| 2010-01-07 16:48:21 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 09120549 |
| | ADD: 5701 N MILITARY TRAIL |
| | CONT: PENTEON SYNDICATED INC |
| | TEL: (561) 714-3444 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | JAN. 06/ 2010 |
| | |
| | 1) STRUCTURAL ANALYSIS REPORT FROM IETS ENGINEERING |
| | SERVICES, THE COVER PAGE IS NOT SIGNED NOR SEALED AS |
| | REQUIRED BY FLORIDA ADMINISTRATIVE CODE: |
| | 61G15-23.002 SEAL, SIGNATURE AND DATE SHALL BE AFFIXED. |
| | (1) A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND |
| | AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS, |
| | FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR THE |
| | OWNER???S REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED |
| | OR ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC |
| | RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED |
| | AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS, |
| | SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. |
| | (2) EACH SHEET OF PLANS MUST BE SEALED UNDER THE |
| | PROVISIONS OF CHAPTER 471, F.S., SHALL BE SEALED, |
| | SIGNED AND DATED BY THE PROFESSIONAL ENGINEER IN |
| | RESPONSIBLE CHARGE. |
| | |
| | 2) THE STRUCTURAL ANALYSIS REPORT FROM IETS ENGINEERING |
| | SERVICES MAY ELECT TO COMPLY IN THIS MANNER, THE COVER |
| | SHEET OR INDEX PAGE WILL NEED TO IDENTIFY HOW MANY |
| | PAGES ARE TO BE WITHIN THE REPORT. |
| | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| | ON THE COVER SHEET OR INDEX. |
| | |
| | 3) THE STRUCTURAL ANALYSIS REPORT FROM IETS ENGINEERING |
| | SERVICES PAGE 3 THE INTRODUCTION INDICATES THE TOWER |
| | WAS ORIGINALLY DESIGNED IN APRIL UNDER THE 1997 |
| | SOUTH FLORIDA BUILDING CODE FOR 120 MPH. PLEASE REVIEW, |
| | THE CITY OF WEST PALM BEACH WAS NOT UNDER THE SOUTH |
| | FLORIDA BUILDING CODE EVER. APRIL 1997 THE CITY OF WEST |
| | PALM BEACH WAS UNDER TTHTE 2004 STANDARD BUILDING CODE, |
| | 110 MPH. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |