Plan Review Details - Permit 09120546
Plan Review Stops For Permit 09120546
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-12-31 Cont ID  
Sent By mcarsill Date 2009-12-31 Time 07:41 Rev Time 0.00
Received By mcarsill Date 2009-12-31 Time 07:35 Sent To  
Notes
2009-12-31 07:41:091. THE FIRE ALARM SYSTEM AND COMPONENTS ARE TO BE
 INSTALLED IN ACCORDANCE WITH NFPA 72, THE NATIONAL FIRE
 ALARM CODE.
  
 2. THE ENTIRE SYSTEM IS TO BE TESTED WITH THIS OFFICE
 UPON COMPLETION.
  
 3. THE EXISTING FIRE ALARM EQUIPMENT SHALL ALSO BE IN
 GOOD WORKING ORDER.
  
 4. THE ENTIRE INSTALLATION IS SUBJECT TO FIELD
 INSPECTION AND APPROVAL.
  
 5. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL
 LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION
 SERVICE.
  
 6. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT
 LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS.
  
  
 APPROVED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION