Plan Review Details - Permit 09120310
Plan Review Stops For Permit 09120310
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-01-14 Cont ID  
Sent By jwitmer Date 2010-01-14 Time 14:39 Rev Time 0.33
Received By jwitmer Date 2010-01-14 Time 14:39 Sent To  
Notes
2010-01-14 14:42:29NEW EXTERIOR DOOR PRODUCT APPROVAL:
 ARCH ALUMINUM NOA 04-1208.01
 OUTSWING-IMPACT
 =/- 70

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-12-16 Cont ID  
Sent By jwitmer Date 2009-12-16 Time 18:28 Rev Time 1.50
Received By jwitmer Date 2009-12-16 Time 17:00 Sent To  
Notes
2009-12-16 18:22:56BUILDING PLAN REVIEW
 PERMIT: 08080193/
 REVISION 09120310
  
 ADD: 118 S CLEMATIS ST
 CONT: FIVE STAR CONSTRUCTION
 TEL: (561)436-8508
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
  
 BUILDING PROVISO :
  
  
 1) SHEET 1.0A & 1.1A TWO FIRE SPRINKLER HEADS TO BE
 INSTALLED AT WITHIN 1???-0??? OF TEMPERED GLAZING IN
 THE 1 HR RATED STAIRWELL FIRST FLOOR GLAZING AND 2ND
 FLOOR GLAZING, A TOTAL OF FOUR SPRINKLER HEADS PER
 JOBSITE MEETING.
  
  
 2) BOTH DOOR AND WINDOW FRAMES WITHIN THE ONE-HOUR
 RATED STAIRWAY WILL NEED TO BE 45 MINUTE RATED PER
 TABLE 715.4 AND LABELED PER 715.4.5.4.
  
  
  
 3) SHEET 1.3A, NEW EXTERIOR STAIRWELL DOOR NEEDS
 PRODUCT APPROVALS TO BE SUBMITTED BEFORE BUCK
 INSPECTION. COMPONENTS AND CLADDING 1609.1.2.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2010-01-15 Cont ID  
Sent By dpalmer Date 2010-01-15 Time 11:59 Rev Time 0.00
Received By dpalmer Date 2010-01-15 Time 11:59 Sent To  
Notes
2010-01-15 12:00:17LOW VOLTAGE, FIRE ALARM, UNDER SEPARATE PERMITS.
 AS OF TODAY NO LOW VOLTAGE PERMIT HAS BEEN APPLIED FOR
 OR ISSUED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-12-29 Cont ID  
Sent By dpalmer Date 2009-12-29 Time 13:49 Rev Time 0.00
Received By dpalmer Date 2009-12-29 Time 13:49 Sent To  
Notes
2009-12-29 13:49:19 
 ** DENIED REVIEW **
  
 **REVISION
 ***IMPORTANT** A SEPARATE PROVISO WILL BE DONE FOR ALL
 CIRCUITING AND PANEL SCHEDULES. HOWEVER CODE COMPLIANCE
 FOR LOADS ON BRANCH CIRCUITS, PANELS, CIRCUITING, OVER
 CURRENT PROTECTION AND WIRING CAN NOT BE REVIEWED AT
 THIS TIME. ALL CIRCUITING AND WIRING ON-SITE WILL BE AT
 THE COMPLETE RISK OF DESIGNER AND CONTRACTOR. THIS IS
 PER THE REQUEST OF THE DESIGNER.
  
  
 1) NOTE: WHEN SUBMITTING PLANS PLEASE BE SURE TO SUBMIT
 TWO COMPLETE SETS. ONE SET MISSING ELECTRICAL PAGES.
  
 2) NOTE: CODE COMPLIANCE FOR LIGHTING CALCULATIONS CAN
 NOT BE VERIFIED AT THIS TIME. THERE IS LIGHTING
 FIXTURES NOT IDENTIFIED ON PLANS AND ON FIXTURE LEGEND.
 FOR EXAMPLE: ELECTRICAL PLANS DO NOT CONTAIN LIGHTING
 PERFORMANCE CALCULATIONS. THESE WERE LOCATED ON THE
 SHEET 1.2A HOWEVER ONLY FOR FIRST FLOOR LIGHTING. WHERE
 IS THE SECOND FLOOR LIGHTING PLANS FOR IDENTIFICATION
 AND CALCULATIONS? THE SECOND FLOOR LIGHTING PLANS ON
 ELECTRICAL SHEETS DO NOT CONTAIN FIXTURE
 IDENTIFICATION.
 FOR EXAMPLE: PLEASE SEE LIGHTING ON SHEET 1.2A AS THERE
 ARE FIXTURES SUCH AS THE 2X4 LAY-INS WHICH ARE
 IDENTIFIED WITH A LETTER *D* FOR THE FIXTURE YET THE
 FIXTURE LEGEND DOES NOT HAVE ANY FIXTURE *D*.
 FOR EXAMPLE: THE SECOND FLOOR LIGHTING PLANS DO NOT
 HAVE FIXTURES IDENTIFIED. THE FIXTURES SUCH AS THE
 2LIGHT FLUORESCENT IN COOLERS ARE ONLY BEING SHOWN AS
 2-LT FIXTURES. WHAT KIND OF TWO LIGHT FIXTURES? MAXIMUM
 WATTAGE? THESE CAN NOT BE ASSUMED. PLANS DO STATE ON
 1.2A THE PF OF 1.0 HOWEVER IF THE FIXTURE WATTAGE IS
 NOT LISTED THIS CAN NOT BE FIGURED.
 WHERE ARE THE TRACK LIGHTS AS SHOWN ON THE FIXTURE
 LEGEND? COULD NOT LOCATE THESE ON PLANS. THE FIXTURE IS
 SHOWN AS TYPE K AND THE ONLY LOCATION ON SHEET 1.2A IS
 IN THE CORNER OF MAIN EATING AREA. THIS SAME AREA ON
 E-SHEETS APPEAR TO BE A KEY PAD??
 PLEASE BE SURE TO REMEMBER IF COVE LIGHTING IS TRACK
 TYPE, THEN 30VA MINIMUM IS REQUIRED TO BE USED.
 13-415.2, 13-415.2.ABC.1.1, .1.2. PLEASE COMPLETE AND
 SUBMIT.
  
 3) NOTE: PLEASE COMPLETE CONTROLS FOR ALL LIGHTS ON
 PLANS. SOME AREAS SUCH AS KITCHEN LIGHTING ON 2.0E AND
 COOLER LIGHTS ON 2.1E DO NOT HAVE ANY CONTROLS?
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 4) NOTE: LIGHTING IN STAIRWAYS MUST MEET MINIMUM LEVELS
 FOR LIFE SAFETY. THE TWO MR-16 50WATT FIXTURES AS SHOWN
 DO NOT PROVIDED ENOUGH LIGHT FOR 10FT CANDLES.
 NFPA-101 7.8.1.3.
 WITH THE SCOPE OF WORK BEING DONE AT THIS LOCATION THIS
 WILL BE REQUIRED TO MEET CURRENT CODE.
  
 5) NOTE: NEW BAR AREAS WHERE SINKS ARE LOCATED WILL BE
 REQUIRED TO HAVE RECEPTACLES GFI/GFI PROTECTED. 210.8B2
 PLANS CONTAIN NOTES FOR FIRST FLOOR KITCHEN AND BAR
 AREAS ALONG WITH GFI IDENTIFICATION HOWEVER NOT SECOND
 FLOOR.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-28 Cont ID  
Sent By dpalmer Date 2009-12-28 Time 10:16 Rev Time 0.00
Received By dpalmer Date 2009-12-28 Time 10:16 Sent To  
Notes
2009-12-28 10:16:15** FAILED REVISION **
  
  
 1) NOTE: NO ELECTRICAL REVISIONS SUBMITTED. THERE ARE
 SUBSTANTIAL CHANGES TO THE REFLECTED CEILING PLANS
 HOWEVER NO PLANS SUBMITTED. COVER SHEET ALSO INDICATES
 THERE IS GOING TO BE ELECTRICAL SHEETS HOWEVER NONE IN
 SETS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-12-30 Cont ID  
Sent By mawillia Date 2009-12-30 Time 13:31 Rev Time 0.00
Received By mawillia Date 2009-12-30 Time 13:10 Sent To  
Notes
2009-12-30 13:31:11*****REVISION, DATED 11/28/2009, APPROVED*****
  
 REVISED PLAN SHEETS 1.0A, 1.1A, 1.2A, 1.3A, AND 1.4A
 WERE STAMPED, INITIALED, AND DATED.
  
 (ORIGINAL PERMIT #08080193)

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-01-13 Cont ID  
Sent By lmartine Date 2010-01-12 Time 11:10 Rev Time 0.00
Received By lmartine Date 2010-01-12 Time 11:10 Sent To  
Notes
2010-01-13 11:14:492ND REVIEW***************************EXPEDITED*********
 ******************
 C--10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-30 Cont ID  
Sent By kstevens Date 2009-12-30 Time 17:39 Rev Time 0.00
Received By kstevens Date 2009-12-15 Time 10:30 Sent To  
Notes
2009-12-16 10:30:37C--11
 ********************EXPEDITED********************

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-01-21 Cont ID  
Sent By rregueir Date 2010-01-21 Time 09:57 Rev Time 0.00
Received By rregueir Date 2010-01-21 Time 09:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-12-23 Cont ID  
Sent By rregueir Date 2009-12-23 Time 10:43 Rev Time 0.00
Received By rregueir Date 2009-12-23 Time 09:55 Sent To  
Notes
2009-12-23 10:43:14REVIEW #: 1ST (REVISION EXPANDING SCOPE TO INCLUDE
 MECH.)
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE 3.2M SHOWS A RETURN AIR GRILL IN THE KITCHEN.
 AS THIS SYSTEM IS NOT DEDICATED TO THE KITCHEN AREA,
 RETURN AIR FROM THE KITCHEN IS PROHIBITED IN ACCORDANCE
 WITH FBC-M 407.1. HOOD EXHAUST AND MAKE-UP AIR SYSTEMS
 SHALL BE BALANCED TO MAINTAIN PRESSURE DIFFERENTIAL
 REQUIREMENTS AS STATED IN FBC-B 13-409.1.ABC.3.6.1.
  
 2. PAGE 3.2M SHOWS A TYPE B GRILL BEHIND THE BAR
 PROVIDING 200 CFM SUPPLY. BASED ON THE "CEILING OUTLET
 SCHEDULE," THIS GRILL IS CAPABLE OF PROVIDING A MAXIMUM
 150 CFM. COORDINATE FLOOR PLANS TO FACILITATE A PROPER
 AIR BALANCE IN ACCORDANCE WITH FBC-M 603.1.
  
 3. PAGE 3.2M AND 3.3M EACH CONTAIN NOTES DESCRIBING THE
 PROPOSED WORK AS BEING "AS-BUILT HVAC 04NOV09." PLEASE
 CLARIFY HOW AS-BUILT DRAWINGS ARE BEING PRODUCED PRIOR
 TO ISSUANCE OF A MECHANIACL PERMIT FOR THE PROPOSED
 SCOPE OF WORK. A PERMIT SHALL BE SECURED PRIOR TO THE
 COMMENCEMENT OF ANY REGULATED WORK IN ACCORDANCE WITH
 FBC-B 105.1.
  
 4. PAGE 3.3M: RETURN AIR GRILL DESIGNATION AND CFM IS
 MISSING FOR RTU 4. PROVIDE MISSING INFORMATION IN
 ACCORDANCE WITH FBC-M 603.1.
  
 5. PAGE 3.2M SHOWS THE 12.5 TON RTU 1 AS EXISTING WHILE
 THE "SCOPE OF WORK" NOTES ON PAGE 3.3M CALL FOR RTU 1
 TO BE REPLACED WITH NEW. PLEASE COORDINATE NOTES AND
 FLOR PLANS TO ACCURATELY REFLECT THE PROPOSED SCOPE OF
 WORK IN ACCORDANCE WITH FBC-B 106.1.
  
 6. NEW RTU 1 SHALL BE PROVIDED WITH A MOTORIZED DAMPER
 AND SHUTOFF DAMPER CONTROLS ON THE OUTSIDE AIR INTAKE
 PER FBC-B 13-409.1.ABC.3.3.
  
 7. PAGE 3.3M SHOWS A 10" ROUND RETURN AIR TRANSFER DUCT
 FROM THE PREP/STORAGE ROOM. THIS TRANSFER ALSO CARRIES
 THE RETURN AIR FROM THE ADJACENT OFFICE. SIZE THIS
 TRANSFER DUCT TO MEET THE BALANCED RETURN EXCEPTIONS
 UNDER FBC-M 601.4 OR A FIELD TEST WILL BE REQUIRED
 PRIOR TO FINAL INSPECTION TO VERIFY PRESSURE
 DIFFERENTIAL OF 0.01 INCHES W/C.
  
 8. SEPARATE PLANS AND PERMIT APPLICATION SHALL BE
 SUBMITTED FOR PIZZA OVEN HOOD SYSTEM.
 NOTE: ARE ANY PROVISIONS BEING MADE FOR
 MAKEUP/COMBUSTION AIR FOR THE NEW PIZZA OVEN?
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-12-30 Cont ID  
Sent By kstevens Date 2009-12-30 Time 17:38 Rev Time 0.00
Received By kstevens Date 2009-12-30 Time 17:38 Sent To  
Notes
2009-12-30 17:39:21REVISION OK -- SHT 3.0P. -- NEW SHT 3.1P.

Review Stop Z ZONING
Rev No 1 Status P Date 2009-12-24 Cont ID  
Sent By aaponte Date 2009-12-24 Time 11:31 Rev Time 0.00
Received By aaponte Date 2009-12-24 Time 11:31 Sent To  
Notes
***NONE***