Plan Review Details - Permit 09120174
Plan Review Stops For Permit 09120174
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-15 Cont ID  
Sent By shill Date 2009-12-15 Time 14:34 Rev Time 0.00
Received By shill Date 2009-12-15 Time 14:34 Sent To  
Notes
2009-12-15 14:36:07***PROVISO***
  
 PROVIDE EVIDENCE (COPY OF SHUTTER PERMIT FLOOR PLAN) OF
 IMPACT PROTECTION FOR OPENINGS WHICH HAD A SHUTTER
 PERMIT. FOR ALL OTHERS, IMPACT PROTECTION IS REQUIRED.
 THIS MUST BE ADDRESSED BEFORE FIRST INSPECTION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-15 Cont ID  
Sent By shill Date 2009-12-14 Time 14:32 Rev Time 0.00
Received By shill Date 2009-12-14 Time 14:34 Sent To  
Notes
2009-12-15 14:33:56****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM
 /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF).
  
 THE SHUTTER PERMIT ON FILE SHOWS 4 OPENINGS ONLY.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-15 Cont ID  
Sent By shill Date 2009-12-15 Time 14:34 Rev Time 0.00
Received By shill Date 2009-12-15 Time 14:34 Sent To  
Notes
***NONE***