Plan Review Details - Permit 09120427
Plan Review Stops For Permit 09120427
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-03-25 Cont ID  
Sent By rmcdouga Date 2010-03-25 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2010-03-24 Time 07:17 Sent To  
Notes
2010-03-25 09:51:47REVISIONS REQUIRED
  
 1) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. DOORS SHALL MEET
 LARGE MISSILE IMPACT AND COMPONENT/CLADDING PRESSURE
 REQUIREMENTS.
  
 2) SUBMIT TWO COPIES OF DETAIL OF UL X526.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-28 Cont ID  
Sent By rmcdouga Date 2009-12-28 Time 18:26 Rev Time 0.00
Received By rmcdouga Date 2009-12-28 Time 08:43 Sent To  
Notes
2009-12-28 08:43:172007 FBC W/2009 REVISIONS
 LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) INDICATE THE SUITE OR UNIT NUMBER ON THE PLANS AND
 APPLICATION.
  
 2) SPECIFY THE LEVEL OF ALTERATION PER 2007 FBC
 EXISTING BUILDING ON THE PLANS.
  
 3) SPECIFY THE TYPE OF CONSTRUCTION BASED ON THE 2007
 FBC DESIGNATIONS AS LISTED IN TABLE 602. TYPE IV
 CONSTRUCTION WHICH IS STATED ON THE PLANS IS HEAVY
 TIMBER CONSTRUCTION IN THIS TABLE. PLEASE CORRECT.
  
 4) PLEASE SEE TABLE 601 IN THE 2007 FBC FOR THE
 REQUIRED FIRE RESISTANCE RATINGS FOR BUILDING ELEMENTS.
 ALSO PLEASE NOTE THAT THE CODE NO LONGER USES THE ONE
 HOUR PROTECTED DESIGNATION. INSTEAD USING THE LETTERS A
 OR B AFTER THE CONSTRUCTION TYPE, WITH THE A BEING
 SIMILAR TO ONE HOUR PROTECTED.
  
 5) PROVIDE A LIFE SAFETY PLAN FOR THE ALTERED AREA.
 SPECIFY TRAVEL DISTANCES, COMMON PATHS OF TRAVEL, SHOW
 EXIT SIGNS, FIRE EXTINGUISHER LOCATIONS, ETC.
  
 6) SUBMIT A FIRE SPRINKLER PLAN.
  
 7) SPECIFY THE AMOUNT AND TYPES OF HAZARDOUS
 MATERIALS/CHEMICALS THAT WILL BE STORED AND USED IN THE
 BICARB AND WATER TREATMENT ROOMS. SUBMIT MATERIAL
 SAFETY DATA SHEETS FOR ALL HAZARDOUS MATERIALS. SHOW
 COMPLIANCE WITH 2007 FBC SECTIONS 307, 414 AND 415 AS
 APPLICABLE.
  
 8) INDICATE THE USE FOR THE ROOM WHICH HAS DOOR 27 THAT
 IS BEING BLOCKED BY WHEEL CHAIR STORAGE. CLARIFY WHY IS
 THIS DOOR IS BEING BLOCKED.
  
 9) SUBMIT PRODUCT APPROVALS FOR THE NEW EXTERIOR DOORS
 AS REQUIRED BY DCA RULE 9B-72. THE DESIGNER OF RECORD
 IS REQUIRED TO REVIEW AND APPROVE THE PRODUCT APPROVALS
 IN WRITING.
  
 10) SPECIFY THE REQUIRED COMPONENT AND CLADDING WIND
 LOAD PRESSURES ON THE PLANS FOR THE NEW EXTERIOR DOORS.
 FBC 1604.9
  
 11) SPECIFY THE WIND DESIGN DATA ON THE PLANS. FBC
 1603.1.4
  
 12) SHOW THAT THE NEW EXTERIOR DOORS WILL MEET IMPACT
 REQUIREMENTS OF FBC 1609.1.2.
  
 13) PROVIDE STRUCTURAL DETAILS FOR THE NEW EXTERIOR
 DOOR OPENINGS ON THE PLANS. FBC 1609.1
  
 14) PROVIDE DOOR BUCK ANCHORING DETAILS. FBC 1714.5.4.2
  
 15) THE DOOR SCHEDULE ON SHEET A-4 IS INCOMPLETE.
 PLEASE LIST ALL DOORS THAT ARE TAGGED INCLUDING THE
 EXISTING ONES.
  
 16) THE INFORMATION FOR DOOR 112 TO THE TOILET ROOM IS
 NOT LISTED AND DOOR 113 IS TO THE JANITOR CLOSET.
  
 17) PROVIDE A DETAIL OF THE ONE HOUR FIRE RATED WALL UL
 X536 ON THE PLANS.
  
 18) THE HANDRAIL DETAILS FOR THE STAIRS ON SHEET A-3C
 DO NOT COMPLY WITH FBC 11-4.9.4 (2).
  
 19) PROVIDE DETAILS OF EXTERIOR STAIRS SHOWING
 COMPLIANCE WITH FBC 11-4.9.
  
 20) FBC 11-4.8.5(2) REQUIRES HANDRAILS ON RAMPS THAT
 ARE NOT CONTINUOUS TO EXTEND 18" BEYOND THE SLOPE
 SEGMENT AND BE PARALLEL TO THE FLOOR OR GROUND SURFACE.
 (FLORIDA SPECIFIC)
  
 21) PROVIDE A DETAIL FOR THE RAMP SHOWING ALL
 DIMENSIONS. SHOW COMPLIANCE WITH FBC 11-4.8.3 (FL
 SPECIFIC EXCEPTION) THAT REQUIRES RAMPS THAT ARE PART
 OF A MEANS OF EGRESS TO BE A MINIMUM OF 44" WIDE.
  
 22) SHOW COMPLIANCE WITH FBC 11-4.8.4 (2) (FL SPECIFIC)
 WHICH REQUIRES LANDINGS ON RAMPS TO BE NOT LESS THAN 60
 INCHES CLEAR AND THE BOTTOM OF THE RAMP TO HAVE NOT
 LESS THAN 72 INCHES OF STRAIGHT AND LEVEL CLEARANCE.
  
 23) SHOW COMPLIANCE WITH FBC 11-4.8.5 (1) HANDRAILS AT
 RAMP SEGMENTS ARE REQUIRED TO BE CONTINUOUS AND FBC
 11-4.8.7 REQUIRING EDGE PROTECTION FOR RAMPS AND
 LANDINGS WITH DROP OFFS.
  
 24) SHOW COMPLIANCE WITH FBC 11-4.8..6 WHICH REQUIRES
 THE CROSS SLOPE OF RAMP SURFACES TO BE NO MORE THAN
 1:50. CHECK THE ELEVATIONS ON C1 FOR CROSS SLOPES.
  
 25) THE PLANS ARE REQUIRED TO BE SEALED WITH THE
 ARCHITECT'S IMPRESSION TYPE SEAL PER FAC 61G1- 16.001.
  
 26) THE LICENSE NUMBER OF THE ARCHITECTURAL FIRM IS
 REQUIRED TO BE IN THE TITLE BLOCK PER 61G1-16.004.
  
 27) PLEASE RESPOND TO REVIEW COMMENTS IN WRITING
 INDICATING HOW THE COMMENTS WERE ADDRESSED AND THE
 LOCATION OF THE CORRECTIONS ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-05-24 Cont ID  
Sent By btrobaug Date 2010-05-24 Time 12:02 Rev Time 0.00
Received By btrobaug Date 2010-05-24 Time 12:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-04-07 Cont ID  
Sent By btrobaug Date 2010-04-07 Time 09:05 Rev Time 0.00
Received By btrobaug Date 2010-04-07 Time 08:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-29 Cont ID  
Sent By dpalmer Date 2009-12-29 Time 10:39 Rev Time 0.00
Received By dpalmer Date 2009-12-29 Time 10:39 Sent To  
Notes
2009-12-29 10:39:35 
 ** DENIED REVIEW **
  
 **09120427
  
  
 1) NOTE: PLANS SUBMITTED UNDER TBD FOR CONTRACTOR. ONCE
 PLANS ARE FOUND CODE COMPLIANT AS WELL AS MEETING ALL
 ADOPTED STATUTORY REQUIREMENTS THE REVIEW WILL STILL BE
 IN FAILED STATUS UNTIL PROPERLY LICENSED CONTRACTOR HAS
 APPLIED FOR PERMIT.
 ** IMPORTANT
 THE APPLIED VALUE FOR THE COMPLETE SCOPE OF WORK IS
 VERY LOW. THE VALUE SHALL INCLUDE ALL DESIGN COSTS,
 LABOR, EQUIPMENT AND MATERIALS EVEN IF ANY OF THESE
 ITEMS ARE OWNER SUPPLIED.
 FBC 108.3 AS ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 2) NOTE: ARCHITECTURAL PLANS ARE NOT DATED AND SEALED
 AS REQUIRED. PLEASE SEE FLORIDA STATUTES 481.221 WHICH
 REQUIRES ARCHITECT TO DATE PLANS WHEN SIGNING AND
 SEALING.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.002
 WHICH REQUIRES SEAL TO BE AN *IMPRESSION TYPE SEAL*.
 THE USE OF A RUBBER STAMP IN LIEU OF THE IMPRESSION
 TYPE SEAL IS NOT PERMITTED.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 3) NOTE: ARCHITECTURAL TITLE BLOCK REQUIRES THE FIRM
 LICENSE NUMBER ALSO KNOW AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER TO BE LISTED ON TITLE BLOCKS.
 PLEASE SEE FAC61G1-16.04 WHICH REQUIRES THE NUMBER TO
 BE ON TITLE BLOCKS.
 PLEASE SEE FS 481.219 WHICH REQUIRES FIRM TO HAVE A
 CERTIFICATE OF AUTHORIZATION NUMBER.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 4) NOTE: ENGINEERING FIRM IS REQUIRED TO HAVE THE FIRM
 LICENSE NUMBER ALSO KNOWN AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER LISTED ON THE TITLE BLOCKS.
 PLEASE SEE FAC 61G15-23.002 WHICH REQUIRES INFORMATION
 ON TITLE BLOCKS.
 PLEASE SEE FS 471.025 WHICH REQUIRES THE C OF A NUMBER.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 5) NOTE: PLANS CONTAIN CODE REFERENCES WHICH NEED TO BE
 ADJUSTED. SEE SOME ITEMS FOR EXAMPLE: M-SHEETS WHICH
 LIST THE 2006 INTERNATIONAL MECHANICAL CODE WITH 2007
 GEORGIA AMENDMENTS. THE SCOPE OF WORK IS BEING DONE IN
 THE STATE OF FLORIDA. PLEASE ADJUST.
  
 THE PLANS LIST THE 2007 FBC FOR ELECTRICAL CODE HOWEVER
 BASED ON WHEN PERMIT APPLICATION IS MADE THIS WILL
 GOVERN WHICH NFPA-70 THE DESIGN IS REQUIRED TO MEET.
 THIS PERMIT APPLICATION WAS MADE AFTER OCTOBER 1ST
 ,2009. THIS PLACES THE PROJECT UNDER THE SECOND SET OF
 2009 SUPPLEMENTS ADOPTED UNDER THE 2007 FBC. AS OF
 10/1/09 THE ELECTRICAL IS REQUIRED TO BE 2008 NFPA-70 (
 NEC).
 ** PLEASE SEE 2008 NEC FOR SUBSTANTIAL CHANGES.
  
 THE NFPA-101A LISTED ON PLANS STATE 2004. THE STATE OF
 FLORIDA FIRE MARSHAL AND FLORIDA BUILDING CODE DOES NOT
 ADOPTED NFPA-101A.
 PLEASE SEE FAC 69A-60.004 WHICH ADOPTED THE 2006
 NFPA-101.
 PLEASE SEE FAC 69A-60.003 WHICH ADOPTED THE 2006
 NFPA-1.
  
  
 ** IT IS IMPORTANT TO KNOW THAT THERE WERE TWO
 SUBSTANTIAL REVISIONS TO THE 2007 FBC FOR ENERGY CODE
 REQUIREMENTS UNDER CHAPTER 13.
  
 6) NOTE: NO AUTOMATED LIGHTING CONTROLS SHOWN ON PLANS
 AS REQUIRED PER FBC 13-415.AB.1.1,.1.2 AND .1.3.
 NOT ALL AREAS ARE EXEMPT.
  
 7) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS WERE
 SUBMITTED. PLEASE SEE FBC 13-415.AB.5 FOR REQUIRED
 INTERIOR LIGHTING PERFORMANCE CALCULATIONS.
 MUST MEET MINIMUM PRESCRIPTIVE.
  
 8) NOTE: FIRE ALARM SYSTEM IS REQUIRED TO BE UNDER
 SEPARATE PERMITS HOWEVER BASE PLANS ARE REQUIRED
 MINIMUM DESIGN INTENT. PLEASE SEE FBC 11-4.28.1,.2 AND
 .3(4) FOR MINIMUM LOCATIONS, HEIGHTS AND LEVELS OF
 HORNS AND STROBE FOR ADA COMPLIANCE. THE STATE OF
 FLORIDA CHAPTER 11 FOR ACCESSIBILITY IS MORE STRINGENT
 THAN NFPA-72 AS NOTED ON FIRE ALARM NOTES.
  
 9) NOTE: THERE IS A NOTE #14 ON SHEET E-2 WHICH
 MENTIONS A MANUAL TRANSFER SWITCH HOWEVER NO
 INFORMATION SUCH AS PRODUCT SPECIFICATIONS ARE
 SUBMITTED. PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS.
 PLEASE PROVIDE INFORMATION ON ANY OF THE SYSTEMS
 BESIDES THE BATTERY BACKED UP EMERGENCY LIGHTS WILL
 ALSO REQUIRE BACK UP POWER. LEGALLY REQUIRED OR LIFE
 SAFETY SYSTEM SHALL BE BACKED UP BY ONE OF THE
 ACCEPTABLE BACK UP POWER STANDARDS.
 PLANS CONTAIN NOTES AND CODES WHICH INDICATE THAT PLANS
 SHOULD HAVE BEEN SUBMITTED AND REVIEWED BY ACHA. PLEASE
 SUBMIT THE DOCUMENTATION/LETTER FROM THEIR REVIEW OF
 THE SUBMITTED PLANS.
  
  
 NFPA-99, NFPA-70; 700,701, 110.3, 90.7, 517 PART III
 ETC
  
 10) NOTE: PLEASE INDICATE REDUNDANT GROUNDING PER
 517.13.
  
 11) NOTE: PLANS DO INDICATE SOME SORT OF DOOR CONTROLS
 SUCH AS ACCESS CONTROL SYSTEM HOWEVER NO SPECIFIC
 DETAILS IS PROVIDED. ACCESS CONTROL SYSTEMS ARE
 REQUIRED TO BE UNDER SEPARATE LOW VOLTAGE PERMITS.
 NFPA-101 CHAPTER 7 IS APPLICABLE WHEN SUBMITTING PLANS
 AND PERMIT APPLICATION FOR THE SCOPE OF WORK.
 PLEASE SEE 7.2 AND CALL ELECTRICAL REVIEW AND FIRE
 MARSHAL FOR QUESTIONS.
  
 12) NOTE: ALL EXTERIOR LIGHTING CONTROLS SHALL MEET FBC
 13-415.AB.1.4. THE PHOTO-CELL CONTROL SHOWN MUST BE
 CONNECTED TO BE THE OVER RIDE NOT THE TIME CLOCK. IF
 USING A TIME CLOCK AS THE OVER RIDE THEN IT MUST BE
 ASTRONOMICAL WITH A MINIMUM OF 10HR PROGRAMMING BACK
 UP.
  
 13) NOTE: WHEEL CHAIR STORAGE IS NOT PERMITTED IN FRONT
 OF ELECTRICAL ROOM DOOR. 240.24,110.26
  
 14) NOTE: PLEASE SEE 422.13 WHICH WERE REVISED UNDER
 THE 2005 NEC. ELECTRIC STORAGE TYPE WATER HEATERS ARE
 CONSIDERED CONTINUOUS LOADS.
 SEE CODE COMMENTARY IN HANDBOOK.
  
 15) NOTE: RISER INDICATES ADDING A NEW BREAKER TO THE
 EXISTING MAIN FEEDING NEW SERVICE EQUIPMENT HOWEVER NO
 LOAD CALCULATIONS WERE SUBMITTED FOR THE EXISTING
 SERVICE ADDING NEW.
 PLEASE SUBMIT LOAD ON EXISTING MAIN WITH NEW LOADS
 BEING ADDED.
 NEC 220
  
  
 IF THERE IS NO WORK FOR ELECTRICAL THEN PERMIT APPLIED
 IS TO BE VOIDED.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2010-01-05 Cont ID  
Sent By mgonzale Date 2010-01-05 Time 14:15 Rev Time 0.30
Received By mgonzale Date 2010-01-05 Time 14:15 Sent To  
Notes
2010-01-05 14:16:52COMMENTS:
  
 RE-STRIPING AND HANDICAP ACCESS AT BUILDING ENTRANCE
 WILL BE CERTIFIED BY EOR/ ARCHITECT.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-04-06 Cont ID  
Sent By mcarsill Date 2010-04-06 Time 09:47 Rev Time 0.00
Received By mcarsill Date 2010-04-06 Time 09:47 Sent To  
Notes
2010-04-06 09:48:35SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 SPRINKLER AND FIRE ALARM SYSTEM REMODEL.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 (561) 804-4709 PHONE
 (561) 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2009-12-31 Time   Rev Time 0.00
Received By mawillia Date 2009-12-30 Time 14:56 Sent To  
Notes
2009-12-30 16:14:21*****DENIED***** INCOMPLETE
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE
 WHICH IS BASED ON NFPA 101, LIFE SAFETY CODE, 2006
 EDITION AND NFPA 1, UNIFORM FIRE CODE, 2006 EDITION
 SHALL BE REFERENCED. THIS OCCUPANCY SHALL BE CLASSIFIED
 AS EXISTING HEALTH CARE (CHAPTER 19 OF NFPA 101).
  
 3. PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCE
 TO THE EXITS, LOCATION OF FIRE EXTINGUISHER(S), AND ANY
 OTHER DETAILS PERTINENT WITH THE LIFE SAFETY FEATURES
 OF THIS PROJECT LOCATION.
  
 4. SPECIFY THE INTERIOR FINISH MATERIALS IN TERMS OF
 CLASS A OR CLASS B.
  
 5. PROVIDE A LAYOUT OF THE FIRE SPRINKLERS HEADS FOR
 THE PROJECT SITE LOCATION. HOW WILL THE REMODEL HAVE AN
 AFFECT UPON THIS SYSTEM?
  
 6. ON THE FLOOR PLAN, SHEET A-1A, PLEASE EXPLAIN WHY
 THE DOOR IN ROOM 27 IS BLOCKED BY THE STOCKING OF THE
 WHEEL CHAIRS.
  
 7. PROVIDE THE PRESCRIPTIVE STRENGHTS FOR THE
 GUARDRAILS AND HANDRAILS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2010-03-25 Cont ID  
Sent By lwagner Date 2010-03-25 Time 12:44 Rev Time 0.00
Received By lwagner Date 2010-03-25 Time 12:44 Sent To  
Notes
2010-03-25 12:45:57NO GAS REVIEW REQUIRED.
 WATER HEATER IS CHANGED
 TO ELECTRIC WATER HEATER.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2010-01-06 Cont ID  
Sent By kstevens Date 2010-01-06 Time 16:04 Rev Time 0.00
Received By kstevens Date 2010-01-06 Time 16:04 Sent To  
Notes
2010-01-06 16:09:07DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING ARE
 REQUIRED INFORMATION FOR THE PERMIT. PLEASE SUBMIT THE
 FOLLOWING:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU
 G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2007 FUEL
 GAS CODE SECTION 304 & RESIDENTIAL CODE SECTION G2407.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2007 FUEL GAS CODE
 SECS. 502 THRU 505 & RESIDENTIAL CODE SECS. G2426 THRU
 G2429.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2.
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-05-19 Cont ID  
Sent By jgomez Date 2010-05-19 Time 10:28 Rev Time 0.00
Received By jgomez Date 2010-05-19 Time 10:28 Sent To  
Notes
2010-05-19 10:32:58SENT TO C-7.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-03-23 Cont ID  
Sent By lmartine Date 2010-03-18 Time 16:19 Rev Time 0.00
Received By lmartine Date 2010-03-18 Time 16:19 Sent To  
Notes
2010-03-23 16:20:14******************EXPEDITED *******************
 2ND ROUND
 C--16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2010-01-12 Time   Rev Time 0.00
Received By lmartine Date 2009-12-21 Time 17:28 Sent To  
Notes
2009-12-21 17:36:08******************EXPEDITED********************
  
2009-12-21 17:35:17C--24

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2010-04-08 Cont ID  
Sent By rkussner Date 2010-04-08 Time 16:28 Rev Time 0.00
Received By rkussner Date 2010-04-08 Time 16:28 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2010-01-05 Cont ID  
Sent By rkussner Date 2010-01-05 Time 16:43 Rev Time 0.00
Received By rkussner Date 2010-01-05 Time 16:43 Sent To  
Notes
2010-01-05 16:51:23***LANDSCAPE REVIEW FAILED***
  
 MUST APPLY FOR A SEPARATE LANDSCAPE PERMIT. SUBMIT 2
 COPIES OF THE APPROVED LANDSCAPE PLAN AND A CERTIFIED
 COST ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL
 LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO UNIT
 COST.
 MUST ALSO APPLY FOR A SEPARATE IRRIGATION PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-03-29 Cont ID  
Sent By hmoser Date 2010-03-29 Time 12:44 Rev Time 0.00
Received By hmoser Date 2010-03-29 Time 12:44 Sent To  
Notes
2010-03-29 12:53:59PASS PROVISO
 1) PLEASE REFER TO SECTION 606.2.1 SUPPLY AIR 2007 FBC
 (M)
 2) COMMENT # 3 WAS NOT ADDRESSED PLEASE REFER TO
 SECTION 301.12 WIND RESISTANCE , BE FOR 1ST INSPECTION
 .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2010-01-12 Cont ID  
Sent By rregueir Date 2010-01-12 Time 08:24 Rev Time 0.00
Received By rregueir Date 2010-01-11 Time 17:20 Sent To  
Notes
2010-01-11 18:08:34REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-3 SHOWS DUCT SMOKE DETECTOR INSTALLED ON THE
 RETURN DUCT WHILE PACKAGE UNIT SCHEDULE CALLS FOR
 DETECTOR IN THE SUPPLY. SMOKE DETECTOR SHALL BE
 INSTALLED ON THE SUPPLY DUCT IN ACCORDANCE WITH FBC-M
 606.2.1. COORDINATE FLOOR PLAN AND SCHEDULE TO SHOW THE
 CORRECT LOCATION (SUPPLY).
  
 2. ENGINEERING BUSINESS LICENSE NUMBER (CERTIFICATE OF
 AUTHORIZATION) SHALL APPEAR IN THE TITLE BLOCK IN
 ACCORDANCE WITH FFAC RULE 61G15-23.002. SIMILAR
 REQUIREMENTS EXIST FOR THE ARCHITECTURAL BUSINESS.
  
 3. PLAN SHOWS PACKAGE UNIT AND DUCTWORK LOCATED
 OUTDOORS. NO INFORMATION WAS PROVIDED REGARDING OUTDOOR
 INSTALLATIONS AND WIND RESISTANCE. OUTDOOR APPLIANCES
 AND DUCTWORK SHALL BE DEIGNED AND INSTALLED FOR WIND
 RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. PROVIDE
 MANUFACTURER'S DATA FOR THE WIND RESISTANCE CABILITIES
 OF THE PACKAGE UNIT WITH ENGINEERED INSTALLATION
 DETATIL FOR THE PACKAGE UNIT AND OUTDOOR DUCTWORK.
  
 4. PAGE M-1 MECHANICAL NOTE #7 CALLS FOR CONDENSATE TO
 BE DISCHARGED TO THE NEAREST DRAIN. CONDENSATE SHALL
 NOT DISCHARGE TO THE SANITARY SEWER SYSTEM PER CITY
 ORDINANCE. CONDENSATE SHALL DISCHARGE TO AN APPROVED
 LOCATION (SUCH AS A PERVIOUS AREA AT LEAST 12" FROM THE
 BUILDING) IN ACCORDANCE WITH FBC-M 307.2.1.
  
 5. MECHANICAL NOTES AND OUTSIDE AIR SCHEDULE REFERENCE
 THE INTERNATIONAL CODES AND GEORGIA AMENDMENTS. PLEASE
 CORRECT ALL CODE REFERENCES TO THE 2007 FLORIDA
 BUILDING CODE WITH 2009 SUPPLEMENTS, WHICH IS THE CODE
 IN EFFECT IN FLORIDA AS OF MARCH 1, 2009.
  
 6. FAN SCHEDULE NOTE #4 CALLS FOR "INLINE" EF-2 TO BE
 MOUNTED ON A ROOF CURB WHILE FLOOR PLAN SHOWS THE FAN
 INSIDE THE BUILDING. PLEASE CLARIFY. AN OUTDOOR FAN
 WILL BE SUBJECT TO THE WIND RESISTANCE REQUIREMENTS AS
 STATED IN COMMENT #3 ABOVE.
  
 7. PACKAGE UNIT SCEDULE, VAV SCHEDULE AND FLOOR PLANS
 DO NOT CORRESPOND. SEE EXAMPLES.
  
 EXAMPLE: TOTAL MAX CFM FOR ALL VAV SYSTEMS IS
 SIGNIFICANTLY LESS THAN THE 6000 BEING PROVIDED BY THE
 PACKAGE SYSTEM.
 EXAMPLE: VAV SCHEDULE GIVES A MAX CFM OF 900 FOR VAV-1
 WHILE THE FLOOR PLAN CALLS FOR 1900 CFM.
  
 THESE ARE EXAMPLES OF DISCREPANCIES AND NOT AN
 EXHAUSTIVE LIST. COORDINATE VOLUMES AND SIZES OF ALL
 EQUIPMENT AND AIR DISTRIBUTION COMPONENTS TO SHOW THE
 REQUIRED AIRFLOWS IN ACCORDANCE WITH FBC-M 603.1.
  
 8. OUTSIDE AIR INTAKE ON THE PACKAGE UNIT SHALL BE
 EQUIPPED WITH A MOTORIZED VOLUME DAMPER WITH SHUTOFF
 DAMPER CONTROLS IN ACCORDANCE WITH FBC-B 13-407.AB.3.3.
  
 9. ISOLATION ROOM 111 DOES NOT SHOW ANY MEANS FOR
 RETURN AIR. BALANCED RETURN AIR WITH MINIMAL PRESSURE
 DIFFERENTIALS IS REQUIRED. SHOW HOW BALANCED RETURN IS
 TO BE ACHIEVED IN THIS ROOM IN ACCORDANCE WITH FBC-M
 601.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-03-25 Cont ID  
Sent By lwagner Date 2010-03-25 Time 12:54 Rev Time 0.00
Received By lwagner Date 2010-03-25 Time 11:14 Sent To  
Notes
2010-03-25 13:02:39SEPERATE PERMIT REQUIRED FOR PLUMBING

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-01-06 Cont ID  
Sent By kstevens Date 2010-01-06 Time 13:41 Rev Time 0.00
Received By kstevens Date 2010-01-06 Time 13:41 Sent To  
Notes
2010-01-06 16:04:40DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 FUEL GAS
 FBC-2007 BUILDING
 FBC-2007 EXISTING BUILDING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH THE ARCHITECTURAL TITLE BLOCK. THE
 BUSINESS NUMBER (CERTIFICATE OF AUTHORIZATION) IS
 REQUIRED IN THE TITLE BLOCK. FAC 61G1-16.004(2) & FS
 481.2055.
  
 2. ALL SHEETS SIGNED, SEALED BY THE ARCHITECT OF RECORD
 SHALL BE SEALED BY AN IMPRESSION TYPE SEAL PER FAC
 61G1-16.00(1)(2) & FS 481.2055. ALSO THE DATE THE SEAL
 AND SIGNATURE ARE AFFIXED SHALL BE INDICATED UNDER THE
 SIGNATURE.
  
 2. ALL SHEETS WITH THE ENGINEERING TITLE BLOCK. THE
 CERTIFICATE OF AUTHORIZATION IS REQUIRED IN THE TITLE
 BLOCK OF EACH SHEET. FAC 61G15-23.002(2) & FA 471.025.
  
 3. THE TITLE BLOCK OF EACH SHEET AND THE APPLICATION
 SHALL INCLUDE THE SUITE NUMBER OF THE PROJECT. SECTION
 106.1.1.
  
 4. SHT A-1A ROOM 107 LOUNGE SINK SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE (GARBAGE DISPOSAL NOT ALLOW
 IN CLEARANCE AREA)
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE (CABINET DOORS NOT
 APPROVED)
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 5. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 SPOUT LOCATION
 C. 11-4.15.5 CLEARANCES AND CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIRED)
  
 6. SHT A-4 FINISH SCHEDULE INDICATES PAINT OVER WR GYP
 BOARD. SECTION 1210.2 REQUIRES THE SURFACE WITHIN 2
 FEET OF A WATER CLOSET UP TO 4 FEET ABOVE THE FLOOR TO
 BE SMOOTH, HARD & NONABSORBENT. A PAINTED WALL BOARD
 DOES NOT MEET THE "HARD" REQUIREMENT. PLEASE SHOW
 COMPLIANCE.
  
 7. SHT P-3 AN ISOMETRIC WATER RISER DIAGRAM IS REQUIRED
 FOR THE R.O. PIPING. SECTION 106.3.5.1.3. SHOW ALL PIPE
 SIZING, VALVES ETC.
  
 8. SHTS P-3 KEY NOTE #2 AND P-6 R.O. ROOM PIPING
 INDICATE SCHEDULE 80 PVC FOR THE R.O. PIPING. PER TABLE
 605.4 PVC IS NOT APPROVED FOR DISTRIBUTION PIPING.
  
 9. SHTS P-2 FLOOR PLAN & P-4 SANITARY RISER DIAGRAM
 INDICATE DRY HORIZONTAL VENT PAST THE FLOOR SINK IN
 BICARB ROOM 108. SECTIONS 905.3 & 905.4.
  
 10. SHT P-5 DETAIL 2 INDICATES A GAS WATER HEATER. A
 SEPARATE GAS PERMIT AND ARE REQUIRED. SEE GAS REVIEW
 FOR REQUIREMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2010-04-08 Cont ID  
Sent By lfranco Date 2010-04-08 Time 16:26 Rev Time 0.00
Received By lfranco Date 2010-04-08 Time 16:26 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2010-01-06 Cont ID  
Sent By lfranco Date 2010-01-06 Time 17:59 Rev Time 0.00
Received By lfranco Date 2010-01-06 Time 17:59 Sent To  
Notes
2010-01-06 18:05:02PLANNING AND ZONING: **** FAILED: MUST ADDRESS
 LANDSCAPE COMMENTS PRIOR TO APPROVAL, SUBMIT A SEPARATE
 LANDSCAPE PERMIT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING
 TEL: (561) 822-1443
 EMAIL: [email protected]