Plan Review Details - Permit 09120487
Plan Review Stops For Permit 09120487
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-02-24 Cont ID  
Sent By jwitmer Date 2010-02-24 Time 08:54 Rev Time 0.20
Received By jwitmer Date 2010-02-24 Time 08:54 Sent To  
Notes
2010-02-24 08:54:45NEW A-3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-12-29 Cont ID  
Sent By jwitmer Date 2009-12-29 Time 13:28 Rev Time 1.50
Received By jwitmer Date 2009-12-29 Time 13:28 Sent To  
Notes
2009-12-29 13:30:56BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 DOOR 11 & 12 PLEASE REVIEW 11-4.13.6 & FIG. 25A, WHEN
 THE DOOR HAS A CLOSEER AND LATCH THE MEASUREMENT X= MIN
 12 INCHES.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-02-23 Cont ID  
Sent By btrobaug Date 2010-02-23 Time 12:14 Rev Time 0.00
Received By btrobaug Date 2010-02-23 Time 11:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2010-01-04 Cont ID  
Sent By btrobaug Date 2010-01-04 Time 11:26 Rev Time 0.00
Received By btrobaug Date 2010-01-04 Time 10:37 Sent To  
Notes
2010-01-04 11:26:50 
 PROVISO
  
 1} THE EQUIPMENT GROUND TO THE METER AND BETWEEN THE
 METER AND DISCONNECT ON THE RISER DIAGRAM CREATES A
 PARALLEL PATH TO GROUND WITH THE NEUTRAL AND MUST BE
 REMOVED. AN ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE
 TO BE RAN FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 2} 408.36(A) LIGHTING AND APPLIANCE BRANCH-CIRCUIT
 PANELBOARD INDIVIDUALLY PROTECTED EACH LIGHTING AND
 APPLIANCE BRANCH-CIRCUIT PANELBOARD SHALL BE
 INDIVIDUALLY PROTECTED ON THE SUPPLY SIDE BY NOT MORE
 THAN TWO MAIN CIRCUIT BREAKERS OR TWO SETS OF FUSES
 HAVING A COMBINED RATING NOT GREATER THAN THAT OF THE
 PANELBOARD.*** THE 200 AMP FUSES MUST BE 150 AMP IN THE
 DISCONNECT.
  
 3} THE HEAT PUMPS ON PANEL SCHEDULE "A" AND SHOWN ON
 SHEET "E-1 DO NOT CORRELATE WITH THE HEAT PUMP SCHEDULE
 ON SHEET M4.1. CORRELATE SAME , PLACE ON PLAN AND
 RECALCULATE THE CONNECTED LOAD. 106.1.1 FBC
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2010-01-04 Cont ID  
Sent By mawillia Date 2010-01-04 Time 12:59 Rev Time 0.00
Received By mawillia Date 2010-01-04 Time 12:36 Sent To  
Notes
2010-01-04 13:00:52*****APPROVED*****
  
 PLAN SHEETS A-1, A-2, AND E-2 WERE STAMPED, INITIALED,
 AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-02-11 Cont ID  
Sent By kstevens Date 2010-02-11 Time 10:31 Rev Time 0.00
Received By kstevens Date 2010-02-11 Time 10:31 Sent To  
Notes
2010-02-11 10:33:40SENT TO B-11.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-01-13 Time   Rev Time 0.00
Received By dpalmer Date 2009-12-28 Time 08:09 Sent To  
Notes
2009-12-28 08:09:20TO B4

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-03-02 Cont ID  
Sent By rregueir Date 2010-03-02 Time 16:35 Rev Time 0.00
Received By rregueir Date 2010-03-02 Time 16:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-01-13 Cont ID  
Sent By rregueir Date 2010-01-13 Time 16:18 Rev Time 0.00
Received By rregueir Date 2010-01-13 Time 13:59 Sent To  
Notes
2010-01-13 14:03:34REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. SHOW ON PLANS THE MEANS AND LOCATION OF CONDENSATE
 DISPOSAL IN ACCORDANCE WITH FBC-M 307.2.1.
  
 2. ELECTRICAL PLANS SHOW 3 HEAT PUMPS WHILE MECHANICAL
 PLANS SHOW 6 HEAT PUMPS PLUS 1 FUTURE 100% OUTSIDE AIR
 UNIT ON THE SAME PANEL. PLEASE COORDINATE MECHANICAL
 AND ELECTRICAL PLANS SHOWING HOW ALL APPLIANCES ARE TO
 BE PROVIDED WITH POWER IN ACCORDANCE WITH FBC-M 304.1.
  
 3. HEAT PUMP SCHEDULE NOTE #5 CALLS FOR CONDENSATE
 PUMPS AT EACH HEAT PUMP. NO CONDENSATE PUMPS ARE SHOWN
 ON MECHANICAL FLOOR PLANS OR ELECTRICAL PLANS. PLEASE
 CLARIFY IN ACCORDANCE WITH FBC-M 307.2.1 AND 304.1.
  
 4. OUTSIDE AIR CALCULATIONS STATE THEY ARE BASED ON
 TABLE 403.3 AND ASHRAE 62-01. THE ASHRAE
 STANDARDREFERENCED IS NOT A REFERENCED STANDARD IN THE
 2007 FBC. CALCULATIONS ARE NOT IN COMPLIANCE WITH FBC-M
 SECTION 403. THERE IS NO 3-HOUR DIVERSITY RULE ALLOWED
 IN SECTION 403. PROVIDE FULL VENTILATION RATES AS
 REQUIRED BY TABLE 403.3. ALSO, SOME OUTSIDE AIR
 CALCULATIONS ARE INACCURATE. A CORRIDOR AND RECEPTION
 AREA HAVE DIFFERENT VENTILATION RATE REQUIREMENTS. THE
 RATE OF 20 CFM IS OK FOR CORRIDOR #1 BUT NOT ENOUGH FOR
 THE RECEPTION AREA. CORRIDOR CALCULATIONS SHALL BE
 BASED ON SQUARE FOOTAGE AND NOT OCCUPANT LOAD BASED ON
 TABLE 403.3. PLEASE MAKE ALL NECESSARY CORRECTIONS TO
 COMPLY WITH 403.3 OR CHANGE REFERENCE TO ASHRAE
 62.1-2004 AND DEMONSTRATE COMPLIANCE WITH THAT
 STANDARD. DO NO REFERENCE BOTH 403.3 AND ASHRAE. SELECT
 ONE OR THE OTHER.
  
 5. SHOW ALL HYDRONIC PIPING LOCATIONS ON PLANS IN
 ACCORDANCE WITH FBC-M 1201.1 AND FBC-B 106.3.5.
  
 6. SUBMIT LOUVER PRODUCT APPROVAL DOCUMENTATION WITH
 WIND PRESSURE INFORMATIONAND INSTALLATION INSTRUCTIONS
 FOR BUILDING PLAN REVIEW IN ACCORDANCE WITH FBC-B
 106.3.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2010-01-05 Cont ID  
Sent By kstevens Date 2010-01-05 Time 09:39 Rev Time 0.00
Received By kstevens Date 2010-01-04 Time 16:58 Sent To  
Notes
2010-01-05 09:41:12 
  
 PASSED/PROVISO:
  
 REVISION REQUIRED.
  
 PER SECTION 712.2 A CHECK VALVE AND A FULL OPEN VALVE
 ON THE DISCHARGE SIDE OF THE CHECK VALVE ARE REQUIRED
 ON THE DISCHARGE PIPING OF THE PUMP.

Review Stop Z ZONING
Rev No 1 Status N Date 2009-12-30 Cont ID  
Sent By eschneid Date 2009-12-30 Time 16:18 Rev Time 0.25
Received By eschneid Date 2009-12-30 Time 16:18 Sent To  
Notes
2009-12-30 16:19:05PERMITS W/IN PAST 12 MONTHS DO NOT EXCEED 50% OF
 STRUCTURE VALUE.