Plan Review Details - Permit 09120349
Plan Review Stops For Permit 09120349
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-01-28 Cont ID  
Sent By jwitmer Date 2010-01-28 Time 16:51 Rev Time 2.20
Received By jwitmer Date 2010-01-28 Time 16:51 Sent To  
Notes
2010-01-28 16:55:28COMMON PATH OF TRAVEL:
 2007 EXISTING BUILDING CODE
 705.3 NUMBER OF EXITS. THE NUMBER OF EXITS SHALL BE IN
 ACCORDANCE WITH THE APPROPRIATE SECTIONS OF THE FLORIDA
 FIRE PREVENTION CODE.
 NFPA 101- 392.5.3.2.
 COMMON PATH OF TRAVEL SHALL NOT BE LIMITED IN A
 SINGLE-TENANT SPACE WITH AN OCCUPANT LOAD NOT EXCEEDING
 30 PEOPLE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-22 Cont ID  
Sent By jwitmer Date 2009-12-22 Time 10:35 Rev Time 1.00
Received By jwitmer Date 2009-12-22 Time 10:35 Sent To  
Notes
2009-12-22 10:49:55BUILDING PLAN REVIEW
 PERMIT: 09120349
 ADD: 1920 PALM BEACH LAKES, SUITE 217
 CONT: TOMPSON CONSTRUCTION
 TEL: (954)552-1220
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 DEC. 22/ 2009
  
 1) TITLEBLOCK SBA WILL REQUIRE A CERTIFICATE OF
 AUTHORIZATION. 481.219 F.S. CERTIFICATE OF
 AUTHORIZATION. THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ARCHITECT PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 3) SHEET A-1 INDICATES A NEW 3'-0" DOOR W/ ELECTRIC
 STRIKE LEADING DOWN THE COORIDOR, PLEASE REVIEW SECTION
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITHIN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 4) PLEASE PROVIDE TTHE DISTANCE FOR COMMON PATH OF
 TRAVEL, SECTION 1014.3, IS THIS BUILDING FIRE
 SPRINKLERED?
  
 5) SHEET A-2 WHERE THE NEW DOOR IS BEING ADDED IN THE
 HALLWAY THIS DOOR BLOCKS THE VIEW OF THE EXIT LIGHT
 REQUIRING A SECOND EXIT LIGHT. 1006.1.1.
  
 6) SHEET A-2 DROPPED CEILING DETAIL INDICATES A SOFFIT
 WITH NOTTE TO SECURE TO THE BOTTOM OF THE CEILING.
 PLEASE PROVIDE THE TYPE OF FASTENERS. 106.1.2
 ADDITIONAL INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-10-22 Cont ID  
Sent By jleahy Date 2010-10-22 Time 09:05 Rev Time 0.00
Received By jleahy Date 2010-10-22 Time 09:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2010-02-04 Cont ID  
Sent By dpalmer Date 2010-02-04 Time 15:41 Rev Time 0.00
Received By dpalmer Date 2010-02-03 Time 16:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-28 Cont ID  
Sent By dpalmer Date 2009-12-28 Time 13:58 Rev Time 0.00
Received By dpalmer Date 2009-12-28 Time 13:58 Sent To  
Notes
2009-12-28 13:58:23 
 ** DENIED **
  
 1) NOTE: PLANS DO NOT CONTAIN ANY SPECIFIC RELEVANT
 CODES. ALL PERMIT APPLICATIONS AFTER OCTOBER 1ST, 2009
 ARE REQUIRED TO BE UNDER THE FOLLOWING CODES.
  
 2007 FBC W/ 2009 SUPPLEMENTS.
 2006 NFPA-101
 2008 NFPA-70
 2002 NFPA-72
  
  
  
 PER: FS 553.73, FAC 69A-3.012, 69A-60.004
  
 2) NOTE: PLANS LIST AN ENGINEERING FIRM AS THE
 RESPONSIBLE DESIGNERS HOWEVER THE ENGINEER HAS NOT
 SIGNED, DATED OR SEALED PLANS. PLEASE REVISE TITLE
 BLOCKS, OR HAVE ENGINEER SIGN, DATE AND SEAL PLANS AS
 REQUIRED. FS 471.025, FAC 61G15-23.002
  
 3) NOTE: PLEASE SHOW CIRCUITING FOR NEW ELECTRICAL AND
 COORDINATE WITH PANEL SCHEDULE.
 PLEASE SEE 408.4 OF THE NEC WHICH REQUIRES CIRCUITING
 TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED.
 THE USE OF *RECEPTACLES* OR *LIGHTING* IN GENERAL TERMS
 IS NOT PERMITTED. PLEASE SEE CODE COMMENTARY WHICH WAS
 ACTUALLY REVISED IN THE 2005 NEC.
  
 4) NOTE: RISER MENTIONS THE EXISTING FEEDERS ARE RATED
 FOR 600AMPS, NEW CONDUCTORS MUST MEET 310.16,240.4.
  
 5) NOTE: PLEASE VERIFY WITH FIRE MARSHAL THAT MORE THAN
 ONE DISCONNECT WILL BE PERMITTED FOR SINGLE TENANT.
  
 6) NOTE: PLEASE SEE 13-415.AB.1.1,.1.2 FOR MINIMUM
 PRESCRIPTIVE REQUIREMENTS FOR LIGHTING CONTROLS FOR NEW
 BEING INSTALLED. THIS WOULD BE ANY NEW LOCATION SUCH AS
 NEW BATH.
  
 7) NOTE: PLANS SEEM TO INDICATE A NEW TRANSFORMER OF
 SOME KIND AND NEW EQUIPMENT HOWEVER NO SPECIFIC DETAIL
 AND INFORMATION IS PROVIDED.
 450,240,310, ETC GIVEN IN GENERAL AS THERE IS NO
 INFORMATION.
  
 8) NOTE: IS THERE ANY FIRE ALARM SYSTEM IN THIS
 BUILDING? IS THERE EXISTING OR NEW DEVICES MEETING FBC
 11-4.28.1, .2 AND .3 FOR ADA LOCATED IN SPACE?
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-02-04 Cont ID  
Sent By mawillia Date 2010-02-04 Time 15:37 Rev Time 0.00
Received By mawillia Date 2010-02-04 Time 15:25 Sent To B
Notes
2010-02-04 15:36:44*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A-1 & A-2 WERE STAMPED,
 INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-12-29 Cont ID  
Sent By mawillia Date 2009-12-29 Time 13:38 Rev Time 0.00
Received By mawillia Date 2009-12-29 Time 13:14 Sent To  
Notes
2009-12-29 13:38:21*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. INDICATE IF THE BUILDING HAS A FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEM, AND TO WHAT EFFECT WILL THE
 SCOPE OF WORK HAVE ON THE/THESE SYSTEM(S).
  
 3. ON SHEET A-2, ONLY ONE (1) EXIT LIGHT IS SHOWN. SHOW
 THE LOCATION OF ADDITIONAL EXIT LIGHTS AND/OR EMERGENCY
 LIGHTS PERTINENT TO EGRESSING THE BUILDING.
  
 4. SHOW THE LOCATION OF THE FIRE EXTINGUISHER(S) WHICH
 SATIFY THE 75' TRAVEL DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-01-27 Cont ID  
Sent By lmartine Date 2010-01-26 Time 11:47 Rev Time 0.00
Received By lmartine Date 2010-01-26 Time 11:47 Sent To  
Notes
2010-01-27 11:51:32C--20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-12-29 Time   Rev Time 0.00
Received By kstevens Date 2009-12-17 Time 12:56 Sent To  
Notes
2009-12-17 12:57:16SENT TO C-16.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-12-22 Cont ID  
Sent By rregueir Date 2009-12-22 Time 15:19 Rev Time 0.00
Received By rregueir Date 2009-12-22 Time 15:17 Sent To  
Notes
2009-12-22 15:19:02**PROVISO**
  
 1. REVISE PLAN TO SHOW THE CFM OF THE EXHAUST FAN IN
 ACCORDANCE WITH FBC-M 403.3
  
 2. REVISE PLAN TO SHOW LOCATION OF EXHAUST DISCHARGE IN
 ACCORDANCE WITH FBC-M 401.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2010-02-01 Cont ID  
Sent By kstevens Date 2010-02-01 Time 13:59 Rev Time 0.00
Received By kstevens Date 2010-02-01 Time 13:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2010-01-05 Cont ID  
Sent By kstevens Date 2010-01-05 Time 14:01 Rev Time 0.00
Received By kstevens Date 2010-01-05 Time 14:01 Sent To  
Notes
2010-01-05 14:13:33DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 EXISTING BUILDING
  
 1. PER SECTION 401.4 A DESIGN PROFESSIONAL OR OWNER
 MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION.
  
 2. PER SECTION 106.3.5.1.3 A WATER ISOMETRIC RISER
 DIAGRAM IS REQUIRED. PLEASE SUBMIT THE RISER DIAGRAM
 SHOWING ALL PIPE SIZES, VALVES & (WHERE REQUIRED BY
 SECTION 604.9), WATER HAMMER ARRESTORS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2010-01-21 Cont ID  
Sent By astelly Date 2010-01-21 Time 17:35 Rev Time 0.00
Received By astelly Date 2010-01-21 Time 17:35 Sent To I
Notes
***NONE***