| 2010-01-27 14:51:06 | |
| | ** PROVISO * |
| | |
| | ** THE FOLLOWING ITEMS LISTED BELOW ARE REQUIRED TO BE |
| | REVISED, SUBMITTED FOR REVIEW AND ON-SITE FOR INSPECTOR |
| | BEFORE FINAL ELECTRICAL INSPECTION. ALL OTHER REVISIONS |
| | ARE REQUIRED BEFORE ROUGH ELECTRICAL INSPECTION. |
| | |
| | 1) NOTE: THE PANEL SCHEDULE CONTAINS SEVERAL CIRCUITS |
| | WHICH ARE LISTED A *EXISTING POWER* HOWEVER NOT |
| | INFORMATION ON PLANS OR WHAT THESE FEED IS PROVIDED. |
| | THERE ARE SEVERAL SINGLE POLE CIRCUITS AS WELL AND A |
| | 2-POLE CIRCUIT WHICH IS NOT SHOWN. ALL CIRCUITING IS TO |
| | BE SHOWN ON PLANS AND IDENTIFIED ON PANEL SCHEDULE. |
| | CIRCUITING FROM THIS TENANT SPACE PANEL MAY NOT FEED |
| | OTHER TENANT SPACES OR COMMON AREAS. |
| | PLEASE ALSO BE SURE TO UPDATE THE ROOF TOP GFI |
| | RECEPTACLES WHICH ARE NOTED ON PLANS. |
| | 408.4. |
| | |
| | 2) NOTE: THE WATER HEATER IN THE LOAD CALCULATIONS |
| | NOTES A DE-RATING OF 65%. THE ACTUAL CALCULATIONS DO |
| | DEPICT THE REQUIRED 125% PER 422.13. A CALL WAS PLACED |
| | TO DESIGN TEAM AND APPEARS TO BE A MISPRINT. PLEASE |
| | ADJUST WHEN REVISING FINAL SET OF PLANS. |
| | |
| | 3) NOTE: SHEET E3.01 NOTES CONTAIN CODE REFERENCES. |
| | MOST ARE OK HOWEVER PLANS CONTAIN REFERENCE TO THE 2005 |
| | NFPA-72. THE STATE HAS NOT YET ADOPTED THE 2005 EDITION |
| | OF NFPA-72. |
| | THIS WAS REDLINED ON BOTH SETS. PLEASE ADJUST WHEN |
| | MAKING OTHER CHANGES TO THE PLANS. |
| | |
| | 4) NOTE: AS NOTED AND STAMPED ON PLANS, ALL LOW VOLTAGE |
| | IS REQUIRED TO BE UNDER SEPARATE PERMITS. MAIN PLANS |
| | MAY BE REFERENCED FOR PHONE AND DATA TURN AROUND |
| | PERMIT. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |