| 2009-12-29 10:39:35 | |
| | ** DENIED REVIEW ** |
| | |
| | **09120427 |
| | |
| | |
| | 1) NOTE: PLANS SUBMITTED UNDER TBD FOR CONTRACTOR. ONCE |
| | PLANS ARE FOUND CODE COMPLIANT AS WELL AS MEETING ALL |
| | ADOPTED STATUTORY REQUIREMENTS THE REVIEW WILL STILL BE |
| | IN FAILED STATUS UNTIL PROPERLY LICENSED CONTRACTOR HAS |
| | APPLIED FOR PERMIT. |
| | ** IMPORTANT |
| | THE APPLIED VALUE FOR THE COMPLETE SCOPE OF WORK IS |
| | VERY LOW. THE VALUE SHALL INCLUDE ALL DESIGN COSTS, |
| | LABOR, EQUIPMENT AND MATERIALS EVEN IF ANY OF THESE |
| | ITEMS ARE OWNER SUPPLIED. |
| | FBC 108.3 AS ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | |
| | 2) NOTE: ARCHITECTURAL PLANS ARE NOT DATED AND SEALED |
| | AS REQUIRED. PLEASE SEE FLORIDA STATUTES 481.221 WHICH |
| | REQUIRES ARCHITECT TO DATE PLANS WHEN SIGNING AND |
| | SEALING. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.002 |
| | WHICH REQUIRES SEAL TO BE AN *IMPRESSION TYPE SEAL*. |
| | THE USE OF A RUBBER STAMP IN LIEU OF THE IMPRESSION |
| | TYPE SEAL IS NOT PERMITTED. |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | ANY OTHER TRADE. |
| | |
| | 3) NOTE: ARCHITECTURAL TITLE BLOCK REQUIRES THE FIRM |
| | LICENSE NUMBER ALSO KNOW AS THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER TO BE LISTED ON TITLE BLOCKS. |
| | PLEASE SEE FAC61G1-16.04 WHICH REQUIRES THE NUMBER TO |
| | BE ON TITLE BLOCKS. |
| | PLEASE SEE FS 481.219 WHICH REQUIRES FIRM TO HAVE A |
| | CERTIFICATE OF AUTHORIZATION NUMBER. |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | ANY OTHER TRADE. |
| | |
| | 4) NOTE: ENGINEERING FIRM IS REQUIRED TO HAVE THE FIRM |
| | LICENSE NUMBER ALSO KNOWN AS THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER LISTED ON THE TITLE BLOCKS. |
| | PLEASE SEE FAC 61G15-23.002 WHICH REQUIRES INFORMATION |
| | ON TITLE BLOCKS. |
| | PLEASE SEE FS 471.025 WHICH REQUIRES THE C OF A NUMBER. |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | ANY OTHER TRADE. |
| | |
| | 5) NOTE: PLANS CONTAIN CODE REFERENCES WHICH NEED TO BE |
| | ADJUSTED. SEE SOME ITEMS FOR EXAMPLE: M-SHEETS WHICH |
| | LIST THE 2006 INTERNATIONAL MECHANICAL CODE WITH 2007 |
| | GEORGIA AMENDMENTS. THE SCOPE OF WORK IS BEING DONE IN |
| | THE STATE OF FLORIDA. PLEASE ADJUST. |
| | |
| | THE PLANS LIST THE 2007 FBC FOR ELECTRICAL CODE HOWEVER |
| | BASED ON WHEN PERMIT APPLICATION IS MADE THIS WILL |
| | GOVERN WHICH NFPA-70 THE DESIGN IS REQUIRED TO MEET. |
| | THIS PERMIT APPLICATION WAS MADE AFTER OCTOBER 1ST |
| | ,2009. THIS PLACES THE PROJECT UNDER THE SECOND SET OF |
| | 2009 SUPPLEMENTS ADOPTED UNDER THE 2007 FBC. AS OF |
| | 10/1/09 THE ELECTRICAL IS REQUIRED TO BE 2008 NFPA-70 ( |
| | NEC). |
| | ** PLEASE SEE 2008 NEC FOR SUBSTANTIAL CHANGES. |
| | |
| | THE NFPA-101A LISTED ON PLANS STATE 2004. THE STATE OF |
| | FLORIDA FIRE MARSHAL AND FLORIDA BUILDING CODE DOES NOT |
| | ADOPTED NFPA-101A. |
| | PLEASE SEE FAC 69A-60.004 WHICH ADOPTED THE 2006 |
| | NFPA-101. |
| | PLEASE SEE FAC 69A-60.003 WHICH ADOPTED THE 2006 |
| | NFPA-1. |
| | |
| | |
| | ** IT IS IMPORTANT TO KNOW THAT THERE WERE TWO |
| | SUBSTANTIAL REVISIONS TO THE 2007 FBC FOR ENERGY CODE |
| | REQUIREMENTS UNDER CHAPTER 13. |
| | |
| | 6) NOTE: NO AUTOMATED LIGHTING CONTROLS SHOWN ON PLANS |
| | AS REQUIRED PER FBC 13-415.AB.1.1,.1.2 AND .1.3. |
| | NOT ALL AREAS ARE EXEMPT. |
| | |
| | 7) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS WERE |
| | SUBMITTED. PLEASE SEE FBC 13-415.AB.5 FOR REQUIRED |
| | INTERIOR LIGHTING PERFORMANCE CALCULATIONS. |
| | MUST MEET MINIMUM PRESCRIPTIVE. |
| | |
| | 8) NOTE: FIRE ALARM SYSTEM IS REQUIRED TO BE UNDER |
| | SEPARATE PERMITS HOWEVER BASE PLANS ARE REQUIRED |
| | MINIMUM DESIGN INTENT. PLEASE SEE FBC 11-4.28.1,.2 AND |
| | .3(4) FOR MINIMUM LOCATIONS, HEIGHTS AND LEVELS OF |
| | HORNS AND STROBE FOR ADA COMPLIANCE. THE STATE OF |
| | FLORIDA CHAPTER 11 FOR ACCESSIBILITY IS MORE STRINGENT |
| | THAN NFPA-72 AS NOTED ON FIRE ALARM NOTES. |
| | |
| | 9) NOTE: THERE IS A NOTE #14 ON SHEET E-2 WHICH |
| | MENTIONS A MANUAL TRANSFER SWITCH HOWEVER NO |
| | INFORMATION SUCH AS PRODUCT SPECIFICATIONS ARE |
| | SUBMITTED. PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS. |
| | PLEASE PROVIDE INFORMATION ON ANY OF THE SYSTEMS |
| | BESIDES THE BATTERY BACKED UP EMERGENCY LIGHTS WILL |
| | ALSO REQUIRE BACK UP POWER. LEGALLY REQUIRED OR LIFE |
| | SAFETY SYSTEM SHALL BE BACKED UP BY ONE OF THE |
| | ACCEPTABLE BACK UP POWER STANDARDS. |
| | PLANS CONTAIN NOTES AND CODES WHICH INDICATE THAT PLANS |
| | SHOULD HAVE BEEN SUBMITTED AND REVIEWED BY ACHA. PLEASE |
| | SUBMIT THE DOCUMENTATION/LETTER FROM THEIR REVIEW OF |
| | THE SUBMITTED PLANS. |
| | |
| | |
| | NFPA-99, NFPA-70; 700,701, 110.3, 90.7, 517 PART III |
| | ETC |
| | |
| | 10) NOTE: PLEASE INDICATE REDUNDANT GROUNDING PER |
| | 517.13. |
| | |
| | 11) NOTE: PLANS DO INDICATE SOME SORT OF DOOR CONTROLS |
| | SUCH AS ACCESS CONTROL SYSTEM HOWEVER NO SPECIFIC |
| | DETAILS IS PROVIDED. ACCESS CONTROL SYSTEMS ARE |
| | REQUIRED TO BE UNDER SEPARATE LOW VOLTAGE PERMITS. |
| | NFPA-101 CHAPTER 7 IS APPLICABLE WHEN SUBMITTING PLANS |
| | AND PERMIT APPLICATION FOR THE SCOPE OF WORK. |
| | PLEASE SEE 7.2 AND CALL ELECTRICAL REVIEW AND FIRE |
| | MARSHAL FOR QUESTIONS. |
| | |
| | 12) NOTE: ALL EXTERIOR LIGHTING CONTROLS SHALL MEET FBC |
| | 13-415.AB.1.4. THE PHOTO-CELL CONTROL SHOWN MUST BE |
| | CONNECTED TO BE THE OVER RIDE NOT THE TIME CLOCK. IF |
| | USING A TIME CLOCK AS THE OVER RIDE THEN IT MUST BE |
| | ASTRONOMICAL WITH A MINIMUM OF 10HR PROGRAMMING BACK |
| | UP. |
| | |
| | 13) NOTE: WHEEL CHAIR STORAGE IS NOT PERMITTED IN FRONT |
| | OF ELECTRICAL ROOM DOOR. 240.24,110.26 |
| | |
| | 14) NOTE: PLEASE SEE 422.13 WHICH WERE REVISED UNDER |
| | THE 2005 NEC. ELECTRIC STORAGE TYPE WATER HEATERS ARE |
| | CONSIDERED CONTINUOUS LOADS. |
| | SEE CODE COMMENTARY IN HANDBOOK. |
| | |
| | 15) NOTE: RISER INDICATES ADDING A NEW BREAKER TO THE |
| | EXISTING MAIN FEEDING NEW SERVICE EQUIPMENT HOWEVER NO |
| | LOAD CALCULATIONS WERE SUBMITTED FOR THE EXISTING |
| | SERVICE ADDING NEW. |
| | PLEASE SUBMIT LOAD ON EXISTING MAIN WITH NEW LOADS |
| | BEING ADDED. |
| | NEC 220 |
| | |
| | |
| | IF THERE IS NO WORK FOR ELECTRICAL THEN PERMIT APPLIED |
| | IS TO BE VOIDED. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |