| 2009-12-08 13:40:04 | |
| | ** DENIED ** |
| | |
| | 1) NOTE: THE APPLIED VALUE FOR THE COMPLETE SCOPE OF IS |
| | VERY LOW. THE VALUE SHALL INCLUDE, ALL DESIGN COSTS, |
| | ALL EQUIPMENT, MATERIALS, LABOR ETC EVEN IF ANY OF |
| | THESE ITEMS ARE OWNER SUPPLIED. |
| | FBC 108.3 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 2) NOTE: PLANS SUBMITTED NEED TO STATE RELEVANT CODES |
| | IN WHICH DESIGN IS DONE. ALL PERMIT APPLICATIONS |
| | SUBMITTED OCTOBER |
| | 1ST, 2009 OR LATER ARE UNDER THE 2008 NEC. |
| | ** THERE IS A SUBSTANTIAL AMOUNT OF CHANGES IN THE 2008 |
| | NEC UNDER 690. |
| | |
| | 3) NOTE: PLANS SUBMITTED ARE REQUIRED TO CONTAIN THE |
| | DESIGNER OF RECORD INDICATED. PLEASE SEE FS 471.003 |
| | WHEN MEETING EXCEPTIONS FOR REQUIRED DESIGN |
| | PROFESSIONAL. IF MEETING EXCEPTION, DESIGN IS STILL |
| | REQUIRED TO BE DONE BY A LICENSED PROFESSIONAL PER FS |
| | 489. |
| | PLEASE BE SURE TO PRINT AND SIGN ON SHEETS. PLEASE CALL |
| | IF THERE ARE QUESTIONS. |
| | |
| | 4) NOTE: PLEASE SEE 310.15(A) AND (B) FOR DE-RATING FOR |
| | THE NUMBER OF CONDUCTORS AND THE DE-RATING FOR THE |
| | AMBIENT AIR EXPOSED TO DIRECT SUB LIGHT. PLEASE SEE |
| | 310.15(B)(2)(C). |
| | PLEASE ALSO SEE 690.7 AND PROVIDE CALCULATIONS FOR |
| | BOTH. |
| | |
| | 5) NOTE: PLEASE PROVIDE DOCUMENTATION FROM FLORIDA |
| | POWER AND LIGHT SO THEY ARE AWARE OF SYSTEM BEING |
| | CONNECTED INTO THE GRID. PLEASE CHECK WITH LOCAL |
| | SERVICE REP AND SEE FPL2009 SERVICE STANDARDS. |
| | ELECTRICAL RISER INDICATES A *BI-DIRECTIONAL METER* |
| | HOWEVER THE BASE BUILDING PLANS DO NOT INDICATE THIS. |
| | PLEASE COORDINATE ALL ONCE REVISED. |
| | |
| | 6) NOTE: PLEASE SEE 690.5 FOR GROUND FAULT, PLEASE |
| | INDICATE ON PLANS. |
| | |
| | 7) NOTE: DISCONNECTING MEANS FOR SERVICING EQUIPMENT ON |
| | ROOF. |
| | |
| | 8) NOTE: PLEASE PROVIDE LISTING ON ALL EQUIPMENT. SOME |
| | OF THE PRODUCT DATA SHEETS INDICATE LISTING FROM A NRTL |
| | HOWEVER NOT ALL. |
| | PLEASE SEE 690.4D, 110.3, 90.7 ETC |
| | PLEASE ALSO SEE OSHA FOR COMPLETE LISTING OF NATIONALLY |
| | RECOGNIZED TESTING LABORATORIES. |
| | |
| | 9) NOTE: PLEASE HAVE THE REVIEW STAMP AND SIGNATURE |
| | FROM THE RESPONSIBLE BASE BUILDING DESIGNER ON PLANS. |
| | PLEASE BE SURE IT IS THE ENGINEER OF RECORD ALONG WITH |
| | ORIGINAL SIGNATURE AND SHOP DRAWING REVIEW STAMP. |
| | PLEASE DO NOT STAMP ON THE BACK OF A BLANK SHEET. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |