| 2009-11-19 11:29:44 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST. |
| | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- ACCORDING TO MIAMI-DADE PRODUCT APPROVAL WEBSITE NOA |
| | 07-1203.01 SUBMITTED WAS SUPERSEDED. SEE MIAMI-WEBSITE |
| | AND DOWNLOAD CURRENT NOA. NEED TO PROVIDE 2 COPIES OF |
| | CURRENT NOA. |
| | |
| | 2- PROVIDE COMPLETE NOA, NOT JUST THE PAGES SHOWING THE |
| | ASSEMBLY TO BE USED. PROVIDE THE FIRST PAGES OF THE NOA |
| | SHOWING ALL THE APPROVED COMPONENTS AND INSULATION AND |
| | THE LAST PAGE SHOWING THE GENERAL LIMITATION OF THE |
| | PRODUCT. |
| | |
| | 3- CLEARLY IDENTIFY WHICH BASE SHEET FASTENING OPTION |
| | IS GOING TO BE USED ON THE SELECTED ASSEMBLY. |
| | |
| | 4- IF THE SELECTED ASSEMBLY FASTENING OPTION IS LIMITED |
| | BY GENERAL LIMITATION #7, THEN NEED TO PROVIDE THE |
| | PERIMETER AND CORNER AREAS NAIL ENHANCING RAS 117 |
| | CALCULATIONS. SUCH CALCULATIONS NEED TO BE SIGNED AND |
| | SEALED AS REQUIRED BY GENERAL LIMITATION #7 OF THE NOA |
| | PROVIDED. |
| | ***NOTE: ASSEMBLIES LIMITED BY GENERAL LIMITATION #9 |
| | MAY NOT BE USED BECAUSE THEY DON'T MEET THE DESIGN |
| | PRESSURES REQUIRED BY SEC. R301 OF 2007 FLORIDA |
| | RESIDENTIAL CODE FOR PERIMETER AND CORNER AREAS AND |
| | THIS LIMITATION DOESN'T ALLOW NAIL ENHANCING. |
| | |
| | 5- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | *NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |