Plan Review Details - Permit 10010276
Plan Review Stops For Permit 10010276
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-04-26 Cont ID  
Sent By jwitmer Date 2010-04-26 Time 16:07 Rev Time 0.77
Received By jwitmer Date 2010-04-26 Time 16:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-02-04 Cont ID  
Sent By jwitmer Date 2010-02-04 Time 12:02 Rev Time 1.00
Received By jwitmer Date 2010-02-04 Time 11:32 Sent To  
Notes
2010-02-04 12:09:44BUILDING PLAN REVIEW
 PERMIT: 10010276
 ADD: 6895 N JOG
 CONT:T B D
 TEL: (561)684-7534 JOSE HURTAS
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) CURRENTLY PERMIT APPLICATION INDICATES TBD TO BE
 DETERMINED, A LICENSED CONTRACTOR WILL NEED TO SIGN ON
 AND LICENSURE BE VERIFIED.
  
 2) STRUCTURAL PLANS TITLEBLOCK INDICATE THEY WERE
 CREATED BY WILLIAM KIAHON P.E., THEY ARE NOT SIGNED NOR
 SEALED.
 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 3) PLANS ARE MISSING THE WIND DESIGN CRITERIA:1603.1.4
 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 3.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 3.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 3.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 3.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 4) 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-04-22 Cont ID  
Sent By btrobaug Date 2010-04-22 Time 11:28 Rev Time 0.00
Received By btrobaug Date 2010-04-22 Time 10:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-02-02 Cont ID  
Sent By dpalmer Date 2010-02-02 Time 16:02 Rev Time 0.00
Received By dpalmer Date 2010-02-02 Time 16:01 Sent To  
Notes
2010-02-02 16:02:15*DENIED*
  
  
 1) NOTE: PERMIT APPLICATION HAS BEEN MADE HOWEVER NOT
 BY A LICENSED CONTRACTOR. REVIEW WILL REMAIN IN FAILED
 STATUS UNTIL APPLICATION IS UNDER LICENSED CONTRACTOR
 WHERE LICENSE INFORMATION CAN BE VERIFIED.
  
 2) NOTE: PLANS SUBMITTED ARE NOT SIGNED, DATED OR
 SEALED AS REQUIRED PER FAC 61G15-23.002 OR FS 471.025.
  
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2010-02-01 Cont ID  
Sent By dlauderm Date 2010-02-01 Time 09:59 Rev Time 1.00
Received By dlauderm Date 2010-02-01 Time 09:57 Sent To  
Notes
2010-02-01 09:59:04PASSED.
 NO CHANGES TO PERVIOUS/IMPERVIOUS AREAS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-04-22 Cont ID  
Sent By mawillia Date 2010-04-22 Time 16:06 Rev Time 0.00
Received By mawillia Date 2010-04-22 Time 15:57 Sent To  
Notes
2010-04-22 16:14:31*****APPROVED*****
  
 PLAN SHEET C-2 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2010-02-11 Cont ID  
Sent By mawillia Date 2010-02-11 Time 11:20 Rev Time 0.00
Received By mawillia Date 2010-02-11 Time 11:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-04-26 Cont ID  
Sent By jwitmer Date 2010-04-26 Time 16:08 Rev Time 0.00
Received By jwitmer Date 2010-04-14 Time 15:30 Sent To  
Notes
2010-04-14 16:03:58INCOMING SENT TO C-8

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-02-11 Time 11:17 Rev Time 0.00
Received By rmcdouga Date 2010-01-19 Time 11:59 Sent To  
Notes
2010-01-21 12:00:11C32

Review Stop Z ZONING
Rev No 2 Status P Date 2010-04-19 Cont ID  
Sent By eschneid Date 2010-04-19 Time 10:58 Rev Time 0.50
Received By eschneid Date 2010-04-19 Time 10:58 Sent To  
Notes
2010-04-19 10:58:45REPLACE ANY DAMAGED/DESTROYED SHRUBS AND TREES.

Review Stop Z ZONING
Rev No 1 Status F Date 2010-01-26 Cont ID  
Sent By eschneid Date 2010-01-26 Time 17:15 Rev Time 0.25
Received By eschneid Date 2010-01-26 Time 16:45 Sent To  
Notes
2010-01-26 17:15:23FAILED - MORE INFORMATION REQUIRED.
  
 1) THE NEW GATE ARM GATE FOR THE INBOUND LANE APPEARS
 TO BE IN CONFLICT WITH EXISTING TREES SHOWN IN THE 2009
 AERIAL. PLEASE VERIFY THAT THAT THERE WILL BE NO
 CONFLICT - BEST METHOD IS WITH PHOTOS SHOWING PROPOSED
 ARM GATE ADDED.
  
 2) IF NOT CONFLICT, THEN OK FOR ZONING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved