| 2009-12-30 12:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. APPLICATION IS FOR "2 PICNIC PAVILLIONS," BUT PLANS |
| | SHOW OTHER ITEMS. SOME SHEETS, SUCH AS E5 AND LD1, HAVE |
| | DETAILS FOR OTHER STRUCTURES ON THIS SITE BUT NO |
| | DETAILS ON THOSE PAGES FOR THE TWO PICNIC PAVILLIONS. |
| | PLEASE BE ADVISED THAT ONLY THE PICNIC PAVILLIONS ARE |
| | BEING REVIEWED AT THIS TIME. OTHER DETAILS WILL BE |
| | CROSSED OFF PRIOR TO ISSUANCE UNLESS SCOPE OF WORK ON |
| | THE PERMIT APPLICATION IS REVISED. PLEASE REMOVE SHEETS |
| | WHICH DO NOT APPLY TO THIS PERMIT. |
| | |
| | 2. THE PAVILLIONS ARE TO BE LOCATED ON AN ACCESSIBLE |
| | ROUTE, FBC11-4.1.2(2). IT APPEARS THAT THE SIDEWALK IS |
| | THE ACCESSIBLE ROUTE; PLEASE CONFIRM. |
| | |
| | 3. FBC1802.2, PROVIDE TWO ORIGINAL SOILS REPORTS. |
| | |
| | 4. FAC9B72, PROVIDE PRODUCT APPROVAL FOR THE ROOF. |
| | PRIOR TO SUBMITTAL, THE PRODUCT APPROVALS SHOULD BE |
| | REVIEWED BY DESIGNER OF RECORD. ALSO, PRIOR TO |
| | SUBMITTAL, DESIGNER OF RECORD IS TO CONFIRM WITH THE |
| | METAL ROOF MANUFACTURER THAT THE PRODUCT IS SUITABLE |
| | FOR THIS PROJECT (COASTAL/CORROSIVE). |
| | |
| | 5. PAGE LD2 HAS A NOTE WHICH STATES "REFER TO ANCHOR |
| | AND FOOTING DOWLOAD SHEETS FOR GENERAL INFORMATION . . |
| | . " (ETC.). THESE SHEETS WERE NOT SUBMITTED. NO |
| | STRUCTURAL INFORMATION REGARDING THE PROPOSED SHELTER |
| | OR FOOTING WAS SUBMITTED. DETAILS ON LD1 ARE FOR THE |
| | 10X10 TENNIS SHELTER (NOT THE 20X20 PICNIC SHELTERS). |
| | PLEASE PROVIDE OR REVISE PLANS TO INCLUDE STRUCTURAL |
| | INFORMATION. |
| | |
| | 6. WIND DESIGN CRITERIA (COMPONENTS & CLADDING |
| | PRESSURES) REQUIRED FOR THE ROOF, FBC1603.1.4. |
| | |
| | 7. SEPARATE PERMIT WILL BE REQUIRED FOR THE ROOF. THIS |
| | MAY BE DONE PRIOR TO INSTALLATION. A ROOF PERMIT WILL |
| | REQUIRE ROOF FASTENING OPTIONS TO BE INDICATED ON THE |
| | PRODUCT APPROVAL. |
| | |
| | |
| | |
| | |