Plan Review Details - Permit 09110455
Plan Review Stops For Permit 09110455
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-11-19 Cont ID  
Sent By jgomez Date 2009-11-19 Time 16:01 Rev Time 0.00
Received By jgomez Date 2009-11-19 Time 16:01 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-11-19 Cont ID  
Sent By jgomez Date 2009-11-19 Time 11:08 Rev Time 0.00
Received By jgomez Date 2009-11-19 Time 11:08 Sent To PC
Notes
2009-11-19 11:29:44RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDING TO MIAMI-DADE PRODUCT APPROVAL WEBSITE NOA
 07-1203.01 SUBMITTED WAS SUPERSEDED. SEE MIAMI-WEBSITE
 AND DOWNLOAD CURRENT NOA. NEED TO PROVIDE 2 COPIES OF
 CURRENT NOA.
  
 2- PROVIDE COMPLETE NOA, NOT JUST THE PAGES SHOWING THE
 ASSEMBLY TO BE USED. PROVIDE THE FIRST PAGES OF THE NOA
 SHOWING ALL THE APPROVED COMPONENTS AND INSULATION AND
 THE LAST PAGE SHOWING THE GENERAL LIMITATION OF THE
 PRODUCT.
  
 3- CLEARLY IDENTIFY WHICH BASE SHEET FASTENING OPTION
 IS GOING TO BE USED ON THE SELECTED ASSEMBLY.
  
 4- IF THE SELECTED ASSEMBLY FASTENING OPTION IS LIMITED
 BY GENERAL LIMITATION #7, THEN NEED TO PROVIDE THE
 PERIMETER AND CORNER AREAS NAIL ENHANCING RAS 117
 CALCULATIONS. SUCH CALCULATIONS NEED TO BE SIGNED AND
 SEALED AS REQUIRED BY GENERAL LIMITATION #7 OF THE NOA
 PROVIDED.
 ***NOTE: ASSEMBLIES LIMITED BY GENERAL LIMITATION #9
 MAY NOT BE USED BECAUSE THEY DON'T MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301 OF 2007 FLORIDA
 RESIDENTIAL CODE FOR PERIMETER AND CORNER AREAS AND
 THIS LIMITATION DOESN'T ALLOW NAIL ENHANCING.
  
 5- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 *NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2009-11-18 Cont ID  
Sent By swurafti Date 2009-11-18 Time 12:45 Rev Time 0.00
Received By swurafti Date 2009-11-18 Time 12:45 Sent To  
Notes
2009-11-18 12:48:57HISTORIC APPROVED BY JPAPA


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved