Plan Review Details - Permit 10010055
Plan Review Stops For Permit 10010055
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-01-20 Cont ID  
Sent By jwitmer Date 2010-01-20 Time 10:09 Rev Time 2.22
Received By jwitmer Date 2010-01-19 Time 16:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-01-21 Cont ID  
Sent By dpalmer Date 2010-01-21 Time 16:56 Rev Time 0.00
Received By dpalmer Date 2010-01-21 Time 16:56 Sent To  
Notes
2010-01-21 16:56:53 
 ** PROVISO **
  
 ** REVISE THE FOLLOWING BEFORE ROUGH. SUBMIT PLANS AND
 BE SURE PLANS ARE ON-SITE FOR INSPECTION.
  
  
 1) NOTE: PLANS ARE REFERENCED TO THE 2005 NEC. ALL PER
 ALL PROJECTS SUBMITTED FOR PERMIT AFTER OCTOBER 1ST,
 2009 IS UNDER THE 2008 NEC.
  
 2) NOTE: RISER DOES INCLUDE A PANEL L1 HOWEVER NO PANEL
 SCHEDULE FOR PANEL L WAS SUBMITTED. CAN NOT VERIFY SIZE
 OF FEEDER AND OVER CURRENT PROTECTION TO L1.
 240.4,310.16,408.4 ETC
 CAN NOT VERIFY ADJUSTED LOADS ON PANEL L.
 220,220.12,220.14,220.42,220.44 ETC. CONTINUOUS LOADS
 PER 215.3,230.42 ETC
 CAN NOT VERIFY TAPPED CONDUCTORS FROM TRANSFORMER
 TERMINATING IN OVER CURRENT PROTECTION PER 240.21, AND
 408.36. PANEL L1 IS A MLO PANEL.
  
 3) NOTE: ALL MINIMUM LEVELS FOR HORNS, STROBE FOR ADA
 COMPLIANCE NEEDS TO BE SHOWN. FOR EXAMPLE: STATING
 STROBES TO MEET ADA COMPLIANCE DOES NOT PROVIDE MINIMUM
 INFORMATION FOR COMPLIANCE. THIS SHOULD STATE MINIMUM
 CD OR CANDELA 75 OR WORDS TO THAT AFFECT. THE SAME FOR
 SOUNDING DEVICES AND LOCATIONS FOR DB LEVELS.
 ALTHOUGH THE FIRE ALARM WILL BE UNDER A SEPARATE PERMIT
 THE BASE PLANS IS REQUIRED TO SHOWN BASE DESIGN INTENT.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-01-25 Cont ID  
Sent By mawillia Date 2010-01-25 Time 13:17 Rev Time 0.00
Received By mawillia Date 2010-01-25 Time 13:05 Sent To  
Notes
2010-01-25 13:17:35*****APPROVED*****
  
  
 PLAN SHEETS A2, A-3, A-5, AND E-2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-01-25 Cont ID  
Sent By rregueir Date 2010-01-25 Time   Rev Time 0.00
Received By rregueir Date 2010-01-11 Time 14:59 Sent To  
Notes
2010-01-11 15:01:16C-20

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-01-25 Cont ID  
Sent By rregueir Date 2010-01-25 Time 16:52 Rev Time 0.00
Received By rregueir Date 2010-01-25 Time 16:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2010-01-12 Cont ID  
Sent By kstevens Date 2010-01-12 Time 08:48 Rev Time 0.00
Received By kstevens Date 2010-01-12 Time 08:48 Sent To  
Notes
2010-01-12 08:48:49NO PLUMBING INDICATED OR SHOWN ON PLANS.

Review Stop Z ZONING
Rev No 1 Status N Date 2010-01-25 Cont ID  
Sent By kdfreema Date 2010-01-25 Time 16:52 Rev Time 0.00
Received By kdfreema Date 2010-01-25 Time 16:52 Sent To  
Notes
***NONE***