| 2010-01-14 16:59:07 | |
| | ** DENIED/NONE * |
| | |
| | 1) NOTE: ON SHEET A5 SUBMITTED FOR REVISIONS THERE ARE |
| | NO REVISIONS INDICATED ON PLANS AND THERE NO ACTUAL |
| | CHANGES MADE. |
| | |
| | ** THE PREVIOUS PLANS STAMPED FOR PERMIT ISSUANCE HAD A |
| | REDLINED NOTE FOR 250.6 AND 250.24. RISER AT THAT TIME |
| | INDICATED *EQUIPMENT GROUNDING CONDUCTORS* BEFORE THE |
| | FIRST MEANS OF DISCONNECT. HOWEVER PER THE SECTIONS |
| | NOTED ABOVE THIS IS NOT PERMITTED. THE GROUNDED |
| | (NEUTRAL) IS REQUIRED TO BONDED AT THE FIRST MEANS OF |
| | DISCONNECT PER 250.24. IF AN *EQUIPMENT GROUNDING |
| | CONDUCTOR* IS ALSO INSTALLED THIS WOULD PARALLEL THE |
| | GROUND (NEUTRAL) CONDUCTOR CREATING OBJECTIONABLE |
| | CURRENTS. THIS IS NOT PERMITTED AND IS A POSSIBLE FIRE |
| | AND OR LIFE SAFETY HAZARD. |
| | NO EQUIPMENT GROUNDING CONDUCTORS ARE TO BE INSTALLED |
| | BEFORE THE FIRST MEANS OF DISCONNECT FOR EITHER OF THE |
| | TWO MAINS SHOWN. IF THERE ARE QUESTIONS ON THIS PLEASE |
| | CALL. |
| | |
| | 2) NOTE: ON SHEET B5 SUBMITTED FOR REVISIONS, THERE IS |
| | NO ACTUAL REVISION. THERE IS A CLOUD INDICATED ON |
| | ELECTRICAL SECOND FLOOR LAYOUT FOR PORCH AREA HOWEVER |
| | THERE ARE NO ACTUAL CHANGES MADE TO PLANS. THE PLANS ON |
| | FILE DATED |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |