Plan Review Details - Permit 09110611
Plan Review Stops For Permit 09110611
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-12-15 Cont ID  
Sent By jwitmer Date 2009-12-15 Time 16:32 Rev Time 0.77
Received By jwitmer Date 2009-12-15 Time 16:32 Sent To  
Notes
2009-12-15 16:47:10BUILDING PLAN REVIEW
 PERMIT: 09080581
 ADD: 400 N FLAGLER / TENANT B
 CONT: SHAKMAN HOSPITALITY
 TEL: (561)756-2553
  
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
  
 REVISION- REVIEW- 09110611
  
  
 1) SHEET A-4/ DETAIL# 1 & M1.01. PLANS INDICATE A
 PLENUM RETURN.
 BUILDING APPROVED WITH EXCEPTION!
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF REINSPECTION FEE(S).
  
 PLENUMS- MECHANICAL 602.2.1.5.1, SEPARATION REQUIRED.
 THE FOAM PLASTIC INSULATION SHALL BE SEPARATED FROM THE
 PLENUM BY A THERMAL BARRIER COMPLYING WITH SECTION
 2603.4 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2603.4 THERMAL BARRIER. EXCEPT AS PROVIDED FOR IN
 SECTIONS 2603.4.1 AND 2603.9, FOAM PLASTIC SHALL BE
 SEPARATED FROM THE INTERIOR OF A BUILDING BY AN
 APPROVED THERMAL BARRIER OF 0.5-INCH (12.7 MM) GYPSUM
 WALLBOARD OR EQUIVALENT THERMAL BARRIER MATERIAL THAT
 WILL LIMIT THE AVERAGE TEMPERATURE RISE OF THE
 UNEXPOSED SURFACE TO NOT MORE THAN 250??F (120??C)
 AFTER 15 MINUTES OF FIRE EXPOSURE, COMPLYING WITH THE
 STANDARD TIME-TEMPERATURE CURVE OF ASTM E 119. THE
 THERMAL BARRIER SHALL BE INSTALLED IN SUCH A MANNER
 THAT IT WILL REMAIN IN PLACE FOR 15 MINUTES BASED ON FM
 4880, UL 1040, NFPA 286 OR UL 1715. COMBUSTIBLE
 CONCEALED SPACES SHALL COMPLY WITH SECTION 717.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-12-14 Cont ID  
Sent By dpalmer Date 2009-12-14 Time 11:46 Rev Time 0.00
Received By dpalmer Date 2009-12-14 Time 11:46 Sent To  
Notes
2009-12-14 11:47:44REDLINED PLANS, TRACK LIGHTING TRACK MAY NOT EXCEED 3FT
 IN LENGTH. ANY TRACK OVER 3FT WILL CAUSE LIGHTING
 PERFORMANCE CALCULATIONS TO EXCEED ALLOWANCES.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-12-21 Time   Rev Time 0.00
Received By lmartine Date 2009-11-30 Time 09:36 Sent To  
Notes
2009-12-08 09:36:43B--17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-12-21 Cont ID  
Sent By rregueir Date 2009-12-21 Time 08:53 Rev Time 0.00
Received By rregueir Date 2009-12-21 Time 08:47 Sent To  
Notes
2009-12-21 08:53:45REVISED M1.01 DELTA 4

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-12-15 Cont ID  
Sent By kstevens Date 2009-12-15 Time 11:18 Rev Time 0.00
Received By kstevens Date 2009-12-15 Time 11:18 Sent To  
Notes
2009-12-15 11:19:27REVISIONS OK -- SHTS P1.01 & P2.01. -- REVISIONS 2 & 3
 NOT FOUND OR APPROVED FOR EITHER SHEET.