Review Stop E ELECTRICAL
Rev No 1 Status F Date 2010-01-06 Cont ID  
Sent By dpalmer Date 2010-01-06 Time 12:04 Rev Time 0.00
Received By dpalmer Date 2010-01-06 Time 12:04 Sent To  
Notes
2010-01-06 12:18:05ZONING HAS ELECTRICAL SITE PLANS FOR COORDINATION
 REVIEW.
2010-01-06 12:04:58 
 ** DENIED *
  
  
 1) NOTE: NEW PROOFING OVEN IN KITCHEN NOT SHOWING GFI
 OR GFI PROTECTION ON PANEL SCHEDULE. 210.8B3 ( 2002
 NEC)
  
 2) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16. (
 2002 NEC) SINCE THESE UNITS FALL UNDER THE DEFINITION
 OF A DWELLING UNIT WITH PERMANENT MEANS FOR COOKING ALL
 SMALL APPLIANCE LOADS ARE REQUIRED TO BE FIGURED PER
 220.16 BELOW. ALL DE-RATINGS ARE PERMITTED AND MAY BE
 ON SOME PANELS SUCH AS B4.
 PLEASE BE SURE TO ADJUST LOADS THROUGH TO THE L PANELS,
 H PANELS AND SERVICE.
  
  
 220.16 SMALL APPLIANCE AND LAUNDRY LOADS ??? DWELLING
 UNIT.
 (A) SMALL APPLIANCE CIRCUIT LOAD. IN EACH DWELLING
 UNIT, THE LOAD SHALL BE COMPUTED AT 1500 VOLT-AMPERES
 FOR EACH 2-WIRE SMALL-APPLIANCE BRANCH CIRCUIT REQUIRED
 BY 210.11(C)(1). WHERE THE LOAD IS SUBDIVIDED THROUGH
 TWO OR MORE FEEDERS, THE COMPUTED LOAD FOR EACH SHALL
 INCLUDE NOT LESS THAN 1500 VOLT-AMPERES FOR EACH 2-WIRE
 SMALL-APPLIANCE BRANCH CIRCUIT. THESE LOADS SHALL BE
 PERMITTED TO BE INCLUDED WITH THE GENERAL LIGHTING LOAD
 AND SUBJECTED TO THE DEMAND FACTORS PROVIDED IN TABLE
 220.11.
  
 3) NOTE: THERE ARE REVISIONS INDICATED WITH CLOUDS ON
 SOME SHEETS HOWEVER THERE IS NO ACTUAL CHANGE FROM
 PREVIOUS PLANS ON FILE. THERE ARE REVISION DATES ON
 TITLE BLOCK WITH NO CHANGES OR PLANS ALREADY ON FILE OR
 DATES WHICH ACTUALLY GO BACK BEFORE THE LATEST REVISION
 ON FILE. PLEASE SEE EXAMPLES BELOW.
  
 EXAMPLE: SHEET E301B RIGHT OUTSIDE NEXT TO DRIVE UP
 AREA WHICH HAS A CLOUD AROUND THE CIRCUITING TO H1-50.
 HOWEVER THIS IS THE SAME ON PLANS ALREADY IN RECORD
 FILE SET.
 EXAMPLE: PLEASE SEE SHEET E301A ELEVATOR MACHINE ROOM
 THERE IS A CLOUD NOTING A REVISION #13, HOWEVER THERE
 IS NO CHANGE FROM PREVIOUS PLANS
  
 ON FILE.
 EXAMPLE: SHEET 302 HAS NO CHANGES OR REVISIONS FROM
 PLANS ON FILE.
 EXAMPLE: SHEET 303 HAS NO CHANGES OR REVISIONS FROM
 PLANS ON FILE. LAST REVISION MADE TO SHEET WAS FROM
 DECEMBER 2007.
 EXAMPLE: SHEET E-401. THE LAST REVISION ON FILE IS
 DECEMBER 2007 HOWEVER THERE IS NOW A REVISION #9
 INDICATED AS JULY 2007. THIS DATE PRECEDES THE DECEMBER
 DATE?
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  
  
  
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmartine Date 2009-12-15 Time 19:08 Sent To  
Notes
2009-12-16 19:09:20GAVE TO DEWEY

Review Stop Z ZONING
Rev No 1 Status F Date 2010-01-07 Cont ID  
Sent By lfranco Date 2010-01-07 Time 10:27 Rev Time 0.00
Received By lfranco Date 2010-01-07 Time 10:27 Sent To E
Notes
2010-01-07 10:44:29PLANNING AND ZONING: **** FAILED - HOMEWOOD SUITES
 HOTEL - ELECTRICAL REVISIONS ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THE REVISED ("SITE PLAN"), SHEET E-601 SHOWING
 ELECTRICAL REVISIONS DEPICT A NEW (RELOCATED) LIGHTPOLE
 AT THE CORNER OF THE PARKING TERMINAL ISLAND AT
 SOUTHEAST CORNER OF THE PARKING LOT FOR HOMEWOOD
 SUITES. THIS LIGHT POLE LOCATION IS IN DIRECT CONFLICT
 WITH REQUIRED TREES SHOWN AT THAT LOCATION ON THE
 "ASBUILT" PLANS SUBMITTED TO THE PLANNING AND ZONING
 DEPARTMENT FOR THE MINOR PLANNED DEVELOPMENT AMENDMENT.
 REVISE ELECTRICAL PLANS TO SHOW REQUIRED TREES
 ACCORDINGLY. ALSO THERE WAS A LIGHT POLE JUST EAST OF
 THE TERMINAL ISLAND, BETWEEN THE ROW OF PARKING SHOWING
 FIVE (5) SPACES THAT IS NOW BEING OMITTED, REVISE PLANS
 SUBMITTED FOR THE MINOR AMENDMENT TO SHOW LATEST
 REVISIONS.
  
 IF YOU HAVE ANY QUESTION,
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL (561) 822-1443
 EMAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved