Plan Review Details - Permit 09120416
Plan Review Stops For Permit 09120416
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-02-01 Cont ID  
Sent By jwitmer Date 2010-02-01 Time 10:24 Rev Time 0.50
Received By jwitmer Date 2010-02-01 Time 10:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-23 Cont ID  
Sent By jwitmer Date 2009-12-23 Time 13:50 Rev Time 3.00
Received By jwitmer Date 2009-12-23 Time 09:49 Sent To  
Notes
2009-12-28 09:54:57BUILDING PLAN REVIEW
 PERMIT: 09120416
 ADD: 5300 EAST AVE
 CONT: R E ANDERSON CONSTRUCTION
 TEL: (561)719-3921
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 DEC. 28/ 2009
  
 1) PLEASE REFER TO THE LS1 SHEET, THE PLANS INDICATE A
 I-1 OCCUPANCY IN NEED OF SUPERVISED RESIDENTIAL
 ASSISTANCE VERSES A I-2 MEDICAL ASSISTANCE (NOT CAPABLE
 OF SELF-PRESERVATION). IT WOULD APPEAR TOUGHS IN NEED
 OF HOSPICE HELP WOULD BE IN NEED OF MEDICAL ASSISTANCE
 PLACING THE BUILDING IN A I-2 OCCUPANCY, PLEASE CORRECT
 PLANS. THIS REVIEW WILL WITH THE COMMENTS OF A I-2
 REVIEW.
  
 2) SHEET LS-1 INDICATES A SMOKE TIGHT TYPE WALL. PLEASE
 USE CODE TERMINOLOGY, SECTION 709 SMOKE BARRIERS AND
 710 FOR SMOKE PARTITIONS. PLEASE IDENTIFY THE RATINGS
 AS INDICATED NOT JUST A SMOKE TIGHT WALL.
  
 3) THE SECOND ISSUE WITH THIS REVIEW WILL BE ADDITIONAL
 INFORMATION WILL BE REQUIRED. SHEET LS-1 ALSO INDICATES
 THIS BUILDING AS A MIXED OCCUPANCY WITH A A-2 OCCUPANCY
 THE PLANS DO NOT INDICATE WHERE A RESTAURANT OR SIMILAR
 USAGE OCCURS. JUST INSIDE THE MAIN ENTRY IT APPEARS
 THERE IS A LARGE LOBBY OR WAITING ROOM. SHEET LS-1 AND
 A-4 DO INDICATE A INTEGRATED THERAPY BEREAVEMENT OFFICE
 THE QUESTION IS WOULD THESE WALLS REQUIRE EITHER A
 SMOKE OR FIRE RATING?
  
 3A) IS THIS LOBBY AREA A A-3 OCCUPANCY, TABLE 508.3.3
 WOULD REQUIRE A 1 HR SEPARATION WHEREAS:
  
 3B) IF THIS LOBBY AREA IS TO BE CONSIDERED A SPACE OF
 UNLIMITED AREA AS PER SECTION 407.2.1.
 THE ISSUE HERE IS 407.2.1(1) THE SPACES ARE NOT
 OCCUPIED FOR PATIENT SLEEPING UNITS, TREATMENT ROOMS,
 HAZARDOUS OR INCIDENTAL USE AREAS AS DEFINED IN SECTION
 508.2. THE INTEGRATED THERAPY BEREAVEMENT OFFICE WOULD
 NEED TO HAVE SMOKE PARTITION SEPARATION FOR WALLS PER
 407.3 ALSO SEE 407.3.1 FOR RATINGS OF CORRIDOR DOORS.
 IT WOULD ALSO APPEAR THE SMOKE BARRIER THAT IS ALREADY
 IDENTIFIED ON THE BACK WALL OF THIS WOULD STILL NEED TO
 BE IDENTIFIED AS A SMOKE BARRIER.
  
 4) SHEET A-2 & A-4 BOTH INDICATE A DOOR F-1 FUTURE
 CONTROL DOORS, ARE THESE DOOR PART OF THIS PERMIT? IF
 SO PLEASE PROVIDE ADDITIONAL INFORMATION, IF NOT WHY
 HAVE THEM ON THESE SHEETS? 106.1.2 ADDITIONAL
 INFORMATION REQUIRED. THERE ALSO APPEARS TO BE A
 DISCEPANCY A-2 & A-4 BOTH INDICATE A PAIR OF DOORS WITH
 SIDE LIGHTS WHERE AS A-4 DETAIL F-1 THERE IS ONLY 1
 DOOR DEPICTED.
  
 5) SHEET A-4 IT APPEARS PART OF A SMOKE BARRIER HAS
 BEEN REMOVED BETWEEN OFFICES 124 AND 126? THERE ALSO
 APPEARS TO BE A ROOM BETWEEN THESE TWO OFFICES THAT IS
 NOT LABELED AS TO USAGE, MAY REQUIRE ADDITIONAL FIRE
 RATING PER SECTION 508.2 & TABLE 508.2.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-02-02 Cont ID  
Sent By btrobaug Date 2010-02-02 Time 09:31 Rev Time 0.00
Received By btrobaug Date 2010-02-02 Time 09:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-28 Cont ID  
Sent By btrobaug Date 2009-12-28 Time 14:27 Rev Time 0.00
Received By btrobaug Date 2009-12-28 Time 13:21 Sent To  
Notes
2009-12-28 14:27:30 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 1} THE ARCHITECTURAL FIRM WHOSE TITLE BLOCK APPEARS ON
 THE PLANS, MUST SIGN AND SEAL THE PLAN PER
 481.221(1)(B)FS.
  
 2} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1*** SHOW COMPLIANCE ON THE PLAN. THIS
 CAN BE DEMONSTRATED ON THE PLANS INDICATING THE
 WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT
 CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES
 ON THE FIXTURE SCHEDULE TO CORRELATE WITH THE ONES IN
 THE CALCULATIONS.
  
 3} 13-415.1.AB.1.2 SPACE CONTROL.
 EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL
 HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY
 CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH
 MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED
 SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING.
 A. A CONTROL DEVICE SHALL BE INSTALLED THAT
 AUTOMATICALLY TURNS LIGHTING OFF WITHIN 30 MINUTES OF
 ALL OCCUPANTS LEAVING A SPACE, EXCEPT SPACES WITH
 MULTISCENE CONTROL, IN THE FOLLOWING:
 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS,
 LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE
 CLASSROOMS).
 2. CONFERENCE/MEETING ROOMS.
 3. EMPLOYEE LUNCH AND BREAK ROOMS.
  
 4} A SEPARATE PERMIT (LOW VOLTAGE) IS REQUIRED TO MOVE
 THE ALARM PANEL ON SHEET A4.
  
 5} PER 105.1 FBC AN ELECTRIC PERMIT IS REQUIRED FOR
 REMOVING AND TO SAFE OFF ALL CIRCUITS THAT MUST BE
 REMOVED FOR DEMOLITION
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-02-02 Cont ID  
Sent By mawillia Date 2010-02-02 Time 14:42 Rev Time 0.00
Received By mawillia Date 2010-02-02 Time 13:46 Sent To  
Notes
2010-02-02 14:29:56*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS LS1, A2, A4, A5, A7, A9, AND A10
 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2010-01-13 Cont ID  
Sent By mawillia Date 2010-01-13 Time 08:45 Rev Time 0.00
Received By mawillia Date 2010-01-12 Time 15:30 Sent To  
Notes
2010-01-13 06:08:02*****PARTIAL APPROVAL*****
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE OTHER TRADES PLAN EXAMINERS AS WELL AS THE
 FOLLOWING FIRE COMMENTS HAVE BEEN ADDRESSED:
  
 1. IN ADDITION TO THE LISTED FLORIDA BUILDING CODE,
 INDICATE THE OCCUPANCY TYPE (I.E. BUSINESS, MERCANTILE,
 HEALTHCARE, ASSEMBLY, STORAGE, RESIDENTIAL,
 DETENTIONAL/CORRECTIONAL, INDUSTRIAL, EDUCATIONAL) AS
 PER NFPA 101 - LIFE SAFETY CODE
  
 2. PLEASE EXPLAIN TERMS SMOKE WALL AND OR SMOKE TIGHT
 DOOR (30 MINUTE RATING) AS NOTED IN THE PLANS ON
 VARIOUS SHEETS.
  
 3. ON SHEET A-7, PLEASE EXPLAIN WHAT IS THE PURPOSE OF
 A FIRE ACTION CLOSET.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-01-26 Cont ID  
Sent By lmartine Date 2010-01-25 Time 16:47 Rev Time 0.00
Received By lmartine Date 2010-01-25 Time 16:47 Sent To  
Notes
2010-01-26 16:57:50******************EXPEDITED*****************
 2ND RUN
 B--1
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2010-01-26 Cont ID  
Sent By lmartine Date 2010-01-19 Time 16:47 Rev Time 0.00
Received By lmartine Date 2009-12-22 Time 13:49 Sent To  
Notes
2010-01-14 16:32:29********************EXPEDITED************************
 REQUEST SUBMITTED ON 1/13/10
2009-12-22 13:55:51B13
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2010-01-07 Cont ID  
Sent By rregueir Date 2010-01-07 Time 14:35 Rev Time 0.00
Received By rregueir Date 2010-01-07 Time 14:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2010-01-19 Cont ID  
Sent By lfranco Date 2010-01-19 Time 10:50 Rev Time 0.00
Received By lfranco Date 2010-01-19 Time 10:50 Sent To  
Notes
2010-01-19 10:52:10PLANNING AND ZONING: **** INTERIOR WORK ONLY, WORK DOES
 NOT EXCEED 50% VALUE *****
  
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved