Plan Review Details - Permit 10010253
Plan Review Stops For Permit 10010253
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-03-18 Cont ID  
Sent By jwitmer Date 2010-03-18 Time 15:32 Rev Time 0.33
Received By jwitmer Date 2010-03-18 Time 15:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-02-25 Cont ID  
Sent By jwitmer Date 2010-02-25 Time 15:37 Rev Time 0.77
Received By jwitmer Date 2010-02-25 Time 15:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-01-26 Cont ID  
Sent By jwitmer Date 2010-01-26 Time 10:19 Rev Time 1.55
Received By jwitmer Date 2010-01-26 Time 09:00 Sent To  
Notes
2010-01-26 11:04:37BUILDING PLAN REVIEW
 PERMIT: 10010253
 ADD: 901 45TH ST
 CONT: OVERLAND CONSTRUCTION
 TEL: (561)543-4287
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 JAN 26/ 2010
  
 1) SHEET T1:
 1A) APPLICABLE BUILDING CODE INDICATES PALM BEACH
 COUNTY AMENDMENTS, PLEASE UPDATE TO CITY OF WEST PALM
 BEACH AMENDMENTS, TO CHAPTER 1.
  
 1B) FIRE PROTECTION REQUIREMENTS INDICATE THIS TO BE A
 FULLY FIRE SPREINKLERED BUILDING THEN UNDER THE HEADING
 OF SMOKE COMPARTMENT THE PLANS INDICATE THE BUILDING IS
 ONLY PARTIALLY SPRINKLERED? PLEASE EXPLAIN!
  
 1C) UNDER THE HEADING OF PROJECT DATA THE PLANS
 INDICATE A SECTION FBC 3401.8.3.3 THIS CHAPTER HAS BEEN
 DELETED OUT OF THE 2004 AS WELL AS THE 2007 FBC. THE
 EXISTING BUILDING CODE HAS TAKEN THIS SECTIONS PLACE,
 PLEASE UPDATE PLANS.
  
 1D) PLANS FAIL TO PROVIDE SQUARE FOOTAGE OF OFFICE AREA
 AND OCCUPANT LOAD, TABLE 1004.1.1.
  
 1E) THE FLOOR PLAN NOR THE REFLECTED CEILING PLAN
 INDICATE EXIT LIGHTING AND EMERGENCY EXIT LIGHTING FBC
 -B 1006.
  
 2) SHEET D1 NOTE 11 INDICATES THE REMOVAL OF A DRINKING
 FOUNTAIN. SHEET A1 INDICATES IN ITS PLACE A NEW COFFE
 COUNTER. SHEET A3 ELEVATIONS OF THE COFFEE COUNTER
 INDICATE A HEIGHT OF 2'-10" BUT THE BOTTOM IS BLOCKED
 BY DRAWERS SO A FORWARD APPROACH CAN NOT BE
 ACCOMPLISHED. PLEASE REVIEW SECTION 11-4.24 (1-7).
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-02-25 Cont ID  
Sent By btrobaug Date 2010-02-25 Time 16:14 Rev Time 0.00
Received By btrobaug Date 2010-02-25 Time 15:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-01-21 Cont ID  
Sent By btrobaug Date 2010-01-21 Time 11:03 Rev Time 0.00
Received By btrobaug Date 2010-01-21 Time 09:14 Sent To  
Notes
2010-01-21 11:03:38 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED. AN
 ELECTRICAL CONTRACTOR MUST REMOVE ALL WIRING IN
 AFFECTED AREAS FOR DEMOLITION AND MAKE SAFE SAME. ALL
 TEMPORARY WIRING FOR THIS DEMOLITION SHALL COMPLY WITH
 ARTICLE 590 NEC.
  
 2} THE DESCRIPTION ON THE APPLICATION INDICATES
 ELECTRICAL WORK TO BE DONE UNDER THIS PERMIT BUT NO
 ELECTRICAL PLANS WERE SUBMITTED. SUBMIT PLANS
 INDICATING THE SCOPE OF WORK, OR REMOVE THE ELECTRICAL
 WORK FROM THE APPLICATION. 106.1 FBC AS AMENDED.
  
 3} THE 2008 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 1 OCTOBER 2009. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2010-03-18 Cont ID  
Sent By mawillia Date 2010-03-18 Time 16:11 Rev Time 0.00
Received By mawillia Date 2010-03-18 Time 16:02 Sent To  
Notes
2010-03-18 16:10:38*****PREVIOUSLY APPROVED*****
  
 THE APPROPIATE PLAN SHEETS T1, A2, AND A4 WERE
 PREVIOUSLY STAMPED, INITIALED, AND DATED ON 03/01/2010.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-03-01 Cont ID  
Sent By mawillia Date 2010-03-01 Time 11:48 Rev Time 0.00
Received By mawillia Date 2010-03-01 Time 11:41 Sent To  
Notes
2010-03-01 11:41:38*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN NREVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS T1, A2, AND A4 WERE STAMPED,
 INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-01-28 Cont ID  
Sent By mawillia Date 2010-01-28 Time 16:21 Rev Time 0.00
Received By mawillia Date 2010-01-28 Time 15:50 Sent To  
Notes
2010-01-28 16:17:26*****DENIED*****
  
  
 1. ON SHEET T1 IN THE APPLICABLE BUILDING CODES,
 REFERENCE IS INCORRECTLY MADE TO PALM BEACH COUNTY
 AMENDMENTS. REFERENCE AS PER THE CITY OF WEST PALM
 BEACH.
  
 2. ON SHEET T1, IT IS INDICATED THAT THE BUILDING IS
 PARTIALLY SPRINKLERED. VERIFY AND/OR EXPLAIN THIS
 ARRANGEMENT.
  
 3. PLEASE SHOW THE LOCATION OF EXIT LIGHTS AND
 EMERGENCY LIGHTS FOR THE PROPOSED FLOOR PLAN.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-03-15 Cont ID  
Sent By shill Date 2010-03-15 Time 16:10 Rev Time 0.00
Received By shill Date 2010-03-15 Time 16:09 Sent To  
Notes
2010-03-15 16:09:58B9
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-02-24 Cont ID  
Sent By btrobaug Date 2010-02-24 Time 11:51 Rev Time 0.00
Received By btrobaug Date 2010-02-24 Time 11:51 Sent To  
Notes
2010-02-24 11:54:22B-6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-01-28 Time 16:05 Rev Time 0.00
Received By shill Date 2010-01-20 Time 09:39 Sent To  
Notes
2010-01-20 09:39:28B 20
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2010-03-22 Cont ID  
Sent By lwagner Date 2010-03-22 Time 11:21 Rev Time 0.00
Received By lwagner Date 2010-03-22 Time 11:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2010-03-02 Cont ID  
Sent By kstevens Date 2010-03-02 Time 13:12 Rev Time 0.00
Received By kstevens Date 2010-03-02 Time 13:12 Sent To  
Notes
2010-03-02 13:16:28DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
  
 ****FROM PREVIOUS REVIEW:
  
 1. SHT SHT D1 DEMO NOTE #11 INDICATES THE REMOVAL OF A
 DRINKING FOUNTAIN. PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. IF THERE ARE OTHER DRINKING FOUNTAINS IN
 THE TENANT SPACE PLEASE INDICATE THE LOCATION.
 ****RESPONSE NOTED, BUT THE REQUIRED DRINKING FOUNTAIN
 IS NOT INDICATED. A SINK IS NOT AN ACCEPTABLE
 REPLACEMENT FOR THE REQUIRED DRINKING FOUNTAIN.
  
 2. THE SINK SHALL COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. PLEASE SUBMIT A DETAIL FOR THE FOLLOWING:
 A. OK
 B. 11-4.24.5 CLEAR FLOOR SPACE. (FORWARD APPROACH
 REQUIRED MAX 19" UNDERNEATH THE SINK. (SEE FIG 32).
 ****NOT SHOWN ON FLOOR PLAN. -- CABINET DOORS ARE
 PROHIBITED IN THE "CLEAR FLOOR SPACE" PLEASE DELETE
 FROM ELEVATION.
 C. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-01-27 Cont ID  
Sent By kstevens Date 2010-01-27 Time 13:42 Rev Time 0.00
Received By kstevens Date 2010-01-27 Time 13:42 Sent To  
Notes
2010-01-27 14:08:42DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
  
 1. SHT SHT D1 DEMO NOTE #11 INDICATES THE REMOVAL OF A
 DRINKING FOUNTAIN. PER TABLE 403.1 A DRINKING FOUNTAIN
 IS REQUIRED. IF THERE ARE OTHER DRINKING FOUNTAINS IN
 THE TENANT SPACE PLEASE INDICATE THE LOCATION.
  
 2. THE SINK SHALL COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. PLEASE SUBMIT A DETAIL FOR THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.5 CLEAR FLOOR SPACE. (FORWARD APPROACH
 REQUIRED MAX 19" UNDERNEATH THE SINK. (SEE FIG 32).
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  