Plan Review Details - Permit 09110494
Plan Review Stops For Permit 09110494
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-22 Cont ID  
Sent By jwitmer Date 2009-12-22 Time 13:11 Rev Time 0.00
Received By jwitmer Date 2010-01-05 Time 17:14 Sent To  
Notes
2009-12-22 13:14:03BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
 PLANS WERE SUBMITTED MISSING THE PRODUCT APPROVAL FOR
 STOREFRONT DOORS WILL REQUIRE APPROVAL BEFORE FRAMING
 INSPECTION. SHEET A-8.
  
 12/22/09 1:50 PM SPOKE WITH RAY FROM SASSER GLASS THE
 DOOR NOA FOR STOREFRONT IS NOA 06-0818.02, PRINTED 2
 SETS OF NOA'S AND INSERTED INTO THE SETS OF PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-12-02 Cont ID  
Sent By jwitmer Date 2009-12-02 Time 18:30 Rev Time 4.00
Received By jwitmer Date 2009-12-01 Time 17:00 Sent To  
Notes
2009-12-02 13:28:27BUILDING PLAN REVIEW
 PERMIT: 09110494
 ADD: 314 CLEMATIS ST
 CONT: LARREA AGUIRRE CONSTRUCTION, LLC
 TEL: (954)993-7301
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 DECEMBER 02/ 2009
 ACTION: DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2) SHEET A1:
 2A) PLEASE UPDATE CODE COMPLIANCE NOTES, THE CURRENT
 FIRE PREVENTION CODE THAT IS REFRENCED IN THE FBC
 CHAPTER 35IS THE 2007 NOT THE 2006 PLEASE UPDATE THE
 PLANS.
  
 2B) PLEASE DELETE THE BROWARD COUNTY AMENDMENTS, THIS
 IS A STATE WIDE CODE. ONLY CHAPTER 1 THE ADMINISTRATIVE
 CODE IS A LOCAL ADAPTION, WEST PALM BEACH AMENDMENTS.
  
 2C) OCCUPANT LOAD CALCULATION, REFRENECE SECTION 1004.2
 OF THE FBC. WHERE REQUIRED BY THE BUILDING OFFICIAL, AN
 APPROVED AISLE, SEATING OR FIXED EQUIPMENT DIAGRAM
 SUBSTANTIATING ANY INCREASE IN OCCUPANT LOAD SHALL BE
 SUBMITTED. WHERE REQUIRED BY THE BUILDING OFFICIAL,
 SUCH DIAGRAM SHALL BE POSTED. PLEASE INDICATE THE
 SEATING AND AISLE WIDTHS ON THE LIFE SAFETY PLAN.
  
 2D) SHEET A1 ALSO INDICATES WINDOW AND EXTERIOR DOOR
 PRESSURES, BUT THE PLANS FAILS TO PROVIDE THE WIND
 DESIGN CRITERIA THE PRESSURES WERE DERIVED FROM:
 1609.6.2 WIND DESIGN PROCEDURES
 1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 3) SHEET A2:
 3A) PLEASE INDICATE COMPLIANCE WITH ACCESSIBILITY
 REQUIREMENT:
 11-4.32.2 SEATING. IF SEATING SPACES FOR PEOPLE IN
 WHEELCHAIRS ARE PROVIDED AT FIXED TABLES OR COUNTERS,
 CLEAR FLOOR SPACE COMPLYING WITH SECTION 11-4.2.4 SHALL
 BE PROVIDED. SUCH CLEAR FLOOR SPACE SHALL NOT OVERLAP
 KNEE SPACE BY MORE THAN 19 INCHES (485 MM) (SEE FIGURE
 45).
  
 ALL FIXED SEATING IN PUBLIC FOOD SERVICE
 ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED UNDER THE
 BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES, AND IN
 ALL OTHER FACILITIES GOVERNED BY REFERENCE SECTION
 11-4.1 SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE
 WITH THE FOLLOWING REQUIREMENTS:
  
 (1) ALL AISLES ADJACENT TO FIXED SEATING SHALL PROVIDE
 CLEAR FLOOR SPACE FOR WHEELCHAIRS.
  
 (2) WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES OF
 SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52
 INCHES (1321 MM) WIDE.
  
 3B) PLEASE INDICATE COMPLIANCE WITH ACCESSIBILITY
 REQUIREMENT: 11-5.1 GENERAL. EXCEPT AS SPECIFIED OR
 MODIFIED IN THIS SECTION, RESTAURANTS AND CAFETERIAS
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 11-4.1 TO
 SECTION 11-4.35. WHERE FIXED TABLES (OR DINING COUNTERS
 WHERE FOOD IS CONSUMED BUT THERE IS NO SERVICE) ARE
 PROVIDED, AT LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF
 THE FIXED TABLES (OR A PORTION OF THE DINING COUNTER)
 SHALL BE ACCESSIBLE AND SHALL COMPLY WITH SECTION
 11-4.32 AS REQUIRED IN SECTION 11-4.1.3(18). IN
 ESTABLISHMENTS WHERE SEPARATE AREAS ARE DESIGNATED FOR
 SMOKING AND NONSMOKING PATRONS, THE REQUIRED NUMBER OF
 ACCESSIBLE FIXED TABLES (OR COUNTERS) SHALL BE
 PROPORTIONALLY DISTRIBUTED BETWEEN THE SMOKING AND
 NONSMOKING AREAS. IN NEW CONSTRUCTION, AND WHERE
 PRACTICABLE IN ALTERATIONS, ACCESSIBLE FIXED TABLES (OR
 COUNTERS) SHALL BE DISTRIBUTED THROUGHOUT THE SPACE OR
 FACILITY.
  
 11-5.2 COUNTERS AND BARS. WHERE FOOD OR DRINK IS SERVED
 AT COUNTERS EXCEEDING 34 INCHES (865 MM) IN HEIGHT FOR
 CONSUMPTION BY CUSTOMERS SEATED ON STOOLS OR STANDING
 AT THE COUNTER, A PORTION OF THE MAIN COUNTER WHICH IS
 60 INCHES (1525 MM) IN LENGTH MINIMUM SHALL BE PROVIDED
 IN COMPLIANCE WITH SECTION 11-4.32 OR SERVICE SHALL BE
 AVAILABLE AT ACCESSIBLE TABLES WITHIN THE SAME AREA.
  
 3C) PLEASE PROVIDE INFORMATION HOW THE VENTILATION
 SHAFT WILL BE TRANSFORMED INTO A MECHANICAL SHAFT AND
 LEAVE THE ELEVATOR CAR AND ELECTRICAL CONDUITS &
 EQUIPMENT ASSOCIATED WITH THTE ELEVATOR. HOW WILL THE
 ELEVATOR OPENING ON THE 2ND FLOOR BE HANDLED? PLEASE
 REVIEW COMMENTS FROM FIRE AND MECHANICAL AS TO THE
 REMOVAL OF EQUIPMENET NOT AASOCIATED WITH EXHAUST AIR.
 707.8 PENETRATIONS. PENETRATIONS IN A SHAFT ENCLOSURE
 SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 712 AS
 REQUIRED FOR FIRE BARRIERS.
  
 707.8.1 PROHIBITED PENETRATIONS. PENETRATIONS OTHER
 THAN THOSE NECESSARY FOR THE PURPOSE OF THE SHAFT SHALL
 NOT BE PERMITTED IN SHAFT ENCLOSURES.
  
 4) SHEET A-4 COVERED PATIO CEILING, THERE SEEMS TO BE A
 DISCREPANCY IN THE SYSTEMS BEING USED TO FINISH THE
 CEILING. THE PLANS INDICATE THE USE OF A PAREX EFIS
 CEILING SYSTEM, WITH WIRE LATH AND A DENSGLASS
 SHEATHING BOARD.
  
 4A) PLEASE PROVIDE PRODUCT APPROVAL FOR THE PAREX EFIS
 SYSTEM.
  
 4B) PLEASE PROVIDE PRODUCT APPROVAL FOR THE DENSGLASS
 SHEATHING BOARD.
  
 4C) WIRE LATH, THE PLANS CALL FOR THE WIRE LATH TO BE
 LAYERED BETWEEN THE DENSGLASS AND PAREX EFIS SYSTEM.
 PLEASE PROVIDE THE GAUGE OF WIRE AND TYPE OF WIRE LATH.
 PLANS INDICATE THE STANDARD ASTM C-1063 BUT THE
 DESIGNER NEEDS TO INDICATE THE TYPE OF MATERIAL. ALSO
 HOW THE WIRE LATH IS TO BE ATTACHED TO THE DENSGLASS
 AND NOT DIRECTLY TO THE METAL HI-HAT?
  
 INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 5) SHEET A5:
  
 5A) GENERAL NOTE# 2 PLEASE UPDATE NOTE TO THE CURRENT
 2007FBC W/ 2009 SUPPLEMENTS.
  
 5B) LOCATED AT THE PATIO FRONT ENTRY THERE (2) RAMPS
 ARE INDICATED. ADDITIONAL INFORMATION IS REQUIRED. THE
 PLANS INDICATE THE RISE TO BE 5 ????? TALL BUT THE RUN
 HAS NOT BEEN PROVIDED. THIS INFORMATION IS REQUIRED TO
 SE IF THE REQUIREMENTS OF 11-4.8.5 ARE REQUIRED.
  
 5C) DJ BOOTH- NO INFORMATION WAS PROVIDED IN THE
 ARCHITECTURAL PLANS ON THE HAND RAILS BUT S5 INDICATES
 THE USE OF ONLY (1) HANDRAIL. PLEASE REVIEW SECTION
 1009.10, 1012.5 & 11-4.9.4(2) HORIZONTAL EXTENSIONS.
  
 6) SHEET A-6 BOTH THE MEN???S AND LADIES RESTROOM ENTRY
 DOORS. THE PLANS INDICATE A 1???-0??? MANEUVERING
 CLEARANCE AT THE LATCH SIDE OF THE DOOR. PLEASE REVIEW
 11-4.13.6 AND FIGURE 25(A) WHICH REQUIRES A MINIMUM OF
 18??? AND A PREFERRED 24???.
  
 7) PRODUCT APPROVALS. FLORIDA ADMINISTRATIVE CODE RULE
 9B-72
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
  
 7A) EXTERIOR GLAZED FRONT ENTRY DOORS- NOT PART OF THE
 STOREFRONT NOA
 7B) WALL LOUVERS
 7C) STORM SHUTTERS / PANELS
 7D) EFIS SYSTEMS
 7E) DENSGLASS
 7F) A/C PRE-MANUFACTURED ROOF STANDS
  
 7G) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7H) 106.3.3 PRODUCT APPROVALS .THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7I) 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE
 DEBRIS IMPACT PROTECTION
 QUESTION# 13 RECOGNIZING SUCH CONCERNS AS ABSENTEE
 OWNERS, OR CASES WHERE LONGER TIME & EFFORT IS
 NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR
 IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR
 SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST BE
 SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS FOR
 REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE OFFICIAL NOTIFICATION
 BY THE NATIONAL WEATHER SERVICES OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 7J) STORM SHUTTERS & OR PANELS. PLEASE CIRCLE THE
 CONNECTION TYPE (HEADER / SILL) WITH THAT OF THE
 PRODUCT APPROVAL, TYPE OF ANCHOR TO BE INSTALLED AND
 SPACING FOR THE ASSOCIATED PRESSURES. FL BLD CODE 2004
 SECTION 106.3.3, 1609.1.4, 1714.5.1 & EXIST BUILD CODE
 507.3. PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT
 STORM
 BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 7K) 1511.7 ROOF MOUNTED MECHANICAL UNIT S SHALL BE
 MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES ABOVE THE
 ROOF SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH
 THE UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A
 MINIMUM CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE
 1511.7.
  
 7L) MECH. 301.13 WIND RESISTANCE MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 ON THE EQUIPMENT & THE SUPPORTS AS DETERMINED IN
 ACCORDANCE WITH THE FL BLDG CODE. THIS MAY BE
 ACCOMPLISHED BY DESIGN OR BY APPLICATION OF SECTION
 301.13.1.
  
 THIS WIND REQUIREMENT IS FOR THE ACTUAL ATTACHMENT OF
 THE EQUIPMENT TO THE STRUCTURE BELOW AS WELL AS THE
 EQUIPMENT ITSELF, (A/C ROOF TOP CONDENSERS, EXHAUST
 FANS).
  
 8) THE PLANS ARE DEFICIENT IN THE WALL & CEILING
 FINISHES. SHEET A1 DOES PROVIDE THE PARAMETERS FOR THE
 MATERIALS FOR FLAME SPREAD &SMOKE DEVELOPMENT BUT NOT
 THE ACTUAL FINISH MATERIALS. OUR CONCERNS ARE:
  
 8A) 803.4.1 DIRECT ATTACHMENT AND FURRED CONSTRUCTION.
  
 8B) 803.4.2 SET-OUT CONSTRUCTION.
  
 8C) 803.4.4 MATERIALS.
  
 8D) 803.6 TEXTILES.
  
 8E) 803.9.1 MATERIALS AND INSTALLATION. ACOUSTICAL
 MATERIALS COMPLYING WITH THE INTERIOR FINISH
 REQUIREMENTS OF SECTION 803 SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND
 APPLICABLE PROVISIONS FOR APPLYING INTERIOR FINISH.
  
 8F) 803.9.1.1 SUSPENDED ACOUSTICAL CEILINGS. SUSPENDED
 ACOUSTICAL CEILING SYSTEMS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF ASTM C 635 AND ASTM C
 636.
 PROVIDE DOCUMENTATION, INFORMATIONAL 106.1.1* W.P.B.
 ADMINISTRATIVE CODE/2004 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 8G) 806.3 FOAM PLASTIC. FOAM PLASTIC USED AS TRIM IN
 ANY OCCUPANCY SHALL COMPLY WITH SECTION 2604.2.
  
 8H) 806.4 PYROXYLIN PLASTIC. IMITATION LEATHER OR OTHER
 MATERIAL CONSISTING OF OR COATED WITH A PYROXYLIN OR
 SIMILARLY HAZARDOUS BASE SHALL NOT BE USED IN GROUP A
 OCCUPANCIES.
  
 8I) 806.5 INTERIOR TRIM. MATERIAL, OTHER THAN FOAM
 PLASTIC USED AS INTERIOR TRIM SHALL HAVE A MINIMUM
 CLASS C FLAME SPREAD AND SMOKE-DEVELOPED INDEX WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84, AS DESCRIBED IN
 SECTION 803.1. COMBUSTIBLE TRIM, EXCLUDING HANDRAILS
 AND GUARDRAILS, SHALL NOT EXCEED 10 PERCENT OF THE
 AGGREGATE WALL OR CEILING AREA IN WHICH IT IS LOCATED.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-12-29 Cont ID  
Sent By dpalmer Date 2009-12-29 Time 16:10 Rev Time 0.00
Received By dpalmer Date 2009-12-29 Time 16:10 Sent To  
Notes
2009-12-29 16:10:53** PROVISO **
  
 **REVISION REQUIRED
  
 ***IMPORTANT** A PROVISO IS BEING GIVEN FOR SOME
 CIRCUITING AND PANEL SCHEDULES.
  
  
 1) NOTE: PLEASE SEE CIRCUITING ON PLANS FOR ALL
 EMERGENCY LIGHTS. THESE MUST BE WIRED TO LOCAL LIGHTING
 BRANCH CIRCUIT PER 700.12F OR MEET EXCEPTION. SOME
 AREAS ON PLANS SUCH AS BACK HALLWAY, BATHROOMS WOULD
 NOT MEET EXCEPTIONS SO THEY MUST BE CIRCUITED TO LOCAL
 LIGHTING BRANCH CIRCUIT.
  
 2) NOTE: ALL OCCUPANCY SENSORS CONTROLLING LIGHTS IN
 MULTI-GANG BATHROOMS SHALL BE * FAIL SAFE ON* TYPE
 DEVICES. NFPA-101 7.8.1.2.2, FBC 1016.1.2
  
 3) NOTE: WALK IN COOLER DOES NOT INDICATE ANY LIGHTS?
 THIS IS NOT REQUIRED FOR THIS REVIEWER HOWEVER IF THERE
 IS GOING TO BE LIGHTING THEN CONTROLS NEED TO BE SHOWN.
 AREA OFF OF KITCHEN IDENTIFIED AS LIQUOR STORAGE ON A
 SHEETS DOES NOT HAVE AUTOMATED LIGHTING CONTROLS IN
 SPACE AS REQUIRED PER FBC 13-415.AB.1.2.
  
 4) NOTE: ALL 15/20AMP 120V RECEPTACLE LOCATIONS IN
 KITCHEN AREA ARE REQUIRED TO BE GFI OR GFI PROTECTED.
 CIRCUITS FOR EVEN DEDICATE EQUIPMENT IS REQUIRED TO
 HAVE PROTECTION.
 PLEASE SEE 2008 NEC 210.8B2
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-12-02 Cont ID  
Sent By dpalmer Date 2009-12-02 Time 18:17 Rev Time 0.00
Received By dpalmer Date 2009-12-02 Time 18:17 Sent To  
Notes
2009-12-02 18:17:41 
 ** DENIED**
  
  
 1) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING
 MINIMUM CODES FOR ALL APPLICATIONS MADE AFTER OCTOBER
 1ST, 2009
 PLANS HAVE LOCATIONS IN WHICH STATE THE 2004 FPC WHICH
 SHOULD BE 2007 W/2009 SUPPLEMENTS.
 PLANS CONTAIN NOTES FOR BOTH THE 2006 AND 2003
 NFPA-101.
 NOTE ON PLANS FOR BROWARD COUNTY?
 **PLEASE ADJUST CODES AS FOLLOWS FOR THIS REVIEWER AS
 APPLICABLE. SOME OTHER CODES MAY BE NOTED BY OTHER
 TRADES.
  
 THE 2008 NFPA-70 WAS ADOPTED ON OCTOBER 1ST,2009.
 PLEASE ADJUST DESIGNS FOR NEW REVISED CODES.
 2006 NFPA-101: ADOPTED 12/31/08 BY FAC 69A-60.004
 2002 NFPA-72: ADOPTED 12/31/08 FAC 69A-3.012
 2006 NFPA-1: ADOPTED 12/31/08 FAC 69A-60.003( TO BE
 NOTED BY FIRE REVIEW
 2007 FLORIDA FIRE PREVENTION CODE. ( TO BE NOTED BY
 FIRE REVIEW) PLANS STATE 2006 FFPC.
  
  
 2) NOTE: THIS IS A CHANGE IN OCCUPANCY UNDER THE
 EXISTING BUILDING CODE CHAPTER 9. PLEASE SEE 13-101.3
 FOR CHANGES IN OCCUPANCY FOR ENERGY CODE COMPLIANCE.
 PLEASE SEE THE FOLLOWING ITEMS WHICH WERE NOT SHOWN ON
 PLANS FOR CODE COMPLIANCE OR OTHER ITEMS NOT SUBMITTED.
 MINIMUM COMPLIANCE WITH FLORIDA BUILDING CODE CHAPTER
 13 HAS NOT BEEN MET.
 PLEASE SEE THE 2007 FBC W/2009 SUPPLEMENTS INCLUDING
 SECOND SET OF 2009 SUPPLEMENTS ADOPTED BY THE STATE ON
 OCTOBER 1ST, 2009.
  
 2A) NOTE: PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW OCCUPANCY. PLEASE SEE THE
 FOLLOWING SECTIONS AND CALL TO GO OVER ANY OF THESE
 SECTIONS.
 IN A MEETING HELD BEFORE PLANS WERE SUBMITTED THIS
 INFORMATION WAS GIVEN TO ARCHITECT PRESENT HOWEVER NO
 LIGHTING PERFORMANCE CALCULATIONS WERE SUBMITTED OR
 COMPLIANCE SHOWN ON PLANS.
 PLEASE SEE 13-101.1.3, 13-101.4.1, 13-400.0.B,
 13-400.0.B.4, 13-400.2.
  
 2B) NOTE: PLEASE SEE 13-415.AB.5 FOR INTERIOR LIGHTING
 PERFORMANCE CALCULATIONS REQUIRED. PLEASE KEEP IN MIND
 IF USING A FORM FROM THE FLORIDA BUILDING CODE FOR
 SPACE BY SPACE, THEN ONE FORM IS REQUIRED FOR EACH
 SPACE. IF USING FLA-COM THEN PLEASE BE SURE TO COMPLETE
 THE INPUT DATA REPORT WHICH IS PART OF THE FLA COM
 PROGRAM.
  
 ** IT IS TO BE NOTED THAT A FIXTURE SCHEDULE FOR ALL
 NEW UPGRADE FIXTURE IS REQUIRED IN ORDER TO REVIEW FOR
 LIGHTING ALLOWANCES.
 ** IT IS ALSO TO BE NOTED TO SEE APPENDIX SECTION FOR
 FIGURING TRACK LIGHTING.
  
 2C) NOTE: PLEASE SEE 13-415.AB.2 FOR EXTERIOR LIGHTING
 ALLOWANCES. ( SEE COMMENTS BELOW FOR CONTROLS)
  
 3) NOTE: PLEASE SUBMIT AND SHOW MINIMUM COMPLIANCE WITH
 FBC 13-415.AB.1.1,.1.2,.1.3 AND .1.4 FOR ALL LIGHTING
 CONTROLS.
 PLANS ARE NOT COMPLETE AT THIS TIME WITH LIGHTING
 CONTROLS FOR MAIN DINING AREAS INSIDE AND OUTSIDE.
 NO SWITCH LEGS, WIRING DIAGRAMS, OR METHOD OF CONTROLS
 ARE SHOWN FOR MOST AREAS.
 KITCHEN AREAS ARE NOT COMPLIANT AS ONLY STANDARD
 SWITCHES ARE SHOWN FOR COMPLIANCE.
 AUTOMATED LIGHTING CONTROLS FOR ALL LIGHTING IS
 REQUIRED.
 PLEASE SEE 13-415.AB.1.1 AND .1.2 FOR SPACE AND
 SEPARATE SPACES.
 PLEASE SEE 13-415.AB.1.3 FOR ADDITIONAL CONTROLS
 REQUIRED FOR ACCENT LIGHTING AND OTHER LIGHTING AS
 LISTED IN THE FBC.
 SEE NOTE #5 BELOW FOR NEW EXTERIOR LIGHTING CONTROLS
 REQUIRED.
 ** THIS WAS ALSO GONE OVER IN MEETING HELD BEFORE PLANS
 WERE SUBMITTED. IT WAS STATED THAT A WHOLE NEW SYSTEM
 WAS GOING TO BE INSTALLED YET THE PLANS DO NOT SHOWN
 ANY FOR MINIMUM CODE. THE DETAIL ON E-3 DOES NOT
 PROVIDE INFORMATION FOR AUTOMATED SHUT OFFS/OVER-RIDES,
 ZONES,
 ALL PRESENT SEEMED TO BE AWARE OF LIGHTING CONTROL
 REQUIREMENTS AND THEY WERE GOING TO BE INSTALLED. IF
 THERE ARE FURTHER QUESTIONS, IT IS RECOMMENDED DESIGNER
 CALL TO GO OVER.
  
 4) NOTE: PLANS INDICATE MANY FIXTURES AS EXISTING
 HOWEVER NO CONTROLS/SWITCH LEGS AS NOTED ABOVE ARE
 SHOWN. SOME OF THESE LOCATIONS SUCH AS ABOVE THE SIDE
 WALK AREA ARE ALL NOTED AS EXISTING HOWEVER THEY ARE
 NOT CURRENTLY LOCATED ON SITE AND HAVE NOT BEEN FOR A
 LONG TIME. THESE WOULD BE NEW.
 PLEASE COMPLETE PLANS WITH ALL SWITCHING, SWITCH LEGS
 FOR CONTROLS FOR MINIMUM CODE COMPLIANCE AS NOTED ABOVE
 FOR CURRENT CODE.
 PLEASE BE SURE TO SEE FBC 1016.1.2 AND NFPA-101
 7.8.1.2.2 FOR ANY OCCUPANCY SENSORS CONTROLLING ANY
 NORMAL OR EMERGENCY EGRESS LIGHTING.
  
 5) NOTE: PLEASE SEE SECTION 13-415.AB.1.4 FOR EXTERIOR
 LIGHTING. THE CODE ALLOWS TWO METHODS OF CONTROLS.
 PLEASE INDICATE WHICH ONE WILL BE DONE. THIS INCLUDE
 NEW OUTSIDE DINING AREA.
 CODE PERMITS ASTRONOMICAL TIME CLOCK WITH MINIMUM OF
 10HR PROGRAMMING BACK UP OR PHOTO-SENSOR CONTROLS. IF
 THE EXISTING TIME CLOCK CONTAINS THIS PLEASE SHOW ON
 THE DETAIL ON E3.
  
 6) NOTE: THERE ARE SOME AREAS ON PLANS WHICH ELECTRICAL
 INFORMATION IS NOT COMPLETED. AN EXAMPLE OF THIS IS THE
 SUSHI BAR WHICH INDICATES A NEW WATER FEATURE AND
 COOLER HOWEVER NO ELECTRICAL, OR CIRCUITING. IT IS NOT
 POSSIBLE TO REVIEW FOR CODE COMPLIANCE IF INFORMATION
 IS NOT PRESENT.
 THERE IS NO EQUIPMENT LEGEND ON PLANS.
 PLEASE SEE 210.8B2 FOR ALL 15A/20AMP RECEPTACLES IN
 KITCHEN AREAS WHICH ARE REQUIRED TO BE GFI/GFI
 PROTECTED. THIS IS WHETHER OR NOT THEY FEED COUNTER
 SPACE/TOP RECEPTACLES. PLEASE ALSO SEE BAR AREAS AND
 AREAS WHERE RECEPTACLES ARE LOCATED WITHIN SINK AREAS.
  
 7) NOTE: PLEASE SEE 2008 NEC 406.8 A AND B FOR WEATHER
 RESISTANT TYPE RECEPTACLES REQUIRED.
  
  
 8) NOTE: PLEASE SEE 220.43 (A)AND (B) FOR SHOW WINDOW
 CALCULATIONS AND TRACK LIGHTING LOAD CALCULATIONS TO BE
 SHOWN. ALL LIGHTING LOADS ARE FIGURED TOGETHER HOWEVER
 SECTION GIVEN REQUIRES ADDITIONAL LOADS.
 SHOW WINDOWS AND TRACK LIGHTING CAN NOT BE CONSIDERED
 AS GENERAL LIGHTING. PLEASE SHOW.
  
 9) NOTE: THE EXISTING RISER IS NOT CLEAR AND CONFUSING.
 HOW IS THERE TWO CT CANS SHOWN FOR ONE TENANT? THERE
 ARE TWO SHOWN AS Z GALLERIE HOWEVER THIS DOES NOT SEEM
 POSSIBLE.
 THE OTHER PART IS THE OTHER CT ALSO LABELED FOR Z
 GALLERIE IS SHOWN NOT FEEDING ANYTHING???
 PLEASE REVISE SERVICE AND RE-LABEL PER 230.2E, 215.5
 ETC.
  
 10) NOTE: PLEASE SHOW ALL FIRE ALARM AND HORN, STROBE
 OR HORN STROBE DEVICES MEETING MINIMUM CODE FOR ADA.
 PLANS SHOW SOME DEVICES HOWEVER NO LEVELS, HEIGHTS,
 MINIMUM CANDELA LEVELS OR DB LEVELS INDICATED.
 AS NOTED ABOVE THIS IS A CHANGE IN OCCUPANCY TO A
 HIGHER HAZARD PER THE FBC AND ANY DEVICES NOT CURRENTLY
 MEETING CURRENT CODES WILL BE REQUIRED TO BE UPDATED.
 PLEASE SEE FBC 11-4.28.1.,2 AND .3. IF THERE ARE
 QUESTIONS PLEASE CALL.
 EVEN THOUGH FIRE ALARM PERMIT AND PLANS WILL BE
 SEPARATE FS 633 REQUIRES ALL BASE BUILDING PLANS TO
 SHOW MINIMUM CODE COMPLIANCE DESIGN INTENT.
  
 11) NOTE: PLEASE SEE 408.4 IN THE NEC. THE PANEL
 SCHEDULE WILL BE REQUIRED TO BE UPDATED WITH ALL
 CIRCUITS. PLANS WILL ALSO BE REQUIRED TO HAVE ALL
 CIRCUITS LABELED AND COORDINATED WITH PANEL SCHEDULES.
 THE USE OR WORDING OF *LIGHTING* OR *RECEPTACLES* IS
 NOT ACCEPTABLE. THE FOLLOWING IS EXTRACTED DIRECTLY
 FROM THE NEC HANDBOOK.
 **
 SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.**
  
 ** AS THIS IS AN EXISTING SITUATION A PROVISO CAN BE
 SET UP TO SUBMIT COMPLETE REVISED PANEL SCHEDULES AND
 CIRCUITING ON PLANS FOR ALL EXISTING AND NEW BEFORE
 FINAL.
 ALL NEW IS REQUIRED TO BE COORDINATED AT THIS TIME FOR
 ALL NEW RECEPTACLES, LIGHTING AND EQUIPMENT.
 ALL REVIEW OF LOADING ON CIRCUITS WILL BE DONE ONCE
 PLANS HAVE BEEN REVISED AND COORDINATED WITH PANEL
 SCHEDULES.
  
 12) NOTE: PLEASE INDICATE CIRCUITING FOR ALL EMERGENCY
 LIGHTING AND EXIT LIGHTS PER 700.12F. ( LOCAL LIGHTING
 BRANCH CIRCUIT). THIS CAN BE DONE AS A NOTE ON PLANS AS
 MANY OF THESE ITEMS ARE EXISTING.
 NEW LOCATIONS NEED TO BE CIRCUITED AND SHOWN AT THIS
 TIME.
  
  
 13) NOTE: PLEASE SUBMIT PHOTO-METRIC LEVELS FOR EGRESS
 PATHS. THERE ARE LOCATIONS SUCH AS BOTH BATHROOMS WHICH
 DO NOT APPEAR TO MEET MINIMUM FOOT CANDLES REQUIRED BY
 THE LIFE SAFETY CODE.
 PLEASE SEE NFPA-101 7.8.1.3 AND 7.9.1.2, .2.2 FOR
 MINIMUM LEVELS UNDER EMERGENCY AND NORMAL CONDITIONS.
  
 14) NOTE: THE APPLIED VALUE FOR COMPLETE SCOPE OF WORK
 IS REQUIRED TO INCLUDE VALUE FOR THE FOLLOWING; DESIGN
 COST, ALL LABOR, ALL EQUIPMENT, ALL MATERIALS/BUILDING
 MATERIALS FOR ALL TRADES WHETHER OR NOT ANY OF THESE
 ITEMS ARE OWNER SUPPLIED. VALUE APPLIED IS LOW.
 ** FBC 108.3
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-12-23 Cont ID  
Sent By mawillia Date 2009-12-23 Time 15:29 Rev Time 0.00
Received By mawillia Date 2009-12-23 Time 15:05 Sent To  
Notes
2009-12-23 15:26:46*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A-1, A-2, A-4, A-5, AND E-2 WERE
 STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-12-03 Cont ID  
Sent By mawillia Date 2009-12-03 Time 16:03 Rev Time 0.00
Received By mawillia Date 2009-12-03 Time 12:35 Sent To  
Notes
2009-12-03 16:03:12*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. ON SHEET A-1UNDER FIRE PREVENTION CODE COMPLIANCE,
 IT IS INCORRECTLY STATED FLORIDA FIRE PREVENTION CODE
 2006 EDITION W/ BROWARD COUNTY AMENDMENTS.
  
 3. CORRECT VERBAGE ON SHEET A-5 SHOULD READ LIFE (NOT
 LIVE) SAFETY PLAN. CORRECT VERBAGE ON COVER SHEET ALSO.
  
 4. PROVIDE INFORMATION ON THE FABRICS/MATERIALS AS IT
 RELATES TO FLAME PROPAGATION PERFORMANCE CRITERIA.
  
 5. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR THE
 PROJECT SITE LOCATION.
  
 6. DOES THE COVERED PATIO HAVE FIRE SPRINKLER
 PROTECTION?
  
 7. PROVIDE A LAYOUT OF THE FIRE ALARM DEVICES FOR THE
 PROJECT SITE LOCATION.
  
  
 CAPT. MICHALE A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-12-30 Cont ID  
Sent By kstevens Date 2009-12-30 Time 18:58 Rev Time 0.00
Received By kstevens Date 2009-12-30 Time 18:58 Sent To  
Notes
2009-12-30 19:09:05 
  
  
 PASSED/PROVISO:
  
 REVISION REQUIRED:
  
 SHT P-2 GAS RISER DIAGRAM. PER TABLE 402.4(2) 1-1/2
 INCH PIPE IS REQUIRED UP TO THE STOVE, (TOTAL 589,000
 BTU'S), AND 1-1/4 INCH PIPE IS REQUIRED UP TO THE
 CHARBROILER, (TOTAL 320,000 BTU'S). ALL SHUT OFF VALVES
 SHALL ALSO BE SIZED ALSO PER TABLE 402.4(2). THE SOV
 FOR THE STOVE SHALL BE 1 INCH, AND THE FRYERS SHALL BE
 3/4". ALL OTHERS SHALL BE MINIMUM 1/2 INCH.
  
 THE MANUF. SPECIFICATION SHEETS FOR THE SALAMANDER
 INDICATE TOTAL BTU'S AT 66,000, BUT THE ISOMETRIC RISER
 DIAGRAM INDICATE 30,000. PLEASE CLARIFY, EITHER CHANGE
 THE RISER DIAGRAM OR SUBMIT MANUF. SPECIFICATION SHEETS
 TO REFLECT THE BTU LOAD INDICATED ON THE RISER DIAGRAM.
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-12-01 Cont ID  
Sent By kstevens Date 2009-12-01 Time 18:42 Rev Time 0.00
Received By kstevens Date 2009-12-01 Time 18:42 Sent To  
Notes
2009-12-01 18:47:19DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION FOR REVIEW:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU
 G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2007 FUEL GAS CODE
 SECS. 502 THRU 505 & RESIDENTIAL CODE SECS. G2426 THRU
 G2429.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2.
  
 9. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 10. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 11. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-21 Cont ID  
Sent By jgomez Date 2009-12-21 Time 11:09 Rev Time 0.00
Received By jgomez Date 2009-12-21 Time 11:09 Sent To  
Notes
2009-12-21 11:14:24SENT TO C32. ***EXPEDITED***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-12-09 Time   Rev Time 0.00
Received By lmartine Date 2009-11-19 Time 13:33 Sent To  
Notes
2009-11-24 13:38:19C--6
 ****************EXPEDITED*********************

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2010-01-07 Cont ID  
Sent By rregueir Date 2010-01-07 Time 10:18 Rev Time 0.00
Received By rregueir Date 2010-01-07 Time 10:07 Sent To  
Notes
2010-01-07 10:19:40IMPACT FEE STAMP APPLIED TO CITY/PERMIT RECORD SET OF
 PLANS.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2010-01-05 Cont ID  
Sent By jwitmer Date 2010-01-05 Time 17:14 Rev Time 0.00
Received By jwitmer Date 2010-01-05 Time 17:14 Sent To  
Notes
2010-01-05 17:15:20BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2010-01-05 Cont ID  
Sent By rregueir Date 2010-01-05 Time 17:02 Rev Time 0.00
Received By rregueir Date 2010-01-05 Time 16:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-12-09 Cont ID  
Sent By rregueir Date 2009-12-09 Time 16:46 Rev Time 0.00
Received By rregueir Date 2009-12-09 Time 16:46 Sent To  
Notes
2009-12-09 17:06:05REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-1 SHOWS FRESH AIR INTAKES LOCATED DIRECTLY
 ADJACENT TO THE ALLEY IN THE BACK OF THE BUILDING.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET HORIZONTALLY FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT SOURCE, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS IN ACCORDANCE WITH FBC-M
 401.4.1.
  
 2. PAGE M-1 SHOWS A DETAIL FOR A TANKLESS WATER HEATER
 AND VENT. THE LOCATION OF THE "TERMIATOR VENT" IS NOT
 SHOWN ON THE PLANS. ALSO, THE DETAIL SHOWS THE VENT
 TERMINATING IN A LOUVER. PROVIDE MANUFACTURER'S
 INSTRUCTIONS SHOWING THIS AS AN ACCEPTABLE MEANS OF
 VENT TERMINATION IN ACCORDANCE WITH FBC-FG 304.1.
 NOTE: WH VENT CAN NOT PASS THROUGH A PLENUM PER FBC-M
 601.5.
  
 3. PLANS FOR KITCHEN HOOD AND WALK-IN COOLERS SHALL BE
 SUBMITTED SEPARATELY WITH SEPARATE PERMIT APPLICATIONS.
 NOTE: THE SHAFT FOR THE KITCHEN EXHAUST DUCT MUST BE
 INDEPENDENT AND USED FOR NO PURPOSE OTHER THAN THE
 KITCHEN EXHAUST GREASE DUCT PER FBC-M 506.3.10.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-12-30 Cont ID  
Sent By kstevens Date 2009-12-30 Time 18:36 Rev Time 0.00
Received By kstevens Date 2009-12-30 Time 18:36 Sent To  
Notes
2009-12-30 18:41:00 
  
 PASSED/PROVISO:
  
 REVISION REQUIRED,
  
 SHTS P-1 & P-2
 TWO WAY CLEANOUTS ARE REQUIRED AT THE INLET AND THE
 OUTLET OF THE GREASE INTERCEPTOR.
 HORIZONTAL DRY VENTS ARE NOT APPROVED PER SECTION
 905.3. TWICE AT BAR #1 AND ONCE AT BAR #2.
 A VENT IS REQUIRED FOR THE FLOOR SINK AT THE ICE
 MACHINE. TABLE 906.1.
  
  
  
 .

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-12-02 Cont ID  
Sent By kstevens Date 2009-12-02 Time 14:41 Rev Time 0.00
Received By kstevens Date 2009-12-01 Time 18:47 Sent To  
Notes
2009-12-02 16:43:40DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 CITY WPB CODE OF ORDINANCES
  
 1. SHT P-1 THE GREASE INTERCEPTOR SHALL BE APPROVED.
 PLEASE SUBMIT THE MANUF. SPECIFICATION & INSTALLATION
 SHEETS. SECTION 1003.2.
  
 2. SHT P-1 THE GREASE INTERCEPTOR SHALL NOT BE LOCATED
 IN THE FOOD PREP AREA. ARTICLE III SECTION
 90-124(7)(B).
  
 3. SHT P-1 THE GREASE INTERCEPTOR SHALL BE SIZED
 ACCORDING TO TABLE 1003.5.1. THE FOLLOWING INFORMATION
 IS REQUIRED:
 A. NUMBER OF SEATS IN THE DINING AREA.
 B. GALLONS OF WASTE PER SEAT. (25 OR 10) SEE TABLE.
 C. NUMBER OF HOURS RESTAURANT IS OPEN.
 D. LOADING FACTOR (.75).
  
 4. SHTS P-1 & P-2 WASTE THAT DO NOT REQUIRE TREATMENT
 OR SEPARATION SHALL NOT BE DISCHARGED INTO ANY
 INTERCEPTOR OR SEPARATOR. SECTIONS 1003.2 & 1003.3.1.
 REMOVE THE ICE MAKER AND THE CONDENSATE FROM THE
 WALK-IN COOLER AND CONNECT TO THE SANITARY SYSTEM.
  
 5. SHT P-1 SHOWS 4 WATER FALL FIXTURES. PLEASE INDICATE
 IF THERE WILL BE WATER SUPPLY LINE CONNECTING TO THE
 FIXTURES. IF SO BACKFLOW PREVENTION IS REQUIRED PER
 SECTION 608.2. PLEASE CLARIFY HOW THE WATER FALL
 FIXTURE WILL BE FILLED WITH WATER.
  
 6. SHT P-2 H & C WATER RISER DIAGRAM SHOWS WHAT APPEARS
 TO BE AIR CHAMBERS AT EACH FIXTURE. AIR CHAMBERS ARE
 NOT APPROVED. PLEASE DELETE FROM RISER DIAGRAM. PDI-WH
 201. WATER HAMMER ARRESTORS ARE REQUIRED AND THE DISH
 WASHER AND ICE MAKER PER SECTION 604.9 PLEASE SHOW THE
 REQUIRED WATER HAMMER ARRESTORS.
  
 7.SHT P-2 THE GREASE SYSTEM IS NOT VENTED. SECTION
 901.2. PLEASE SHOW THE VENT FOR THE SYSTEM. SECTION
 912.2.
  
 8. SHT P-2 SANITARY RISER DIAGRAM. THE BRANCH LINE FOR
 THE WATER CLOSET & SUSHI BAR IS NOT VENTED AS WELL AS
 THE BRANCH LINE TO THE EXPRESSO MACHINE/3 COMPARTMENT
 SINK. SECTION 901.2. PLEASE SHOW VENTS.
  
 9. SUBMIT THE FLOW RATE FOR THE FLOOR DRAIN, THE 3
 COMPARTMENT SINK AND THE MOP SINK. SECTION 1003.3.4.2.
  
 10. SHT P-2 SHOWS NO SUPPLY OR DRAINAGE FOR THE
 DISHWASHER. PLEASE CLARIFY. SECTIONS 601.1 & 701.1.
 PLEASE CLARIFY.
  
 11. SHTS P-1 & P-2 BARS #1 & #2 SHOWS NO DRAINAGE FROM
 THE ICE WELLS. PLEASE CLARIFY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2009-12-07 Cont ID  
Sent By aaponte Date 2009-12-07 Time 14:37 Rev Time 0.00
Received By aaponte Date 2009-12-07 Time 14:37 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy