Plan Review Details - Permit 09120298
Plan Review Stops For Permit 09120298
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2010-02-23 Cont ID  
Sent By rmcdouga Date 2010-02-23 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2010-02-23 Time 10:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-21 Cont ID  
Sent By rmcdouga Date 2009-12-21 Time 16:16 Rev Time 0.00
Received By rmcdouga Date 2009-12-21 Time 09:34 Sent To  
Notes
2009-12-21 17:01:012007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE CLASSIFICATION OF WORK IS INCORRECT. THE PLANS
 AND APPLICATION INDICATE THAT THE SCOPE OF WORK IS TO
 BUILD A NEW GAZEBO. NOT AN ADDITION OR A LEVEL 3
 ALTERATION TO AN EXISTING STRUCTURE. PLEASE CORRECT.
  
 2) SPECIFY THE WIND DESIGN INFORMATION ON THE PLANS.
 FBC R301.2.1
  
 3) SPECIFY THE LIVE AND DEAD LOADS FOR THE ROOF AND
 FLOOR ON THE PLANS. FBC R301.4, 301.5 AND 301.6.
  
 4) SPECIFY THE HANGERS THAT WILL BE USED TO ATTACH THE
 2 X 6 FLOOR JOISTS TO THE 2 X 6 BAND. R301.1
  
 5) EVALUATE THE FLOOR LOADS WITH THE JOIST SIZE AND
 SPAN, AS WELL AS, TYPE OF LUMBER ( PLEASE SPECIFY) TO
 DETERMINE THAT THEY ARE ADEQUATE. R301.1
  
 6) EVALUATE THE SPAN OF SINGLE 2 X 6 BAND TO DETERMINE
 THAT IT IS CAPABLE OF SUPPORTING THE FLOOR LOADS.
 R301.1
  
 7) THE PLANS SPECIFY A 2 X 6 GUARDRAIL WITH A HEIGHT OF
 5'-3" AND A 2 X 4 RAILING @ 2' O.C. IS THIS CORRECT?
 PLEASE PROVIDE A DETAILED DRAWING THAT CLARIFIES THE
 DESIGN AND ATTACHMENT. FBC R 312
  
 8) THE PLANS HAVE A DETAIL OF THE DOUBLE 2 X 8 HEADER
 ON A 4 X 4 POST WITH A USP KCC-4 POST CAP. PLEASE
 CLARIFY HOW THE 2 X 8 HEADERS WILL BE CONNECTED
 TOGETHER AT THE TOP OF THE POST. PROVIDE DETAIL. R601.2
  
 9) A SIMPSON HETA 20 CONNECTOR IS SPECIFIED AT THE ROOF
 TRUSSES. THIS IS AN EMBED TYPE OF CONNECTOR USED WITH
 CONCRETE BEAMS. PLEASE CORRECT. R802.1.6.5
  
 10) A SIMPSON SWH 28-2 HANGER IS SPECIFIED AT THE
 DOUBLE 2 X 8S. I COULD NOT FIND THIS CONNECTOR IN THE
 SIMPSON CATALOG. PLEASE CLARIFY. R802.1.6.5
  
 11) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 SIMPSON AND USP CONNECTORS AS REQUIRED BY DCA RULE
 9B-72 OR SPECIFY THE FLORIDA PRODUCT APPROVAL NUMBERS
 FOR EACH OF THEM ON THE PLANS.
  
 12) SHOW COMPLIANCE WITH FBC R 803.2.3.1 FOR SHEATHING
 FASTENING ON THE PLANS, WHICH REQUIRES 8D RING SHANK
 NAILS.
  
 13) THE VALUE OF THE WORK IS LOW AND HAS BEEN ADJUSTED
 TO $ 4300.00 BASED ON ICC VALUATION TABLES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2010-02-17 Cont ID  
Sent By lmartine Date 2010-02-16 Time 09:02 Rev Time 0.00
Received By lmartine Date 2010-02-16 Time 09:02 Sent To  
Notes
2010-02-17 09:03:02GAVE TO ROBBIE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-21 Cont ID  
Sent By rmcdouga Date 2009-12-21 Time 16:16 Rev Time 0.00
Received By rmcdouga Date 2009-12-15 Time 08:39 Sent To  
Notes
2009-12-15 08:39:54TO ZONING

Review Stop Z ZONING
Rev No 1 Status P Date 2009-12-16 Cont ID  
Sent By kdfreema Date 2009-12-16 Time 08:20 Rev Time 0.00
Received By kdfreema Date 2009-12-16 Time 08:20 Sent To B
Notes
***NONE***