Plan Review Details - Permit 09120136
Plan Review Stops For Permit 09120136
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-16 Cont ID  
Sent By rmcdouga Date 2009-12-16 Time 15:52 Rev Time 0.00
Received By rmcdouga Date 2009-12-16 Time 15:52 Sent To  
Notes
2009-12-16 17:01:072007 FBC W/2009 REVISIONS
 BATHROOM ADDITION
  
 DENIED BY BUILDING
  
 1) THE SCOPE OF WORK THAT IS SHOWN ON THE DRAWINGS THAT
 WERE SUBMITTED IS FOR AN ADDITION TO INCREASE THE SIZE
 OF THE BATHROOM. THE PERMIT TYPE NEEDS TO BE CHANGED TO
 ADDITION SO THAT THE APPROPRIATE SUB-PERMITS, REVIEWS,
 AND INSPECTIONS WILL BE ASSIGNED.
  
 2) THE VALUE OF THE WORK LISTED ON THE APPLICATION FORM
 IS TOO LOW. IT SHOULD BE INCREASED TO A MINIMUM OF
 $3500.00 PER CURRENT ICC BUILDING VALUATION DATA.
  
 3) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 4) SPECIFY THE WINDSPEED AND WINDLOAD DESIGN
 INFORMATION ON THE PLANS. FBC R301.2.1
  
 5) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE ROOF
 SHINGLES, WINDOW AND IMPACT PROTECTION (STORM PANELS).
 FAC RULE 9B-72.
  
 6) SPECIFY THE SIZE AND TYPE (SINGLE HUNG, ETC.) OF THE
 BATHROOM WINDOW ON THE PLANS. THE BATHROOM WINDOW IS
 REQUIRED HAVE SAFETY GLAZING BY FBC R308.4.
  
 7) SPECIFY THE WALL AND CEILING INSULATION R-VALUES ON
 THE PLANS AS REQUIRED BY FBC R N1100.B
  
 8) SPECIFY THE TERMITE PROTECTION REQUIRED BY R320 ON
 THE PLANS.
  
 9) SPECIFY THE SIZE OF THE FOOTING, MINIMUM DEPTH AND
 THE NUMBER AND SIZE OF THE STEEL REINFORCING BARS ON
 THE PLANS. SEE FBC R403
  
 10) SPECIFY THE THICKNESS OF THE CONCRETE SLAB AND THE
 REQUIRED VAPOR RETARDER ON THE PLANS. SEE FBC R 506.
  
 11) SPECIFY THE SIZE OF WOOD HEADER ABOVE THE WINDOW.
 R603.6
  
 12) SHOW THE SIZE AND STEEL REINFORCEMENT FOR THE BOND
 BEAM AT THE TOP OF THE MASONRY KNEE-WALL. R609.2
  
 13) SPECIFY THE SIZE AND SPACING OF THE VERTICAL
 REINFORCING BARS IN THE MASONRY KNEE-WALL. R609.3
  
 14) SPECIFY THE ANCHORS AND SPACING FOR THE CONNECTION
 OF THE WOOD FRAME WALL TO THE MASONRY KNEE-WALL. R601.2
  
 15) SPECIFY THE TYPE OF LUMBER FOR THE RAFTERS. IF NOT
 #2 SOUTHERN YELLOW PINE (SYP) OR OTHER WOOD WITH
 SPECIFIC GRAVITY GREATER THAN 0.49 THEN THE FASTENER
 SPACING FOR THE ROOF SHEATHING IS REQUIRED TO BE 4 "
 O.C. IN ROOF ZONE 3 AND 6" O.C. IN THE OTHER ZONES. FBC
 R803.2.3.1.
  
 16) SPECIFY 8D RING SHANK NAILS FOR THE ROOF SHEATHING
 FASTENERS AS REQUIRED BY FBC R803.2.3.1.
  
 17) SPECIFY THE ROOF SLOPE AND ATTIC VENTILATION
 REQUIRED BY FBC R806.1.
  
 18) SHOW COMPLIANCE WITH FBC R703.6.3 WHICH REQUIRES A
 BOND BREAK BETWEEN THE STUCCO AND THE WATER-RESISTIVE
 BARRIER OVER THE FRAME WALL SHEATHING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-22 Cont ID  
Sent By btrobaug Date 2009-12-22 Time 12:06 Rev Time 0.00
Received By btrobaug Date 2009-12-22 Time 11:47 Sent To  
Notes
2009-12-22 12:06:15 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED. A PERMIT SHALL NOT BE ISSUED UNTIL FEES
 AUTHORIZED UNDER SECTION 553.80, FLORIDA STATUTES, HAVE
 BEEN PAID. 108.1 FBC..
  
 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2
 RESIDENTIAL FLORIDA BUILDING CODE.
  
 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). LOCATE SAME ON PLANS.
  
 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER
 106.1.3.FBC.
  
 5} AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS
 AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-12-17 Cont ID  
Sent By rmcdouga Date 2009-12-17 Time 10:30 Rev Time 0.00
Received By rmcdouga Date 2009-12-17 Time 10:30 Sent To  
Notes
2009-12-17 10:31:09NO MECHANICAL PLANS SUBMITTED. NO MECHANICAL CONTRACTOR
 LISTED ON APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-12-10 Cont ID  
Sent By kstevens Date 2009-12-10 Time 12:53 Rev Time 0.00
Received By kstevens Date 2009-12-10 Time 12:53 Sent To  
Notes
2009-12-10 12:56:45DENIED
 REFERENCE:
 FBC-2007 CHAPTER 1
  
 1. PLANS ARE CODE COMPLIANT, BUT PERMIT CAN NOT BE
 ISSUED UNTIL AN APPLICATION FOR THE ADDITION IS APPLIED
 FOR AND PERMIT ISSUED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-12-21 Cont ID  
Sent By eschneid Date 2009-12-21 Time 14:21 Rev Time 0.20
Received By eschneid Date 2009-12-21 Time 14:20 Sent To E
Notes
2009-12-21 14:33:42FAILED
  
 1) PERMITS REQUIRED FOR THE ADDITION OF SQUARE FOOTAGE
 TO THE STRUCTURE. THE ADDITION SHALL BE NO CLOSER THAN
 25 FEET TO THE FRONT PROPERTY LINE.
  
 2) PLEASE NOTE THAT THE PERMIT FOR THE ADDITION SHALL
 INCLUDE 2 SURVEYS THAT ARE LESS THAN ONE YEAR OLD.
  
 3) A TREE APPEARS TO BE IN THE AREA OF WORK ON THE
 AERIAL. PLEASE PROVIDE A PHOTO OF THE FRONT OF THE
 HOUSE. THE REMOVAL OR RELOCATION OF TREES REQUIRES A
 TREE ALTERATION PERMIT FROM THE PLANNING AND ZONING
 DEPARTMENT. NOTE ANY TREES AND.OR SHRUBS REMOVED SHALL
 BE REPLACED ON-SITE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.