Plan Review Details - Permit 10010381
Plan Review Stops For Permit 10010381
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-03-02 Cont ID  
Sent By shill Date 2010-03-01 Time 17:32 Rev Time 0.00
Received By shill Date 2010-03-01 Time 17:32 Sent To  
Notes
2010-03-01 17:49:37THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING PROVISO:
 UL DETAILS (HW AND CL, SEE SHEET A3.1) TO BE PROVIDED
 AT INSPECTION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-01-26 Cont ID  
Sent By shill Date 2010-01-26 Time 18:15 Rev Time 0.00
Received By shill Date 2010-01-26 Time 18:15 Sent To  
Notes
2010-01-26 18:51:50****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. TENANT SEPARATION WALL IS TO MAINTAIN 1 HOUR RATING,
 FBC 708.1(7), 708.3, 708.4. WALL DETAIL W3 IS SPECIFIED
 FOR DOOR INFILL. PLEASE REVISE TO SPECIFY A 1 HOUR WALL
 INFILL DETAIL.
  
 2. PROVIDE OCCUPANT LOAD FOR EACH TENANT SPACE, FBC
 1004.1.
  
 3. DOOR 10 (LOBBY 200) SWINGS AGAINST THE PATH OF EXIT
 TRAVEL, FBC1008.1.2. IT IS NOT CLEAR HOW MANY OCCUPANTS
 THIS EXIT SERVES, BUT PLEASE NOTE THAT THIS IS A
 PRIMARY EXIT AS NOTED ON THE PLAN.
  
 4. ABOVE THE TEXT "LIFE SAFETY PLAN" THERE IS A DASHED
 LINE (INVERTED "U"); PLEASE LABEL AS IT IS UNCLEAR WHAT
 THIS GRAPHIC REPRESENTS.
  
 5. DOOR 11 AT VESTIBULE 207, SHOW 18??? CLEARANCE ON
 PULL SIDE PER FBC FIGURE 11-25.
  
 6. PROVISO ITEM - UL DETAILS (HW AND CL, SEE SHEET
 A3.1) TO BE PROVIDED AT INSPECTION.
  
 7. BATHROOMS ARE A COMMON AREA (TENANCY IN COMMON) AND
 REQUIRE TENANT SEPARATION, FBC 708.1(7), PENETRATIONS
 TO COMPLY WITH FBC712.
  
 8. DETAIL 04 A3.1, BREAK ROOM SINK TO BE ACCESSIBLE,
 FBC 11-4.24.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-03-02 Cont ID  
Sent By dpalmer Date 2010-03-02 Time 16:55 Rev Time 0.00
Received By dpalmer Date 2010-03-02 Time 16:55 Sent To  
Notes
2010-03-02 16:55:19** PROVISO/REDLINED **
  
  
 1) NOTE: PLANS INDICATE 2005 NEC/NFPA-70. REDLINED AND
 STAMPED FOR 2008 NEC.
  
 2) NOTE: ALL DEVICE LOCATIONS FOR HORN/STROBES, PULL
 STATIONS ETC SHALL BE VERIFIED AND SHOWN ON PLANS.
 THESE LOCATIONS ARE REQUIRED TO COMPLY WITH CHAPTER 11
 OF THE FBC.
 11-4.28.1,.2 AND .3. TENANT AREAS WILL BE REQUIRED TO
 SHOW ALL LOCATIONS AND MINIMUM LEVELS. RESPONSE
 MENTIONS DEVICES ALREADY EXISTS HOWEVER BASED ON THE
 SUBMITTED PLANS, NOT ALL ARE SHOWN AS EXISTING. SEE
 AREA 126 FOR EXAMPLE WHICH INDICATES A NEW DEVICE YET
 COMPLIANCE FOR ADA IS NOT SHOWN. THE LOCATIONS OF
 DEVICES IN THIS SAME AREA FOR ADA ARE ALSO NOT MET FOR
 MINIMUM COMPLIANCE.
  
 3) NOTE: REDLINED PLANS: WIRING METHODS IN NEC 645 ARE
 NOT PERMITTED IN ROOM 205.
  
 4) NOTE: LOW VOLTAGE SYSTEMS SUCH AS PHONE AND DATA ARE
 REQUIRED TO BE UNDER SEPARATE PERMIT AND PLANS. THESE
 PLANS DO NOT INDICATE LOW VOLTAGE THEREFORE LV LAYOUT
 PLANS WILL BE REQUIRED WHEN SUBMITTING FOR PERMIT.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-02 Cont ID  
Sent By dpalmer Date 2010-02-02 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2010-02-02 Time 14:39 Sent To  
Notes
2010-02-02 14:39:29DENIED*
  
  
 1) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS SUBMITTED
 AS REQUIRED PER 13-415.AB.5.
 PLEASE BE SURE THE FIXTURE LEGEND IS SUBMITTED FOR NEW
 FIXTURES AND INFORMATION ON OTHERS.
 PLANS HAVE AN *EX* NEXT TO A COUPLE OF FIXTURES HOWEVER
 SINCE THE SYMBOL LEGEND DOES NOT INDICATE WHAT THIS IS,
 IT IS NOT POSSIBLE TO KNOW EXACTLY WHAT THESE ARE.
 EVEN WHEN NOT MEETING THE DEFINITIONS OF A RENOVATION,
 PRESCRIPTIVE REQUIREMENTS MUST BE MET. 13-400.B.0.4
  
 2) NOTE: LIGHTING CONTROLS IN SOME AREAS NOT MEETING
 FBC 13-415.AB.1.1,.1.2. PLEASE SEE SEPARATE SPACE
 REQUIREMENTS. ROOMS ARE NOT IDENTIFIED ON ELECTRICAL
 PLANS SO DESIGNATIONS ON ARCHITECTURAL SHEETS ARE BEING
 USED.
 PLEASE SEE ROOMS 100, 206, 211 ETC
  
 3) NOTE: PANEL SCHEDULES AND CIRCUITING TO BE COMPLETE
 TO SPECIFIC ROOMS AND AREAS IN WHICH THEY FEED. 408.4.
 ( MAY BE ALPHA OR NUMERIC DESIGNATIONS.)
  
 4) NOTE: PLEASE COORDINATE RISER DIAGRAM OR PANEL
 INFORMATION FOR NEW PANEL FEED SUBMITTED.
 RISER INDICATES NEW PANEL AS 60AMP HOWEVER PANEL ON
 SHEET E-2 STATES THIS AS A 200AMP MCB PANEL?
 3/0 AWG WILL NOT FIT INTO 60AMP LUGS.
 215.5, 310.16, 240.4 ETC. NO INFORMATION SUBMITTED SO
 REVIEW OF NEW PANEL FEED CAN NOT BE DONE.
  
 5) NOTE: LOADS ON NEW PANEL ARE ACTUALLY BLANK. THERE
 IS NO LOAD INFORMATION FOR THIS PANEL OR ON THE
 PANELS/SERVICE EQUIPMENT WHICH FEEDS NEW PANEL. THIS
 NEEDS TO BE COMPLETED FOR LOADS ON PANEL K AND A1.
 PLEASE SEE 220.12,220.14,220.42, 220.44,220.87 ETC
 PLEASE ALSO SEE 215.3,230.42, 422.13 FOR CONTINUOUS
 LOADS.
 ** SECTIONS GIVEN IN GENERAL AS NO LOADS, LOAD
 CALCULATIONS WERE SUBMITTED FOR PANELS BEING AFFECT.
 THE LOAD SHOWN FOR SERVICE IS ONLY PART OF THE
 INFORMATION NEEDED.
  
 6) NOTE: NO INFORMATION SHOWN FOR ADA COMPLIANCE FOR
 FBC 11-4.1,.2 AND .3. SHOW LOCATIONS, HEIGHTS AND
 LEVELS OF ALL REQUIRED DEVICES. PLEASE COMPLETE LEGEND
 FOR MINIMUM REQUIRED DEVICES.
  
 7) NOTE: PLEASE SEE FBC 1006.1.2, NFPA-101
 7.8.1.3,7.9.1.2, .2.2 FOR REQUIRED EMERGENCY EGRESS
 LIGHTS. NONE SHOWN ON ELECTRICAL PLANS. PLEASE ALSO SEE
 NEC 700.12F FOR CIRCUITING REQUIREMENTS.
 A FEW ARE LOCATED ON E-1 HOWEVER NOT ALL REQUIRED.
  
 8) NOTE: PLEASE COMPLETED PLANS FOR LIGHTING AND FAN
 CONTROLS IN BATHROOM AREAS. SEE NOTES ABOVE WITH
 RESPECT TO FBC CHAPTER 13 FOR LIGHTING CONTROLS AND
 ALSO MINIMUM REQUIRED FOR NORMAL AND EMERGENCY EGRESS.
  
 9) NOTE: PER PANEL SCHEDULE ONE OF THE ROOMS WILL BE A
 NEW SERVER ROOM. IF THIS IS *NOT* AN IT ROOM PER 645.4
 (1-5) THEN PLEASE PLACE NOTE ON PLANS WHICH WILL *NOT*
 PERMIT THE WIRING METHODS PERMITTED IN NEC 645. THE
 WORDING TO THAT AFFECT MAY BE ADJUSTED.
  
 ** FYI: IT PERSONNEL FOR OWNER MAY WANT TO BE CONSULTED
 WITH DUE THE MORE STRINGENT WIRING METHODS REQUIRED
 WHEN NOT AN IT ROOM.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-03-08 Cont ID  
Sent By mawillia Date 2010-03-08 Time 13:56 Rev Time 0.00
Received By mawillia Date 2010-03-08 Time 13:29 Sent To  
Notes
2010-03-08 13:56:16*****APPROVED******
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS AD1.1, LS1.1, A1.1, A2.1, E1,
 AND E2 WERE STAMPED, INITIALED, AND DATED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-02-11 Cont ID  
Sent By mawillia Date 2010-02-11 Time 15:08 Rev Time 0.00
Received By mawillia Date 2010-02-11 Time 10:36 Sent To  
Notes
2010-02-11 10:50:28*****DENIED******
  
  
 1. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 2. DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL
 WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD OF
 50 OR MORE, EXCEPT UNDER THE CONDITIONS SPECIFIED IN
 7.2.1.4. (SEE BUILDING EXAMINER'S COMMENT # THREE).
  
 3. WHAT ARE THE DASHED LINES BEGINNING FROM THE
 EXTERIOR OF THE DOUBLE EXIT DOORS EXTENDING INTO THE
 LOBBY (ROOM 200) AROUND AND BACK OUT OF THE BUILDING AS
 SHOWN ON LS1.1 SHEET?
  
 4. AS SHOWN ON SHEET LS1.1, THE NEW PROPOSED WALL WILL
 DENY TENANT SPACE #100 ACCESS TO THE EXISTING FIRE
 ALARM PANEL IN THE SERVER ROOM (ROOM 205) . PLEASE
 EXPLAIN.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-02-25 Cont ID  
Sent By kstevens Date 2010-02-25 Time 08:38 Rev Time 0.00
Received By kstevens Date 2010-02-25 Time 08:38 Sent To  
Notes
2010-02-25 08:39:14SENT TO C-17. -- UNABLE TO FIND
 PLANS/APPLICATION/EXPEDITED FORM ETC IN "F" SMALL
 PLANS. KSTEVENS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-02-11 Cont ID  
Sent By mawillia Date 2010-02-11 Time 10:36 Rev Time 0.00
Received By mawillia Date 2010-01-21 Time 16:26 Sent To  
Notes
2010-01-21 16:27:02********EXPEDITED***********
  
 C 36
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-03-01 Cont ID  
Sent By shill Date 2010-03-01 Time 17:49 Rev Time 0.00
Received By shill Date 2010-03-01 Time 17:49 Sent To  
Notes
2010-03-01 17:50:07INTERIOR RENOVATION ONLY (NO INCREASE)
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-03-04 Cont ID  
Sent By rregueir Date 2010-03-04 Time 20:47 Rev Time 0.00
Received By rregueir Date 2010-03-04 Time 20:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-01-26 Cont ID  
Sent By rregueir Date 2010-01-26 Time 20:43 Rev Time 0.00
Received By rregueir Date 2010-01-26 Time 20:22 Sent To  
Notes
2010-01-26 20:43:34REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THE BUILDING PLAN REVIEW INDICATES THAT THERE ARE
 REQUIRED RATED TENANT SEPARATION WALLS WHICH ARE NOT
 SHOWN AS SUCH ON PLANS. SOME OF THE AFFECTED WALLS ARE
 SHOWN AS BEING PENETRATED BY DUCTS WITHOUT PROTECTION.
 COORDINATE WITH CORRECTED ARCHITECTURAL PLASN TO SHOW
 THE DUCT PENETRATIONS OF ALL RATED WALLS PROTECTED IN
 ACCORDANCE WITH FBC-M 607.5 AND 607.8.
  
 2. M1 FLOOR PLAN SHOWS NEW EXHAUST FAN IN NEW PORTION
 OF WOMEN'S RESTROOM. NO INFORMATION WAS PROVIDED
 REGARDING THIS FAN. PROVIDE EQUIPMENT SCHEDULE AND SHOW
 REQUIRED RATINGS AND CFM OF THIS FAN AS WELL AS THE CFM
 OF THE EXISTING EXHAUST SYSTEM TO DEMONSTRATE
 COMPLIANCE WITH FBC-EB 709.1 AND FBC-M TABLE 403.3
  
 3. THERE ARE SEVERAL OTHER RECONFIGURED SPACES IN THE
 WORK AREA. PROVIDE SPACE-BY-SPACE VENTILATION
 CALCULATIONS FOR ALL RECONFIGURED SPACES IN ACCORDANCE
 WITH FBC-EB 709.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-03-03 Cont ID  
Sent By kstevens Date 2010-03-03 Time 07:54 Rev Time 0.00
Received By kstevens Date 2010-03-03 Time 07:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-01-28 Cont ID  
Sent By kstevens Date 2010-01-28 Time 18:24 Rev Time 0.00
Received By kstevens Date 2010-01-28 Time 18:24 Sent To  
Notes
2010-01-28 18:34:53DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
  
 1. SHT A3.1 DETAIL #10 SHOW THE CLEAR FLOOR SPACE FOR
 THE DRINKING FOUNTAIN. (FORWARD APPROACH REQUIRED).
 SECTION 11-4.15.5.
  
 2. SHT A3.1 DETAIL #10 SHOW THE CLEAR FLOOR SPACE FOR
 THE W/C. SECTION 11-4.16.2.
  
 3. SHT A3.1 DETAIL #10 THE ACCESSIBLE TOILET STALLS DO
 NOT COMPLY WITH FIGURE 11-30(E). SECTION
 11-4.1.6)1)(B).
  
 4. SHT A3.1 DETAIL #10 SHOW THE CLEAR FLOOR SPACE FOR
 THE URINAL. SECTION 11-4.18.3.
  
 5. SHT A3.1 DETAIL #10 SHOW THE CLEAR FLOOR SPACE FOR
 THE LAV. SECTION 11-4.19.3.
  
 6. SHT A3.1 DETAIL #4 SHOW THE KNEE CLEARANCE PER
 SECTION 11-4.24.3, THE CLEAR FLOOR SPACE PER 11-4.24.5
 (CABINET DOORS NOT APPROVED, DELETE) & EXPOSED PIPES &
 SURFACES PER SECTION 11-4.24.6.
  
 7. SHT M1 SHOW ALL PIPE SIZES. TABLE 710.1(1).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2010-01-30 Cont ID  
Sent By astelly Date 2010-01-30 Time 10:23 Rev Time 0.00
Received By astelly Date 2010-01-30 Time 10:23 Sent To  
Notes
***NONE***