| 2009-12-29 09:56:25 | ****ISSUED WITH PROVISO**** |
| | ****REVISION REQUIRED**** |
| | ****ISSUED AT CONTRACTOR'S RISK**** |
| | |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. THE APPLICATION STATES: "5/8" DRYWALL AND INSULATE |
| | 1ST FLOOR." PROVIDE A MORE COMPLETE SPECIFICATION FOR |
| | THE WORK INCLUDING SPECIFICATION FOR INSULATION FBC CH |
| | 13 (TYPE OF INSULATION AND R VALUE), DRYWALL ON WALLS |
| | OR CEILINGS OR BOTH? PROVIDE TOTAL SQUARE FOOT AREA FOR |
| | EACH, FLOOR PLAN MAY BE REQUIRED (SEE ITEM 6). |
| | |
| | 2. DOES THIS STRUCTURE HAVE ONE OR TWO UNITS? PAPA |
| | RECORDS SHOW TWO UNITS; PLEASE INCORPORATE THE |
| | REQUESTED INFORMATION INTO THE PLAN. IF THE FIRST AND |
| | SECOND FLOORS ARE DIFFERENT UNITS, FIRE SEPARATION IS |
| | REQUIRED (FBC R317.1). |
| | |
| | 3. THE APPLICATION STATES THAT DRYWALL/INSULATION IS ON |
| | THE FIRST FLOOR, NO INFORMATION PROVIDED REGARDING |
| | LOCATION OF STRUCTURAL ALTERATION (FIRST OR SECOND |
| | FLOOR). PLEASE REVISE. |
| | |
| | 4. FBC R313.2.1, INTERCONNECTED HARD WIRED SMOKE ALARMS |
| | REQUIRED UNLESS EXEMPTED, SEE FBC R313.2.1. SEPARATE |
| | PERMIT REQUIRED FOR ELECTRIC WORK. |
| | |
| | 5. DOES THE FIRST FLOOR INCLUDE AN ATTACHED GARAGE OR |
| | FOSSIL FUEL BURNING APPLIANCE AND A BEDROOM, FBC |
| | R313.4? CARBON MONOXIDE ALARM MAY BE REQUIRED (SEPARATE |
| | PERMIT REQUIRED FOR ELECTRIC WORK). |
| | |
| | 6. PROVIDE A REASONABLE VALUE FOR THE WORK PROPOSED OR |
| | PROVIDE A COST BREAKDOWN. VALUE APPEARS LOW; THIS |
| | SHOULD INCLUDE MARKET-VALUE LABOR AND MATERIALS. |
| | |
| | |