| 2009-12-16 17:01:07 | 2007 FBC W/2009 REVISIONS |
| | BATHROOM ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE SCOPE OF WORK THAT IS SHOWN ON THE DRAWINGS THAT |
| | WERE SUBMITTED IS FOR AN ADDITION TO INCREASE THE SIZE |
| | OF THE BATHROOM. THE PERMIT TYPE NEEDS TO BE CHANGED TO |
| | ADDITION SO THAT THE APPROPRIATE SUB-PERMITS, REVIEWS, |
| | AND INSPECTIONS WILL BE ASSIGNED. |
| | |
| | 2) THE VALUE OF THE WORK LISTED ON THE APPLICATION FORM |
| | IS TOO LOW. IT SHOULD BE INCREASED TO A MINIMUM OF |
| | $3500.00 PER CURRENT ICC BUILDING VALUATION DATA. |
| | |
| | 3) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 4) SPECIFY THE WINDSPEED AND WINDLOAD DESIGN |
| | INFORMATION ON THE PLANS. FBC R301.2.1 |
| | |
| | 5) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE ROOF |
| | SHINGLES, WINDOW AND IMPACT PROTECTION (STORM PANELS). |
| | FAC RULE 9B-72. |
| | |
| | 6) SPECIFY THE SIZE AND TYPE (SINGLE HUNG, ETC.) OF THE |
| | BATHROOM WINDOW ON THE PLANS. THE BATHROOM WINDOW IS |
| | REQUIRED HAVE SAFETY GLAZING BY FBC R308.4. |
| | |
| | 7) SPECIFY THE WALL AND CEILING INSULATION R-VALUES ON |
| | THE PLANS AS REQUIRED BY FBC R N1100.B |
| | |
| | 8) SPECIFY THE TERMITE PROTECTION REQUIRED BY R320 ON |
| | THE PLANS. |
| | |
| | 9) SPECIFY THE SIZE OF THE FOOTING, MINIMUM DEPTH AND |
| | THE NUMBER AND SIZE OF THE STEEL REINFORCING BARS ON |
| | THE PLANS. SEE FBC R403 |
| | |
| | 10) SPECIFY THE THICKNESS OF THE CONCRETE SLAB AND THE |
| | REQUIRED VAPOR RETARDER ON THE PLANS. SEE FBC R 506. |
| | |
| | 11) SPECIFY THE SIZE OF WOOD HEADER ABOVE THE WINDOW. |
| | R603.6 |
| | |
| | 12) SHOW THE SIZE AND STEEL REINFORCEMENT FOR THE BOND |
| | BEAM AT THE TOP OF THE MASONRY KNEE-WALL. R609.2 |
| | |
| | 13) SPECIFY THE SIZE AND SPACING OF THE VERTICAL |
| | REINFORCING BARS IN THE MASONRY KNEE-WALL. R609.3 |
| | |
| | 14) SPECIFY THE ANCHORS AND SPACING FOR THE CONNECTION |
| | OF THE WOOD FRAME WALL TO THE MASONRY KNEE-WALL. R601.2 |
| | |
| | 15) SPECIFY THE TYPE OF LUMBER FOR THE RAFTERS. IF NOT |
| | #2 SOUTHERN YELLOW PINE (SYP) OR OTHER WOOD WITH |
| | SPECIFIC GRAVITY GREATER THAN 0.49 THEN THE FASTENER |
| | SPACING FOR THE ROOF SHEATHING IS REQUIRED TO BE 4 " |
| | O.C. IN ROOF ZONE 3 AND 6" O.C. IN THE OTHER ZONES. FBC |
| | R803.2.3.1. |
| | |
| | 16) SPECIFY 8D RING SHANK NAILS FOR THE ROOF SHEATHING |
| | FASTENERS AS REQUIRED BY FBC R803.2.3.1. |
| | |
| | 17) SPECIFY THE ROOF SLOPE AND ATTIC VENTILATION |
| | REQUIRED BY FBC R806.1. |
| | |
| | 18) SHOW COMPLIANCE WITH FBC R703.6.3 WHICH REQUIRES A |
| | BOND BREAK BETWEEN THE STUCCO AND THE WATER-RESISTIVE |
| | BARRIER OVER THE FRAME WALL SHEATHING. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |