| 2009-12-22 14:50:57 | |
| | ** PROVISO ** |
| | |
| | ** THE FOLLOWING ITEMS ARE REQUIRED TO BE REVISED |
| | BEFORE ROUGH ELECTRICAL INSPECTIONS. THE LAST NOTE IS |
| | REQUIRED TO BE REVISED BEFORE FINAL. ** ALL REVISIONS |
| | SHALL BE SUBMITTED FOR REVIEW, STAMPING AND ON SITE FOR |
| | ELECTRICAL INSPECTOR TO AVOID RE-INSPECTION FEES. |
| | |
| | 1) NOTE: THE LS SHEETS INDICATE SOME CODES WHICH ARE |
| | INCORRECT. |
| | PLANS LIST ON SHEET LS THE FOLLOWING: |
| | |
| | 2004 EDITION OF NFPA-1, HOWEVER AS OF DECEMBER 31ST, |
| | 2008 FAC 69A-3.012, 69A-60.003 ADOPTED THE 2006 NFPA-1. |
| | 2005 NFPA-70 ( NATIONAL ELECTRICAL CODE) HOWEVER AS OF |
| | OCTOBER 1ST 2009, THE STATE ADOPTED THE 2008 EDITION. |
| | 2003 NFPA-101, HOWEVER AS OF DECEMBER 31ST, 2008 FAC |
| | 69A-3.012, 69A-60.004 ADOPTED THE 2006 NFPA-101. |
| | |
| | ** PLEASE BE SURE TO ADJUST: |
| | ** PLANS ALSO NEED TO REFLECT THE 2002 NFPA-72 NATIONAL |
| | FIRE ALARM CODE |
| | |
| | 2) NOTE: THE MINIMUM CANDELA LEVELS ON PLANS SHALL |
| | COMPLY WITH NFPA-72 AND FBC CHAPTER 11. PLEASE SEE FBC |
| | 11-4.28.3(4) WHICH REQUIRES ALL ADA AREAS TO HAVE A |
| | CANDELA LEVEL OF 75. |
| | PLEASE ALSO SHOW HORN DEVICES AS THEY ARE NOT CLEAR ON |
| | PLANS MEETING MINIMUMS FOR ADA. |
| | PLEASE LIST THE DEVICE HEIGHTS AND LOCATIONS TO MEET |
| | MINIMUM CODES IN AREAS FOR SCOPE OF WORK. IF EXISTING |
| | PLEASE SHOW. |
| | |
| | 3) NOTE: TO BE NOTED: ALL LOW VOLTAGE SYSTEMS SUCH AS |
| | SPEAKERS, DATA, PHONE SHALL BE UNDER SEPARATE PERMITS. |
| | |
| | 4) NOTE: TO BE NOTED: AS THIS IS AN EXISTING LOCATION |
| | AND CIRCUITING FOR LOCAL LIGHTING CAN NOT BE VERIFIED |
| | FOR CODE COMPLIANCE, PLEASE BE SURE TO SEE 700.12 OF |
| | NFPA-70. THIS REQUIRES EMERGENCY LIGHTING TO BE |
| | CIRCUITED TO THE LOCAL LIGHTING BRANCH CIRCUIT IN ANY |
| | ONE AREA. |
| | |
| | 5) NOTE: NO NEW LIGHTING IS PERMITTED TO BE INSTALLED. |
| | PLANS INDICATE ALL EXISTING TO REMAIN. IF ANY NEW |
| | LIGHTING IS PROPOSED, THEN LIGHTING PERFORMANCE |
| | CALCULATIONS ARE REQUIRED TO MEET PRESCRIPTIVE |
| | REQUIREMENTS PER FBC 13-415.AB.5. |
| | |
| | 6) NOTE: PANEL SCHEDULES SHALL BE REVISED BEFORE FINAL |
| | INSPECTION. THE USE OF *RECEPTACLES*, *LIGHTING* ETC IN |
| | OFFICES IS NOT ACCEPTABLE. PLEASE SEE REVISIONS MADE TO |
| | THE 2005 NEC IN SECTION 408.4 WHICH REQUIRES ALL |
| | CIRCUITS TO BE IDENTIFIED TO SPECIFIC ROOMS AND AREAS |
| | IN WHICH THEY FEED. THIS MAY BE ALPHA OR NUMERIC |
| | DESIGNATIONS SUCH AS * RECEPTACLES RMS 101,102, *LIGHTS |
| | EAST HALLWAY* ETC THE FOLLOWING IS TAKEN FROM THE CODE |
| | COMMENTARY. |
| | SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS SECTION. |
| | |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | |