobaug Date 2010-02-18 Time 11:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-01 Cont ID  
Sent By btrobaug Date 2010-02-01 Time 13:58 Rev Time 0.00
Received By btrobaug Date 2010-02-01 Time 12:51 Sent To  
Notes
2010-02-01 13:58:45 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THERE IS NOT ENOUGH INFORMATION ON THE PLANS TO
 DETERMINE COMPLIANCE WITH 210. OF TTHE 2008 NEC. SHOW
 ALL RECEPTACLE LOCATIONS ON THE PLANS.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-02-16 Cont ID  
Sent By lmartine Date 2010-02-11 Time 14:31 Rev Time 0.00
Received By lmartine Date 2010-02-11 Time 14:30 Sent To  
Notes
2010-02-16 14:37:17R--13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-02-08 Cont ID  
Sent By jgomez Date 2010-02-08 Time 14:16 Rev Time 0.00
Received By jgomez Date 2010-01-25 Time 13:30 Sent To  
Notes
2010-01-26 13:38:53R--4

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2010-02-25 Cont ID  
Sent By jgomez Date 2010-02-25 Time 10:24 Rev Time 0.00
Received By jgomez Date 2010-02-25 Time 10:06 Sent To  
Notes
2010-02-25 10:26:39NO FEES. PALM BEACH COUNTY STAMP DATED 2/9/10 ON OLD
 DRAWING A.01.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-02-08 Cont ID  
Sent By jgomez Date 2010-02-08 Time 09:56 Rev Time 0.00
Received By jgomez Date 2010-02-08 Time 08:43 Sent To  
Notes
2010-02-08 09:58:18BRING PLANS TO PALM BEACH COUNTY (2300 N JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-02-08 Cont ID  
Sent By jgomez Date 2010-02-08 Time 10:01 Rev Time 0.00
Received By jgomez Date 2010-02-08 Time 10:01 Sent To  
Notes
2010-02-08 10:01:54NO PLANS. NO A/C WORK.

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-03-01 Cont ID  
Sent By kstevens Date 2010-03-01 Time 08:33 Rev Time 0.00
Received By kstevens Date 2010-03-01 Time 08:33 Sent To  
Notes
2010-03-01 08:34:52NEW SHEET -- SECOND FLOOR TOILET FIXTURES NOT APPROVED
 TO DRAIN THRU THE VENT FOR THE FIRST FLOOR. P3107.3.

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-01-27 Cont ID  
Sent By kstevens Date 2010-01-27 Time 15:35 Rev Time 0.00
Received By kstevens Date 2010-01-27 Time 15:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2010-03-01 Cont ID  
Sent By jroach Date 2010-03-01 Time 15:39 Rev Time 0.00
Received By jroach Date 2010-03-01 Time 15:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-02-01 Cont ID  
Sent By jroach Date 2010-02-01 Time 17:31 Rev Time 0.00
Received By jroach Date 2010-02-01 Time 17:31 Sent To  
Notes
2010-02-01 17:40:28ZONING PLAN REVIEW
  
 PERMIT NO.: 10010448
 ADDRESS: 624 SUNSET AVENUE
 CONTRACTOR/CONTACT: G.A. KUZNIAR CONSTRUCTION INC.
 TELEPHONE NO.: 561.596.8155
 SCOPE OF REVIEW: 2ND STORY ADDITION, RELOCATE KITCHEN,
 RELOCATE EXISTING BATH, WINDOWS, AND DOORS.
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1) TWO (2) COPIES OF A CURRENT AND ACCURATE SITE PLANS
 SHALL BE PROVIDED INDICATING ALL EXISTING IMPROVEMENTS
 ON THE PROPERTY.
  
 2) TWO (2) COPIES OF A SITE PLAN SHALL BE PROVIDED
 INDICATING THE LOCATION OF THE EXISTING AND PROPOSED
 IMPROVEMENTS IN RELATIONS TO PROPERTY LINES, ETC.
 DIMENSIONS SHALL BE PROVIDED FOR ALL SETBACKS TO ALL
 EXISTING AND PROPOSED STRUCTURES, MECHANICAL EQUIPMENT,
 ETC.
  
 3) OVERALL HEIGHT OF THE STRUCTURE SHALL BE NOTED ON
 THE ELEVATIONS. OVERALL HEIGHT IS MEASURED FROM GRADE
 (NO FINISHED FLOOR), AND SHALL BE TO THE ROOF DECK ON A
 FLAT ROOF.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 PLANNING AND ZONING DEPARTMENT
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved