Plan Review Details - Permit 09110374
Plan Review Stops For Permit 09110374
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-21 Cont ID  
Sent By jwitmer Date 2009-12-21 Time 13:05 Rev Time 0.55
Received By jwitmer Date 2009-12-21 Time 13:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2009-12-08 Cont ID  
Sent By jwitmer Date 2009-12-08 Time 16:43 Rev Time 0.00
Received By jwitmer Date 2009-12-08 Time 16:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-12-22 Cont ID  
Sent By btrobaug Date 2009-12-22 Time 14:42 Rev Time 0.00
Received By btrobaug Date 2009-12-22 Time 13:54 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-11-30 Cont ID  
Sent By btrobaug Date 2009-11-30 Time 13:34 Rev Time 0.00
Received By btrobaug Date 2009-11-30 Time 11:40 Sent To  
Notes
2009-11-30 13:23:32 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 1} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1 SEE.13-415.AB.2 EXTERIOR LIGHTING.
 SHOW COMPLIANCE ON THE PLAN. THIS CAN BE DEMONSTRATED
 ON THE PLANS INDICATING THE WATTAGES OF THE LUMINAIRES
 CHOSEN FOR THE PROJECT CONFORM TO THE DENSITY
 REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE SCHEDULE
 TO CORRELATE WITH THE ONES IN THE CALCULATIONS.
  
 2} THE 2008 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 1 OCTOBER 2009. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 3} THE GROUNDING ELECTRODE CONDUCTOR MUST BE A MINIMUM
 OF 1/0 PER 250.66
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-12-21 Cont ID  
Sent By mawillia Date 2009-12-21 Time 15:37 Rev Time 0.00
Received By mawillia Date 2009-12-21 Time 15:31 Sent To  
Notes
2009-12-21 15:37:35*****APPROVED******
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS 1 AND 3 WERE STAMPED,
 INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-12-07 Cont ID  
Sent By mawillia Date 2009-12-07 Time 12:18 Rev Time 0.00
Received By mawillia Date 2009-12-07 Time 11:54 Sent To  
Notes
2009-12-07 12:16:59*****FIRE-STAMPING NEEDED******
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE FOLLOWING HAVE BEEN ACKNOWLEDGED:
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241- 2004
 EDITION.
  
 2. THE OTHER TRADES PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-07-13 Cont ID  
Sent By vmolina Date 2010-05-27 Time 10:25 Rev Time 0.00
Received By vmolina Date 2010-05-27 Time 10:25 Sent To  
Notes
2010-05-27 10:31:34B-17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-12-16 Cont ID  
Sent By lmartine Date 2009-12-15 Time 19:02 Rev Time 0.00
Received By lmartine Date 2009-12-15 Time 19:02 Sent To  
Notes
2009-12-16 19:06:56B--4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-12-16 Cont ID  
Sent By jwitmer Date 2009-12-08 Time 16:39 Rev Time 0.00
Received By lmartine Date 2009-11-18 Time 09:15 Sent To  
Notes
2009-11-18 09:16:00B 11

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-12-22 Cont ID  
Sent By kstevens Date 2009-12-22 Time 08:23 Rev Time 0.00
Received By kstevens Date 2009-12-22 Time 08:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-12-07 Cont ID  
Sent By kstevens Date 2009-12-07 Time 09:52 Rev Time 0.00
Received By kstevens Date 2009-12-07 Time 09:52 Sent To  
Notes
2009-12-07 09:58:04DENIED
 REFERENCE:
 FBC-2007 PLUMBING
  
 1. SHT 1 SANITARY ISOMETRIC. RISER DIAGRAM. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. AND ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT. SECTION 909.1. PLEASE SUBMIT AN ISOMETRIC
 SHOWING THE CORRECT CONNECTION FROM THE SERVICE SINK
 AND DRINKING FOUNTAIN TO THE BUILDING DRAIN.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  