Plan Review Details - Permit 10010097
Plan Review Stops For Permit 10010097
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2010-03-18 Cont ID  
Sent By jgomez Date 2010-03-18 Time 09:46 Rev Time 0.00
Received By jgomez Date 2010-03-18 Time 08:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2010-03-09 Cont ID  
Sent By jgomez Date 2010-03-09 Time 14:01 Rev Time 0.00
Received By jgomez Date 2010-03-09 Time 11:41 Sent To  
Notes
2010-03-09 14:14:05OFFICE BUILDING ALTERATION, BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- REVISED DOORS ARE OBSTRUCTING THE CORRIDOR LEADING
 TO THE STAIRWAY #2. THESE DOORS DON'T COMPLY WITH SEC.
 1008.1.8.8 FBC 2007. REVISE AS REQUIRED.
  
 2- OWES $238.05 FOR UPDATED VALUATION.
  
 3- REVISE ALL OTHER DRAWINGS TO MATCH REVISED DRAWING
 SHEET A-3. NEED TO REVISE THE LIFE SAFETY FLOOR PLAN
 AND ANY OTHER FLOOR PLAN THAT NEEDS TO BE REVISED TO
 MATCH SHEET A-3.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2010-01-26 Cont ID  
Sent By jgomez Date 2010-01-26 Time 10:07 Rev Time 0.00
Received By jgomez Date 2010-01-26 Time 09:04 Sent To  
Notes
2010-01-26 10:24:39OFFICE BUILDING ALTERATION, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- NEW DOORS NEED TO SWING ON THE DIRECTION OF EGRESS
 TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50 OR MORE
 PERSONS (97 PEOPLE. SEE SHEET T). SEC. 1001.4 AND SEC.
 1008.1.2 OF FBC 2007 WHEN
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. UPDATE PERMIT VALUATION TO INCLUDE ALL DEMOLITION,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 108.3 OF CITY
 AMENDMENTS TO FBC.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMBINATION COMMERCIAL PLANS EXAMINER
 (561)805-6712
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-01-12 Cont ID  
Sent By btrobaug Date 2010-01-12 Time 10:50 Rev Time 0.00
Received By mawillia Date 2010-01-19 Time 14:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-03-18 Cont ID  
Sent By mawillia Date 2010-03-18 Time 12:26 Rev Time 0.00
Received By mawillia Date 2010-03-18 Time 12:02 Sent To  
Notes
2010-03-18 12:20:27*****APPROVED*****
  
  
 PREVIOUSLY APPROVED (1/19/2010) PLAN SHEETS A-4 AND A-5
 WERE AGAIN STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-01-19 Cont ID  
Sent By mawillia Date 2010-01-19 Time 14:35 Rev Time 0.00
Received By mawillia Date 2010-01-19 Time 14:24 Sent To  
Notes
2010-01-19 14:35:33*****APPROVED*****
  
  
 PLAN SHEETS A-2, A-4, A-5, AND E-1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-03-17 Cont ID  
Sent By rmcdouga Date 2010-03-17 Time 10:26 Rev Time 0.00
Received By rmcdouga Date 2010-03-17 Time 10:26 Sent To  
Notes
2010-03-17 10:27:19SENT TO JULIO GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-03-09 Cont ID  
Sent By jgomez Date 2010-03-09 Time 14:01 Rev Time 0.00
Received By jgomez Date 2010-02-18 Time 08:17 Sent To  
Notes
2010-02-18 08:18:03INCOMING SEENT TO J.G.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-01-26 Cont ID  
Sent By jgomez Date 2010-01-26 Time 10:24 Rev Time 0.00
Received By jgomez Date 2010-01-11 Time 16:23 Sent To  
Notes
2010-01-11 16:31:08TO B11
  
 APPLICATION STATES WORK FOR 9700 PLUS SQ FT HOWEVER
 AREA SHOWN ON PLANS IS LESS. ROUTED TO BOB BOARD

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-01-26 Cont ID  
Sent By jgomez Date 2010-01-26 Time 09:06 Rev Time 0.00
Received By jgomez Date 2010-01-26 Time 09:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2010-01-26 Cont ID  
Sent By jgomez Date 2010-01-26 Time 10:01 Rev Time 0.00
Received By jgomez Date 2010-01-26 Time 10:01 Sent To  
Notes
2010-01-26 10:02:30NO MECHANICAL WORK SHOWN

Review Stop P PLUMBING
Rev No 1 Status N Date 2010-01-26 Cont ID  
Sent By jgomez Date 2010-01-26 Time 10:02 Rev Time 0.00
Received By jgomez Date 2010-01-26 Time 10:02 Sent To  
Notes
2010-01-26 10:03:09NO PLUMBING WORK SHOWN

Review Stop Z ZONING
Rev No 1 Status N Date 2010-01-25 Cont ID  
Sent By kdfreema Date 2010-01-25 Time 09:02 Rev Time 0.00
Received By kdfreema Date 2010-01-25 Time 09:02 Sent To  
Notes
***NONE***