| 2010-01-19 10:11:07 | BUILDING PLAN REVIEW |
| | PERMIT: 10010085 |
| | ADD: 6501 N JOG RD |
| | CONT: B E & K CONST |
| | TEL: (205)972-6000 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS FOR THE TURBINE GENERATOR STRUCTURAL CONCRETE |
| | CONTROL ROOM ACCESS FOUNDATION PLAN, OUTSIDE AREA |
| | LIMITS STRUCTURAL STANDARDS GENERAL NOTES, |
| | SPECIFICATION FOR CAST IN PLACE CONCRETE AND THE |
| | SPECIFICATIONS FOR STRUCTURAL STEEL BOTH ARE COPIES |
| | BOTH SETS REQUIRE ORIGINAL SIGN AND SEALED ORIGINALS. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | |
| | 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED |
| | BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE: |
| | NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR, |
| | THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE |
| | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER |
| | IS PRACTICING (471.025 F.S. AND 471.023 F.S.). |
| | |
| | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| | ON THE COVER SHEET OR INDEX. |
| | |
| | 2) THE TURBINE GENERATOR STRUCTURAL CONCRETE CONTROL |
| | ROOM ACCESS FOUNDATION PLAN, ADDITIONAL INFORMATION IS |
| | REQUIRED, 106.1.2 |
| | 2A) ARE THESE STAIRS THE ONLY ACCESS TO THE CONTROL |
| | ROOM? |
| | |
| | 2B) ARE THESE STAIRS LOCATED WITHIN THE FOOT PRINT OF |
| | THE BUILDING OR ARE THEY LOCATED ON THE EXTERIOR? |
| | IF LOCATED WITHIN THE BUILDING, ARE THEY IN A SHAFT |
| | ENCLOSURE OR IS THE CONTROL ROOM PAART OF A MEZZANINE |
| | NOT REQUIRING A ENCLOSED STAIR? |
| | IF TTHE STAAIRS ARE LOCATED ON THE EXTERIOR OF THE |
| | BUILDING PLEASE PROVIDE THE WIND CRITERIA DESIGN PER |
| | 1609.1.1/ ASCE 7-05 CHAPTER 6 WIND. |
| | |
| | 3) PROVISO: SHOP DRAWINGS FOR HELICAL PIERS. |
| | |
| | 4) S SHEETS INDICATE THE RISE AND RUN OF THE |
| | REPLACEMENT STAIR BUT I COULD NOT FIND INFORMATION ON |
| | THE HANDRAIL / GUARD RAIL CONFIGURATIONS FBC B 1012 & |
| | 1013. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |