Plan Review Details - Permit 10010321
Plan Review Stops For Permit 10010321
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-01-28 Cont ID  
Sent By jwitmer Date 2010-01-28 Time 15:38 Rev Time 2.00
Received By jwitmer Date 2010-01-28 Time 15:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-03-30 Cont ID  
Sent By dwise Date 2010-03-30 Time 20:53 Rev Time 0.00
Received By dwise Date 2010-03-30 Time 20:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-03 Cont ID  
Sent By dpalmer Date 2010-02-03 Time 15:12 Rev Time 0.00
Received By dpalmer Date 2010-02-02 Time 16:38 Sent To  
Notes
2010-02-03 15:12:36*DENIED*
  
  
 1) NOTE: SHEET 8 OF 10 CONTAINS CODES REFERENCES WHICH
 ARE NO LONGER ADOPTED WITH THE STATE OF FLORIDA. THE
 FLORIDA FIRE PREVENTION CODE AND LIFE SAFETY CODES WERE
 CHANGED DECEMBER 31ST, 2008. THE FLORIDA BUILDING CODES
 FOR FUEL GAS AND PLUMBING AS NOTED WERE REVISED ON
 MARCH 1ST 2009 AND THE NFPA-70 WAS REVISED OCTOBER 1ST,
 2009.
 PLEASE BE SURE TO ADJUST ALL OF THE FOLLOWING RELEVANT
 CODES AS APPLICABLE TO PROJECT.
  
 2008 NFPA-70
 2005 NFPA-110
 2006 NFPA -101
 2007 FLORIDA FIRE PREVENTION CODE
 2007 FLORIDA BUILDING CODE WITH 2009 SUPPLEMENTS.
  
 ** THIS IS REQUIRED FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWERS.
  
 2) NOTE: ENGINEERING FIRM MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER ON TITLE BLOCKS. PLANS CONTAIN A
 NOTE THAT THE NUMBER IS TO BE PROVIDED HOWEVER
 LICENSURE IN THE STATE OF FLORIDA IS REQUIRED AT THIS
 TIME.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002,
 FLORIDA STATUTES 471.023.
 ** THIS IS REQUIRED ON ALL PLANS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADE.
 ** AS IT MAY TAKE SOME TIME FOR CERTIFICATE OF
 AUTHORIZATION NUMBER THERE ARE OPTIONS HOWEVER PLEASE
 CALL TO GO OVER.
  
 3) NOTE: PLEASE SUBMIT TWO COPIES OF THE MANUFACTURES
 SPECS/CUT SHEETS FOR GENERATOR, ATS AND FUEL TANK.
 ONE SET SUBMITTED ONLY. SEE COMMENTS FROM OTHER TRADES
 FOR REVIEW STAMPS ETC.
 90.7,110.3,701.6, 701.7.
  
 4) NOTE: COLOR CODING FOR CONDUCTORS SHALL BE BROWN,
 PURPLE, YELLOW FOR 277/480V SYSTEMS. SPECIFICATION
 SHEETS INDICATE ORANGE FOR B HASE AS THIS IS NOT AN
 OPEN DELTA HIGH-LEG SYSTEM PLEASE ADJUST COLOR CODING.
 90.4.
 EXISTING SYSTEM WIRING WITHIN THIS MUNICIPALITY AND
 COUNTY ARE BASED ON PREVIOUS TECHNICAL AMENDMENTS. IN
 KEEPING WITH THE SAFETY ASPECT OF IDENTIFICATION OF
 SUCH SYSTEMS THIS JURISDICTION WILL REQUIRE THE ABOVE.
  
 5) NOTE: PLANS MENTION ON SHEET 3 OF 10 TO REMOVE
 CONCRETE, GRIND ETC. THIS WILL CREATE CONTAMINATES
 WITHIN THE ELECTRICAL EQUIPMENT ENCLOSURES. PLEASE BE
 SURE TO NOTE THAT ALL EQUIPMENT SHALL BE COVERED OR
 PROTECTED.
 PLEASE KNOW THAT DUST, DETERIORATING AGENTS AND
 MOISTURE MITIGATION NEEDS TO BE ADDRESSED.
  
 6) NOTE: PLEASE SEE 225.31-225.39. A DISCONNECTING
 MEANS IS REQUIRED FOR FEEDERS COMING INTO BUILDING
 UNLESS MEETING THE EXCEPTIONS IN 701.11B5. THE
 DISCONNECTING MEANS AT THE GENERATOR MAY BE USED WHEN
 MEETING BOTH WITHIN SIGHT ( 50FT) AND READILY
 ACCESSIBLE. THE GENERATOR IS WITHIN SIGHT HOWEVER THE
 GENERATOR DISCONNECTING MEANS IS NOT READILY
 ACCESSIBLE.
 PLEASE KNOW THAT THE *MUSHROOM* TYPE PUSH/PULL BUTTON
 AT THE BUILDING DOES NOT MEET SECTIONS ABOVE AS THE
 DISCONNECTING MEANS IS REQUIRED TO BE RATED FOR THE
 LOAD SERVED.225.39.
 THE DISCONNECT AT THE BUILDING DOES NOT REQUIRE OVER
 CURRENT PROTECTION IF THE OVER CURRENT PROTECTION IS
 PROVIDED AT THE GENERATOR. IT ONLY REQUIRES THIS TO BE
 A DISCONNECT.
  
 7) NOTE: ALL PULL BOX DIMENSIONS WILL BE REQUIRED TO BE
 LOCATED ON PLANS SIZED IN ACCORDANCE WITH MINIMUM NEC
 REQUIREMENTS.
 PLEASE SEE CHANGES IN 2008 NEC. 314.28
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-03-29 Cont ID  
Sent By mcarsill Date 2010-03-29 Time 11:09 Rev Time 0.00
Received By mcarsill Date 2010-03-29 Time 11:08 Sent To  
Notes
2010-03-29 11:09:20CHANGES MADE ON SHEET E0.00 AS REQUESTED BY CAPTAIN
 MIKE WILLIAMS.
  
 APPROVED
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-02-09 Cont ID  
Sent By mawillia Date 2010-02-09 Time 14:49 Rev Time 0.00
Received By mawillia Date 2010-02-09 Time 14:32 Sent To  
Notes
2010-02-09 14:48:58*****PARTIAL APPROVAL*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE OTHER PLAN EXAMINERS' COMMENTS AS WELL AS THE
 FOLLOWING HAVE BEEN ADDRESSED:
  
 1. THE 2006 EDITION OF NFPA 101 - LIFE SAFETY CODE -
 SHALL BE REFERENCED. (SEE SHEET E0.00)
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2010-03-22 Cont ID  
Sent By lwagner Date 2010-03-22 Time 09:19 Rev Time 0.00
Received By lwagner Date 2010-03-22 Time 09:19 Sent To  
Notes
2010-03-22 09:20:16NOT REQUIRED. DIESEL FUEL

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2010-01-28 Cont ID  
Sent By kstevens Date 2010-01-28 Time 15:36 Rev Time 0.00
Received By kstevens Date 2010-01-28 Time 15:36 Sent To  
Notes
2010-01-28 15:36:55NO FUEL GAS INDICATED OR SHOWN. DIESEL FUEL ONLY
 INDICATED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-03-17 Cont ID  
Sent By rmcdouga Date 2010-03-16 Time 10:06 Rev Time 0.00
Received By rmcdouga Date 2010-03-16 Time 10:06 Sent To  
Notes
2010-03-17 10:23:04TO C-13

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-03-08 Cont ID  
Sent By dpalmer Date 2010-03-08 Time 13:56 Rev Time 0.00
Received By dpalmer Date 2010-03-08 Time 13:55 Sent To  
Notes
2010-03-08 13:56:01TO C-21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-02-09 Time 14:32 Rev Time 0.00
Received By jwitmer Date 2010-01-21 Time 10:21 Sent To  
Notes
2010-01-21 10:25:08INCOMING SENT TO COMMERCIAL BOARD # C-8.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-04-01 Cont ID  
Sent By rregueir Date 2010-02-01 Time 15:30 Rev Time 0.00
Received By amckenzi Date 2010-04-01 Time 12:28 Sent To  
Notes
2010-04-01 12:28:53PASSED PER DW/AMM
2010-02-01 15:30:54REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 ABOVE GROUND FUEL STORAGE TANKES IN EXCESS OF 550
 GALLONS SHALL BE APPROVED BY PALM BEACH COUNTY DERM
 PRIOR TO PERMIT ISSUANCE. FOR ADDITIONAL INFORMATION
 PLEASE VISIT WWW.PBCGOV.COM/ERM OR CALL 561-233-2400.
  
 IF YOU HAVE ANY ADDITIONAL QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2010-03-11 Cont ID  
Sent By eschneid Date 2010-03-11 Time 08:45 Rev Time 0.25
Received By eschneid Date 2010-03-11 Time 08:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2010-02-09 Cont ID  
Sent By eschneid Date 2010-02-09 Time 10:51 Rev Time 0.30
Received By eschneid Date 2010-02-09 Time 10:51 Sent To  
Notes
2010-02-09 10:52:44PASSED W/PROVISO
  
 1) SEPARATE PARKING RE-STRIPE PERMITS ARE REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.