Plan Review Details - Permit 09120539
Plan Review Stops For Permit 09120539
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-30 Cont ID  
Sent By jgomez Date 2009-12-30 Time 10:17 Rev Time 0.00
Received By jgomez Date 2009-12-30 Time 10:17 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-29 Cont ID  
Sent By jgomez Date 2009-12-29 Time 15:56 Rev Time 0.00
Received By jgomez Date 2009-12-29 Time 15:55 Sent To PC
Notes
2009-12-29 15:57:39RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDING TO THE MIAMI-DADE WEBSITE MODIFIED BITUMEN
 07-1203.01 IS SUPERSEDED. GO TO MIAMI-DADE WEBSITE AND
 PROVIDE CURRENT NOA.
  
 2- GAF MODIFIED BITUMEN NOA'S REQUIRE SIGNED AND SEALED
 RAS 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER
 AND CORNER AREAS. SEE GENERAL LIMITATION #7 ON LAST
 PAGE OF NOA SUBMITTED. NEED TO PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS. ***NOTE: DESIGN
 PROFESSIONAL DOING THE CALCULATIONS TO TAKE INTO
 CONSIDERATION THAT ACCORDING TO THE 2009 REVISIONS THIS
 BUILDING IS LOCATED ON EXPOSURE "C" NOT "B".
  
 3- CLEARLY IDENTIFY WHICH APPROVED FLAT ROOF ASSEMBLY
 IS GOING TO BE INSTALLED. AND, WHICH BASE SHEET
 FASTENING OPTION IS GOING TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF
 2007 FLORIDA RESIDENTIAL CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712