| 2009-12-22 10:49:55 | BUILDING PLAN REVIEW |
| | PERMIT: 09120349 |
| | ADD: 1920 PALM BEACH LAKES, SUITE 217 |
| | CONT: TOMPSON CONSTRUCTION |
| | TEL: (954)552-1220 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | DEC. 22/ 2009 |
| | |
| | 1) TITLEBLOCK SBA WILL REQUIRE A CERTIFICATE OF |
| | AUTHORIZATION. 481.219 F.S. CERTIFICATE OF |
| | AUTHORIZATION. THE TITLE BLOCK FOR ANY SHEET BEARING |
| | THE NAME OF AN ARCHITECT PRACTICING UNDER A FICTITIOUS |
| | NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING |
| | ARCHITECTURAL SERVICES, SHALL INCLUDE THE CERTIFICATE |
| | OF AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET. |
| | THIS MAY BE ADDED BY HAND. |
| | |
| | 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009 SUPPLEMENTS. |
| | |
| | PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING |
| | BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO |
| | WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS |
| | PERMIT. |
| | 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 403, 404 AND 405 OF THIS CODE. |
| | |
| | 3) SHEET A-1 INDICATES A NEW 3'-0" DOOR W/ ELECTRIC |
| | STRIKE LEADING DOWN THE COORIDOR, PLEASE REVIEW SECTION |
| | 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM |
| | MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC |
| | OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE |
| | FLOOR OR GROUND AREA WITHIN THE REQUIRED CLEARANCES |
| | SHALL BE CLEAR & LEVEL. |
| | |
| | 4) PLEASE PROVIDE TTHE DISTANCE FOR COMMON PATH OF |
| | TRAVEL, SECTION 1014.3, IS THIS BUILDING FIRE |
| | SPRINKLERED? |
| | |
| | 5) SHEET A-2 WHERE THE NEW DOOR IS BEING ADDED IN THE |
| | HALLWAY THIS DOOR BLOCKS THE VIEW OF THE EXIT LIGHT |
| | REQUIRING A SECOND EXIT LIGHT. 1006.1.1. |
| | |
| | 6) SHEET A-2 DROPPED CEILING DETAIL INDICATES A SOFFIT |
| | WITH NOTTE TO SECURE TO THE BOTTOM OF THE CEILING. |
| | PLEASE PROVIDE THE TYPE OF FASTENERS. 106.1.2 |
| | ADDITIONAL INFORMATION. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |