| 2009-12-22 15:45:06 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | |
| | 1. PROVIDE BUILDING HEIGHT. DESIGN PRESSURES FOR |
| | BUILDINGS OVER 60FEET ARE REQUIRED TO BE DESIGNED USING |
| | ASCE7, FBC1609.1.1. DOCUMENTS PREPARED BY AN ENGINEER |
| | AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED |
| | ORIGINALS FAC61G15-23.002. |
| | |
| | 2. FOR THE SLIDING GLASS DOORS, CIRCLE WHICH GLASS |
| | OPTION/DESIGN PRESSURE APPLIES TO THE PROPOSED DOOR, |
| | SEE PAGES 2 AND 3 OF THE PRODUCT APPROVAL. |
| | |
| | 3. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R |
| | 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS |
| | ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE |
| | (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM |
| | /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF). |
| | GLAZED OPENINGS LOCATED MORE THAN 30' ABOVE GRADE SHALL |
| | MEET THE PROVISIONS OF THE SMALL MISSILE TEST. |
| | |
| | I WAS UNABLE TO LOCATE A PERMIT FOR IMPACT PROTECTION |
| | FOR THIS UNIT. A PERMIT WAS ISSUED FOR FOUR ACCORDION |
| | SHUTTERS, BUT THAT PERMIT WAS NEVER FINALED. IF THE |
| | PROPOSED SLIDING GLASS DOORS HAVE FBC COMPLIANT |
| | EXISTING IMPACT PROTECTION, PLEASE PROVIDE EVIDENCE OF |
| | IMPACT PROTECTION FOR THESE OPENINGS (PERMIT NUMBER |
| | WHICH HAS A FINAL INSPECTION). |
| | |
| | 4. PROVIDE A FLOOR PLAN WHICH SHOWS THE LOCATION OF THE |
| | PROPOSED INTERIOR IMPROVEMENT. PROVIDE A WALL FRAMING |
| | DETAIL FOR THE NEW OPENING. |
| | |
| | |