| 2009-12-08 08:41:10 | DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | |
| | 1. SHT P1-103 GAS ISOMETRIC 2-1/2" GAS LINE REQUIRED TO |
| | EACH GB1 @ 1300 MBH PER TABLE 402.4(2). |
| | |
| | 2. SHT P1-103 GAS ISOMETRIC. PLEASE VERIFY ALL CUT |
| | SECTION MEASUREMENTS. THE REVISION DOES NOT SHOW A |
| | LENGTH FROM THE BRANCH LINE FOR GWH1 TO THE 1 INCH |
| | ELBOW TO THE OFFSET TO THE DRYER AND SHOWS 80 FEET FROM |
| | THE ELBOW TO THE DROP AT THE DRYER AND NO DROP LENGTH |
| | TO THE DRYER. THE LENGTHS APPEAR TO BE CORRECT ON THE |
| | PREVIOUS REVISION, 74' - 22' & 10'. HAVE THESE LENGTHS |
| | CHANGED? ALSO THE LENGTH TO THE GWH1 FROM THE GAS MAIN |
| | TO THE DROP IS SHOWN AS 23 FEET BUT SCALES OUT TO ABOUT |
| | 6 FEET MAX. PLEASE CLARIFY. |
| | |
| | 3. THE FIELD INSPECTOR HAS INFORMED ME THAT THE METER |
| | LOCATION HAS CHANGED AS WELL AS THE PIPING TO THE DRYER |
| | CHANGED TO RUN DOWN THE CORRIDOR. PLEASE VERIFY AND IF |
| | SO THESE CHANGES SHALL BE INDICATED ON THE REVISION FOR |
| | THE ISOMETRIC RISER DIAGRAM AND THE FLOOR PLAN. |
| | SECTIONS 106.1.1 & 401.1. IF THE METER LOCATION HAS |
| | CHANGED, THIS MAY LENGTHEN THE TOTAL DEVELOPED LENGTH |
| | AND MAY CALL FOR INCREASED PIPE SIZES DEPENDING ON THE |
| | DISTANCE TO THE MOST REMOTE APPLIANCE FROM THE METER. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |