Plan Review Details - Permit 09120529
Plan Review Stops For Permit 09120529
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2010-02-03 Cont ID  
Sent By lmartine Date 2010-02-03 Time 16:00 Rev Time 0.00
Received By lmartine Date 2010-02-03 Time 16:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2010-01-14 Cont ID  
Sent By dpalmer Date 2010-01-14 Time 16:58 Rev Time 0.00
Received By dpalmer Date 2010-01-14 Time 16:58 Sent To  
Notes
2010-01-14 16:59:07 
 ** DENIED/NONE *
  
 1) NOTE: ON SHEET A5 SUBMITTED FOR REVISIONS THERE ARE
 NO REVISIONS INDICATED ON PLANS AND THERE NO ACTUAL
 CHANGES MADE.
  
 ** THE PREVIOUS PLANS STAMPED FOR PERMIT ISSUANCE HAD A
 REDLINED NOTE FOR 250.6 AND 250.24. RISER AT THAT TIME
 INDICATED *EQUIPMENT GROUNDING CONDUCTORS* BEFORE THE
 FIRST MEANS OF DISCONNECT. HOWEVER PER THE SECTIONS
 NOTED ABOVE THIS IS NOT PERMITTED. THE GROUNDED
 (NEUTRAL) IS REQUIRED TO BONDED AT THE FIRST MEANS OF
 DISCONNECT PER 250.24. IF AN *EQUIPMENT GROUNDING
 CONDUCTOR* IS ALSO INSTALLED THIS WOULD PARALLEL THE
 GROUND (NEUTRAL) CONDUCTOR CREATING OBJECTIONABLE
 CURRENTS. THIS IS NOT PERMITTED AND IS A POSSIBLE FIRE
 AND OR LIFE SAFETY HAZARD.
 NO EQUIPMENT GROUNDING CONDUCTORS ARE TO BE INSTALLED
 BEFORE THE FIRST MEANS OF DISCONNECT FOR EITHER OF THE
 TWO MAINS SHOWN. IF THERE ARE QUESTIONS ON THIS PLEASE
 CALL.
  
 2) NOTE: ON SHEET B5 SUBMITTED FOR REVISIONS, THERE IS
 NO ACTUAL REVISION. THERE IS A CLOUD INDICATED ON
 ELECTRICAL SECOND FLOOR LAYOUT FOR PORCH AREA HOWEVER
 THERE ARE NO ACTUAL CHANGES MADE TO PLANS. THE PLANS ON
 FILE DATED
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-02-03 Cont ID  
Sent By lmartine Date 2010-02-03 Time 16:01 Rev Time 0.00
Received By lmartine Date 2009-12-28 Time 16:31 Sent To  
Notes
2009-12-28 16:31:22R 8

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-01-27 Cont ID  
Sent By hmoser Date 2010-01-27 Time 13:39 Rev Time 0.00
Received By hmoser Date 2010-01-27 Time 13:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2010-01-04 Cont ID  
Sent By kstevens Date 2010-01-04 Time 16:20 Rev Time 0.00
Received By kstevens Date 2010-01-04 Time 16:20 Sent To  
Notes
2010-01-04 16:21:10NO PLUMBING REVISIONS NOTED.

Review Stop Z ZONING
Rev No 1 Status P Date 2009-12-30 Cont ID  
Sent By jroach Date 2009-12-30 Time 14:25 Rev Time 0.00
Received By jroach Date 2009-12-30 Time 14:25 Sent To  
Notes
***NONE***